CHAPTER 2: INSTALLATION
PQMII POWER QUALITY METER – INSTRUCTION MANUAL
2–3
2.2
Electrical Configuration
2.2.1
External Connections
Signal wiring is to Terminals 21 to 51. These terminals accommodate wires sizes up to 12
gauge. Please note that the maximum torque that can be applied to terminals 21 to 51 is
0.5 Nm (or 4.4 in ·lb.). CT, VT, and control power connections are made using Terminals 1 to
20. These #8 screw ring terminals accept wire sizes as large as 8 gauge. Consult the wiring
diagrams for suggested wiring. A minimal configuration includes connections for control
power, phase CTs/VTs, and the alarm relay; other features can be wired as required.
Considerations for wiring each feature are given in the sections that follow.
Table 2–1: PQMII External Connections
Terminal
Description
Terminal
Description
VT / Control Power Row (1 to 8)
25
Analog out 4+
1
V1 Voltage input
26
Analog out 3+
2
V2 Voltage input
27
Analog out 2+
3
V3 Voltage input
28
Analog out 1+
4
Vn Voltage input
29
Switch 4 input
5
Filter ground
30
Switch 3 input
6
Safety ground
31
Switch 2 input
7
Control neutral (–)
32
Switch 1 input
8
Control live (+)
33
+24 V DC switch com
CT Row (9 to 20)
34
Aux3 relay NC
9
Phase A CT 5A
35
Aux3 relay COM
10
Phase A CT 1A
36
Aux3 relay NO
11
Phase A CT COM
37
Aux2 relay NC
12
Phase B CT 5A
38
Aux2 relay COM
13
Phase B CT 1A
39
Aux2 relay NO
14
Phase B CT COM
40
Aux1 relay NC
15
Phase C CT 5A
41
Aux1 relay COM
16
Phase C CT 1A
42
Aux1 relay NO
17
Phase C CT COM
43
Alarm relay NC
18
Neutral CT 5A
44
Alarm relay COM
19
Neutral CT 1A
45
Alarm relay NO
20
Neutral CT COM
46
Comm 1 COM
Содержание PQMII
Страница 8: ...TOC VI PQMII POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS...
Страница 12: ...1 4 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 1 OVERVIEW FIGURE 1 2 Feature Highlights...
Страница 19: ...CHAPTER 1 OVERVIEW PQMII POWER QUALITY METER INSTRUCTION MANUAL 1 11 FIGURE 1 9 Trace Memory Capture...
Страница 58: ...3 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 3 OPERATION...
Страница 78: ...4 20 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE FIGURE 4 6 Voltage Disturbance Recorder...
Страница 84: ...4 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE...
Страница 170: ...6 32 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 6 MONITORING...
Страница 196: ...7 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 7 APPLICATIONS...
Страница 198: ...8 2 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 8 WARRANTY...
Страница 208: ...A 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL APPENDIX A...
Страница 216: ...B VIII PQM POWER QUALITY METER INSTRUCTION MANUAL CHAPTER B INDEX...