6–22
PQMII POWER QUALITY METER – INSTRUCTION MANUAL
CHAPTER 6: MONITORING
6.4
A3 Power Analysis
6.4.1
Power Quality
PATH: ACTUAL VALUES
Ö
A3 POWER ANALYSIS
ÖØ
POWER QUALITY VALUES
•
Ia/Ib/Ic CREST FACTOR
: The crest factor describes how much the load current can
vary from a pure sine wave while maintaining the system’s full rating. A completely
linear load (pure sine wave) has a crest factor of
(1 /0.707), which is the ratio of the
peak value of sine wave to its RMS value. Typically, the crest factor can range from
to 2.5.
•
Ia/Ib/Ic THDF
: The Transformer Harmonic Derating Factor (THDF), also known as
CBEMA factor, is defined as the crest factor of a pure sine wave (
) divided by the
measured crest factor. This method is useful in cases where lower order harmonics are
dominant. In a case where higher order harmonics are present, it may be necessary
to use a more precise method (K-factor) of calculating the derating factor. This method
also does not take into consideration the losses associated with rated eddy current in
the transformer. The EnerVista PQMII Setup Software provides the K-factor method of
calculating the derating factor, which is defined on a per unit basis as follows:
(EQ 6.3)
where:
I
h
= RMS current at harmonic
h
, in per unit of rated RMS load current
6.4.2
THD
PATH: ACTUAL VALUES
Ö
A3 POWER ANALYSIS
ÖØ
TOTAL HARMONIC DISTORTION
POWER QUALITY
[
Z
]
VALUES
Ia CREST FACTOR =
1.233
MESSAGE
Ib CREST FACTOR =
1.008
MESSAGE
Ic CREST FACTOR =
1.000
MESSAGE
Ia THDF = 0.944
MESSAGE
Ib THDF = 0.999
MESSAGE
Ic THDF = 0.988
2
2
2
K
I
h
2
h
2
×
h
1
=
h
max
∑
=
TOTAL HARMONIC
[
Z
]
DISTORTION
PHASE A CURRENT THD=
5.3%
MESSAGE
PHASE B CURRENT THD=
7.8%
Содержание PQMII
Страница 8: ...TOC VI PQMII POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS...
Страница 12: ...1 4 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 1 OVERVIEW FIGURE 1 2 Feature Highlights...
Страница 19: ...CHAPTER 1 OVERVIEW PQMII POWER QUALITY METER INSTRUCTION MANUAL 1 11 FIGURE 1 9 Trace Memory Capture...
Страница 58: ...3 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 3 OPERATION...
Страница 78: ...4 20 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE FIGURE 4 6 Voltage Disturbance Recorder...
Страница 84: ...4 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE...
Страница 170: ...6 32 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 6 MONITORING...
Страница 196: ...7 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 7 APPLICATIONS...
Страница 198: ...8 2 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 8 WARRANTY...
Страница 208: ...A 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL APPENDIX A...
Страница 216: ...B VIII PQM POWER QUALITY METER INSTRUCTION MANUAL CHAPTER B INDEX...