24VRECT ACC

BLUE    WHITE

MASTER

RED     BLACK    WHITE

24VAC POWER

RED     BLACK

WARN
  YES
  NO

AUTO ON
  YES
  NO

OCCUPIED

RED       WHITE

0

*The 24 volt AC inputs can be used if connecting directly to a transformer.

24 Volt Power Inputs

The RSP12 can be

powered through the

24 volt rectified

terminals on the

Lighting Automation
Panel motherboard*

Master Switch Input
Master ON/OFF control
for all connected relays

12 Individual
Relay Outputs
Connect up to 3 relays
wired in parallel per
output

“Auto On” Function
Can turn on all lights
automatically at the start
of normal working
hours

“Time Delay” Function

After hours, any

individual switch over-

ride will automatically

be turned off if time
delay is set from 15

minutes to 2 hours

12 Individual

Switch Inputs

Accept any 2- or

3-wire momentary

or maintained

dry-contact

switch

“Occupied” Contact

Connected to a

timeclock or BAS,

indicates when a

building is operating

under normal working

hours (closed contact)

or after hours (open

contact). Connection

and scheduling

determine when other

functions will be

enabled

“Warn” Function
Five minutes before the
RSP12 is about to turn
relays OFF at the end of
normal working hours or
at the end of a time
delay, warns occupants
by blinking the lights

Содержание RSP12

Страница 1: ...NTROLS COPYRIGHT 1995 437D687 REV 0 RED BLACK BLUE R L Y 2 RED BLACK BLUE R L Y 3 RED BLACK BLUE R L Y 4 RED BLACK BLUE R L Y 5 RED BLACK BLUE R L Y 6 RED BLACK BLUE R L Y 7 RED BLACK BLUE R L Y 8 RED BLACK BLUE R L Y 9 RED BLACK BLUE R L Y 1 0 RED BLACK BLUE R L Y 1 1 RED BLACK BLUE R L Y 1 2 ASM 437D688G RED BLACK WARN YES NO TIME DELAY AUTO ON YES NO BLUE S W T 1 2 RED BLACK WHITE S W T 1 1 RED...

Страница 2: ...ation Panel motherboard Master Switch Input Master ON OFF control for all connected relays 12 Individual Relay Outputs Connect up to 3 relays wired in parallel per output Auto On Function Can turn on all lights automatically at the start of normal working hours Time Delay Function After hours any individual switch over ride will automatically be turned off if time delay is set from 15 minutes to 2...

Страница 3: ...tion Panel LAP or in an Accessory Cabinet near a Lighting Automation Panel Installation in a Lighting Automation Panel A complete LAP assembly includes the following TLC components Tub RTUB12 24 or 48 Cover RCOV12xx 24xxx or 48xxx Interior RINTER0012RC 0024RC or 0048RC Power Supply RPWRxxx Relays RR7P or RR9P RINTER0012RC and 0024RC accept one RSP12 RINTER0048RC accepts one or two Details for asse...

Страница 4: ...after hours OPEN contact Properly connecting and scheduling the Occupied contact determines when other functions will be enabled Time Delay If the Time Delay function is set when an occupant turns on a switch after hours Occupied contact OPEN the RSP12 will turn off the lights again after a predetermined amount of time Each occupant override will have its own time delay Set the Time Delay dial as ...

Отзывы: