Chapter 1. Introduction
GFK-2571N
May 2018
15
1.6.1
Compression
Due to the smaller memory capacities of CPE302, CPE305 and CPE310, these CPUs require "Compression"
when attaching RX3i PNS or CEP to their PROFINET configuration.
•
CPE302: User MUST use Target PLC parameter with "Compression" set to HIGH.
•
CPE305: User MUST use Target PLC parameter with "Compression" set to MODERATE.
•
CPE310: User can use Target PLC parameter "Compression" set to NORMAL.
•
All other CPUs: User can choose to use "Compression" or not.