APPENDIX A
PQMII POWER QUALITY METER – INSTRUCTION MANUAL
A–5
A.1.5 Additions to Modbus Memory Map
The following two sections are added to the Modbus Memory Map for Mod 506. For
additional information on Modbus, refer to
.
The following memory map format has also been added:
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP VALUEUNITS and
SCALE
FOR-MAT FACTORY DEFAULT
MOD 506
ACTUAL
VALUES
0E10
Step 1 Pickup Timer
---
---
0.1 x
F1
---
0E11
Step 2 Pickup Timer
---
---
0.1 x
F1
---
0E12
Step 3 Pickup Timer
---
---
0.1 x
F1
---
0E13
Step 4 Pickup Timer
---
---
0.1 x
F1
---
0E14
Step 1 Disable Timer
---
---
0.1 x
F1
---
0E15
Step 2 Disable Timer
0.1 x
F1
---
0E16
Step 3 Disable Timer
---
---
0.1 x
F1
---
0E17
Step 4 Disable Timer
---
---
0.1 x
F1
---
0E18
System Stabilization
---
---
0.1 x
F1
---
0E19
Low Voltage Detect
---
---
0.1 x
F1
---
MOD 506
SETPOINTS
1300
Step 1 Relay
0 to 4
1
---
F1
0 = OFF
1301
Step 1 Pickup Level
1 to 65000 1
kvar
F1
6000=600.0 kvar
1302
Step 1 Dropout Level
–32000 to
32000
1
kvar
F2
0=0.0 kvar
1303
Step 1 Pickup Delay
1 to 600
1
min
F1
10=1.0 min
1304
Step 1 Disable Time
1 to 600
1
min
F1
50=5.0 min
1305
Step 2 Relay
0 to 4
1
---
F1
0 = OFF
1306
Step 2 Pickup Level
1 to 65000 1
kvar
F1
6000=600.0 kvar
1307
Step 2 Dropout Level
–32000 to
32000
1
kvar
F2
0=0.0 kvar
1308
Step 2 Pickup Delay
1 to 600
1
min
F1
10=1.0 min
1309
Step 2 Disable Time
1 to 600
1
min
F1
50=5.0 min
130A
Step 3 Relay
0 to 4
1
---
F1
0 = OFF
130B
Step 3 Pickup Level
1 to 65000 1
kvar
F1
6000=600.0 kvar
130C
Step 3 Dropout Level
–32000 to
32000
1
kvar
F2
0=0.0 kvar
130D
Step 3 Pickup Delay
1 to 600
1
min
F1
10=1.0 min
130E
Step 3 Disable Time
1 to 600
1
min
F1
50=5.0 min
130F
Step 4 Relay
0 to 4
1
---
F1
0 = OFF
1310
Step 4 Pickup Level
1 to 65000 1
kvar
F1
6000=600.0 kvar
1311
Step 4 Dropout Level
–32000 to
32000
1
kvar
F2
0=0.0 kvar
1312
Step 4 Pickup Delay
1 to 600
1
min
F1
10=1.0 min
1313
Step 4 Disable Time
1 to 600
1
min
F1
50=5.0 min
1314
System Stabilization
1 to 600
1
min
F1
50=5.0 min
1315
Low Voltage Detect
Level
30 to
65000
1
V
F1
100 V
1316
Low Voltage Detect
Delay
5 to 6000 1
s
F1
10=1.0 s
1317
Step Sequence
0 to 23
1
---
F42
0=“1,2,3,4”
CODE
DESCRIPTION
BITMAS
K
F42
Step Sequence Priority
FFFF
0 = “1, 2, 3, 4”
---
1 = “1, 2, 4, 3”
---
2 = “1, 3, 2, 4”
---
Содержание PQMII
Страница 8: ...TOC VI PQMII POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS...
Страница 12: ...1 4 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 1 OVERVIEW FIGURE 1 2 Feature Highlights...
Страница 19: ...CHAPTER 1 OVERVIEW PQMII POWER QUALITY METER INSTRUCTION MANUAL 1 11 FIGURE 1 9 Trace Memory Capture...
Страница 58: ...3 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 3 OPERATION...
Страница 78: ...4 20 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE FIGURE 4 6 Voltage Disturbance Recorder...
Страница 84: ...4 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE...
Страница 170: ...6 32 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 6 MONITORING...
Страница 196: ...7 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 7 APPLICATIONS...
Страница 198: ...8 2 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 8 WARRANTY...
Страница 208: ...A 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL APPENDIX A...
Страница 216: ...B VIII PQM POWER QUALITY METER INSTRUCTION MANUAL CHAPTER B INDEX...