4
Installation Instructions
ELECTRICAL CONNECTIONS
You must use a 3-wire, single-phase A.C.
208Y/120 Volt or 240/120 Volt, 60 hertz
electrical system.
If the electrical service provided does not
meet the above specifications, have a
licensed electrician install an approved outlet.
Use only a 3-conductor or a 4-conductor
UL-listed range cord. These cords may be
provided with ring terminals on wire and
a strain relief device.
A range cord rated at 40 amps with 125/250
minimum volt range is required. A 50 amp
range cord is not recommended but if used,
it should be marked for use with nominal
1
3
⁄
8
″
diameter connection openings. Care
should be taken to center the cable and
strain relief within the knockout hole to keep
the edge from damaging the cable.
•
Because range terminals are not accessible
after range is in position, flexible service
conduit or cord must be used.
NOTE:
If conduit is being used, go to Step 3D
and then to Step 6 or 7.
•
On some models, a filter capacitor may be
connected between the black and white
leads on the junction block.
ALL NEW CONSTRUCTIONS,
MOBILE HOMES AND
INSTALLATIONS WHERE
LOCAL CODES DO NOT
ALLOW GROUNDING
THROUGH NEUTRAL,
REQUIRE A 4-CONDUCTOR
UL-LISTED RANGE CORD.
ELECTRICAL REQUIREMENTS
CAUTION:
For personal safety,
do not use an extension cord with this
appliance. Remove house fuse or open circuit
breaker before beginning installation.
This appliance must be supplied with the
proper voltage and frequency, and connected
to an individual properly grounded branch
circuit, protected by a circuit breaker or fuse
having amperage as specified on the rating
plate. The rating plate is located above the
storage drawer on the oven frame or on the
side of the drawer frame.
We recommend you have the electrical wiring
and hookup of your range connected by a
qualified electrician. After installation, have
the electrician show you where your main
range disconnect is located.
Check with your local utilities for electrical
codes which apply in your area. Failure to
wire your oven according to governing codes
could result in a hazardous condition. If there
are no local codes, your range must be wired
and fused to meet the requirements of the
National Electrical Code, ANSI/NFPA No. 70–
Latest Edition. You can get a copy by writing:
National Fire Protection Association
Batterymarch Park
Quincy, MA 02269
Effective January 1, 1996, the National
Electrical Code requires that new construction
(not existing) utilize a 4-conductor connection
to an electric range.
When installing an electric range in new
construction, follow Steps 3 and 5 for 4-wire
connection.
Location of
model rating
plate
Содержание Profile JB900TKWW
Страница 10: ...10 Notes...
Страница 11: ...11 Notes...
Страница 12: ...12 Printed in the United States...