GE RX3i PROFINET Скачать руководство пользователя страница 11

IC695PNC001-AJ PROFINET Controller Module

 

11 

 

GFK-2573K

 

Restriction/Open Issues 

Description 

"telnetd" command response 

The CLI does not echo the new number of max connections in its response to the 

telnetd <maxconnections>

 command. However, the command still functions properly, 

and updates the maximum number of telnet connections. 

"log details" command response 

When displaying numerous local log table entries using the 

log details

 command, 

sometimes erroneous blank characters appear within the display. Use the 

log details 

<log entry number>

 command to view the disrupted log table entry. Example: 

log 

details 99

"term" command response 

Occasionally, the CLI does not respond to the "term" command. To recover, restart the 

terminal emulation program. 

 

Содержание RX3i PROFINET

Страница 1: ...ation via the micro USB port or using telnet Note The USB port is for system setup and diagnostics only It is not intended for permanent connection Support for star ring and daisy chain line network t...

Страница 2: ...Control 10 100 1000 Mbps Maximum I O Memory 128 Kbytes of combined input output memory per PROFINET Controller CPU Status Bits 32 PROFINET I O Device Data Update Rates on the PROFINET LAN Configurable...

Страница 3: ...t be installed in an ultimate enclosure that is manufactured to provide safety As a minimum the enclosure shall provide a degree of protection against solid objects as small as 12mm e g fingers This e...

Страница 4: ...tion or is not operational 8 Port4 SFP OK Indicates the health of the SFP plugged in port 4 1 indicates that the SFP matches configuration and is operational 0 indicates that either the SFP does not m...

Страница 5: ...e RX3i system using a Universal Backplane such as IC695CHS007 CHS012 or CHS016 The PNC supports insertion removal while power is applied to the system hot swap This includes backplane power and field...

Страница 6: ...such as Hyperterm The PNC is provided with a driver install application that can be used to enable a computer to communicate with a PNC via its USB port For details on using the Command Line Interfac...

Страница 7: ...res and Enhancements on page 8 IC695PNC001 AF 1 23 Aug 2013 Corrects issue storing PROFINET device configuration greater than 64K bytes in size For details see GFK 2573F IC695PNC001 AE 1 22 Jul 2013 C...

Страница 8: ...0 CPE310 CPE305 Boot Firmware Release 7 10 CRU320 Primary Firmware Release 8 00 CRU320 Boot Firmware Release 5 10 Other CPU models are not supported Programmer version requirements RX3i PNC001 Release...

Страница 9: ...ware configuration or the current hardware configuration in the system is cleared prior to storing a new configuration If the controller is Faulted clear the I O Fault Table to recover Otherwise no ad...

Страница 10: ...he failover occurs It is not recommended to use the PNC reset button in a normally operating system If the reset button must be used it is recommended to first attempt a brief press and release of the...

Страница 11: ...perly and updates the maximum number of telnet connections log details command response When displaying numerous local log table entries using the log details command sometimes erroneous blank charact...

Страница 12: ...t case ring recovery time is 96ms the rate needs to be more than 96ms divided by 3 which is 32ms The next available rate after 32ms is 64ms 16ms When using an I O Update Rate of 16ms you must set the...

Страница 13: ...configurations When storing hardware configurations with more than 64 PROFINET I O Devices that include multiple PNC modules and 3rd party PROFINET I O Devices on a single network occasional Loss Add...