LED
LED State
Operating State
Off
No port activity detected on USB Interface
On Red
RDSD Failure
Blinking
Red
Target name mismatch: Press same RDSD
pushbutton again to dismiss.
SYS FLT
On Red
CPU is in Stop/Faulted mode: a fatal fault has
occurred.
Off
No fatal faults detected.
CPE330 Ethernet Indicators
LED
LED State
Operating State
LINK
(upper)
On Green
The corresponding link is physically connected.
Blinking
Green
Traffic is detected at the corresponding port.
Off
No connection detected at corresponding port.
1Gbps
(lower)
On Amber
(LAN1) or
Corresponding network data speed is 1 Gbps.
On Green
(LAN2)
Off
Corresponding network data speed is 100 Mbps or
10 Mbps.
1.3.
Ethernet Ports
LAN1 connects to the uppermost RJ-45 connector. It is not switched. LAN2 connects
to the two lower RJ-45 connectors. They are switched internally. Record the IP
Address of each LAN in the space provided (Figure 1).
Each of the embedded Ethernet interfaces automatically senses the data rate
(10 Mbps or 100 Mbps or 1 Gbps), communications mode (half-duplex or full-duplex),
and cabling arrangement (straight-through or crossover) of the attached link.
GFK-2941E
May 2016
6