IC695PNC001-AJ PROFINET Controller Module

 

GFK-2573K 

Issue 

Description 

Unexpected Loss of Device faults 

Loss of Device faults for currently connected devices may appear in the PLC I/O 

Fault table and/or PNC local log when the PNC is reset via its reset pushbutton. 

Unintended operation of 

PNIO_DEV_COMM function block 

The power flow output of the PNIO_DEV_COMM function block provides validation 

of the input parameters and confirms that the PNC has locally processed the 

configuration of the specified I/O Device. As currently implemented, the power flow 

output will not turn ON until after the PNC has made its first attempt to connect to 

the specified I/O Device. Therefore, we recommend the user not rely on power flow 

output for parameter validation. 

IOC SW Fault with large configurations 

When storing a configuration to the PNC that is close to the upper limit of the 

controlling PLC’s user memory, the store may fail with an IOC SW Fault logged in 

the PLC’s I/O Fault table. The work-around to resolve this issue is to clear the PLC’s 

existing configuration and store the configuration again. 

PNC's restart button Push and Hold 
behavior takes up to 1 second for CRU320 
to detect that PNC is no longer available 

When the PNC reset button is held down for more than 1 second, the CPU can take 

up to 1 second to detect the loss of the PNC (after the PNC module resets). This 

causes a delay in the CPU detecting the Loss of IOC, and in taking the appropriate 

fault actions (setting point faults, stopping the controller if Loss of or Missing I/O 

Controller faults are configured as Fatal, etc.) 
In a Hot Standby Redundancy System, if the system is synchronized and the PNC in 

question is in the active unit, this also causes a delay in the redundant system 

failing over to the backup unit. If this delay exceeds the Redundancy Data Hold 

Time (RDHT) for a given I/O Device, that IO Device will disconnect from the backup 

unit before the failover occurs. 
It is not recommended to use the PNC reset button in a normally operating system. 

If the reset button must be used, it is recommended to first attempt a brief press 

and release of the PNC reset button (the PNC should reset as soon as the button is 

released). Only if the first attempt fails should the PNC button be depressed until the 

PNC resets (approximately 2-3 seconds). 

Breaking and reconnecting an MRP ring 
by pulling either of the two MRM ports of 
the PNC causes extra ring open/close 
faults 

In some cases, if the network is broken and repaired at either of the two ring ports 

of a PNC configured to be the MRM, extra I/O Bus Fault-Redundant Ethernet 

network ring broken (open) and I/O Bus Fault-Redundant Ethernet network ring 

okay (closed) faults are logged in both the I/O Fault Table and the PNC Local Log 

when the ring is repaired. 
These additional faults can safely be ignored as long as the last fault to be logged is 

I/O Bus Fault-Redundant Ethernet network ring okay (closed). 
Additional verification of ring status can be obtained by issuing a 

show rdnMedia

 

command using the PNC’s CLI interface. 

 

Restrictions and Open Issues related to the Command Line Interface 

Restriction/Open Issues 

Description 

Invalid help response for invalid CLI 

commands 

Occasionally, the CLI will return invalid help suggestions if the user attempts to get 

help on an invalid command by using the question mark key. Attempting to issue the 

command based on this help text will result in an “Error: Bad command” response 

from the CLI. 
Use the 

help

 command to view a list of available commands. 

For more information on available CLI commands, please refer to the 

PACSystems 

RX3i High-Speed I/O LAN Command Line Interface Manual,

 GFK-2572A. 

Page function not available 

The output paging function, as described in the 

shConfig

 command, is not currently 

functioning. 

Response to invalid command entry 

The error message displayed in response to an invalid show port help command does 

not provide useful information. Example: 

show port fdp

 help is an invalid command. 

To see a list of valid parameters for the 

show port 

command, type 

show port ?

 

 

Содержание RX3i PROFINET

Страница 1: ...ation via the micro USB port or using telnet Note The USB port is for system setup and diagnostics only It is not intended for permanent connection Support for star ring and daisy chain line network t...

Страница 2: ...Control 10 100 1000 Mbps Maximum I O Memory 128 Kbytes of combined input output memory per PROFINET Controller CPU Status Bits 32 PROFINET I O Device Data Update Rates on the PROFINET LAN Configurable...

Страница 3: ...t be installed in an ultimate enclosure that is manufactured to provide safety As a minimum the enclosure shall provide a degree of protection against solid objects as small as 12mm e g fingers This e...

Страница 4: ...tion or is not operational 8 Port4 SFP OK Indicates the health of the SFP plugged in port 4 1 indicates that the SFP matches configuration and is operational 0 indicates that either the SFP does not m...

Страница 5: ...e RX3i system using a Universal Backplane such as IC695CHS007 CHS012 or CHS016 The PNC supports insertion removal while power is applied to the system hot swap This includes backplane power and field...

Страница 6: ...such as Hyperterm The PNC is provided with a driver install application that can be used to enable a computer to communicate with a PNC via its USB port For details on using the Command Line Interfac...

Страница 7: ...res and Enhancements on page 8 IC695PNC001 AF 1 23 Aug 2013 Corrects issue storing PROFINET device configuration greater than 64K bytes in size For details see GFK 2573F IC695PNC001 AE 1 22 Jul 2013 C...

Страница 8: ...0 CPE310 CPE305 Boot Firmware Release 7 10 CRU320 Primary Firmware Release 8 00 CRU320 Boot Firmware Release 5 10 Other CPU models are not supported Programmer version requirements RX3i PNC001 Release...

Страница 9: ...ware configuration or the current hardware configuration in the system is cleared prior to storing a new configuration If the controller is Faulted clear the I O Fault Table to recover Otherwise no ad...

Страница 10: ...he failover occurs It is not recommended to use the PNC reset button in a normally operating system If the reset button must be used it is recommended to first attempt a brief press and release of the...

Страница 11: ...perly and updates the maximum number of telnet connections log details command response When displaying numerous local log table entries using the log details command sometimes erroneous blank charact...

Страница 12: ...t case ring recovery time is 96ms the rate needs to be more than 96ms divided by 3 which is 32ms The next available rate after 32ms is 64ms 16ms When using an I O Update Rate of 16ms you must set the...

Страница 13: ...configurations When storing hardware configurations with more than 64 PROFINET I O Devices that include multiple PNC modules and 3rd party PROFINET I O Devices on a single network occasional Loss Add...