21 

IC695CPE400 Rackless CPU w/Field Agent Quick Start Guide 

GFK-3002A 

 

3.

 

Set the WAN interface settings appropriately for the Field Agent’s network.

 DHCP 

can be used for networks where a DHCP server is available, and a static IP 
address for networks where each device is manually assigned an address. Click 
the Save button to accept the changes. 

Note: 

The DNS servers can also be configured to be obtained automatically or 
specified statically. When using a static IP address, DNS servers must also 
be specified statically.  

4.3.3.2.

 

Configure a Network Proxy 

A Network Proxy is only required when your network architecture is configured to 
restrict access directly to the Internet. Contact your network administrator for the 
Network Proxy information. 
 
If a network HTTP/HTTPS proxy server is used to route traffic from the intranet to the 
Internet, the network proxy must be configured in the Web Console under 

Technician 

Console, Network Configuration

. To add or update a network proxy server, check the 

Содержание PACSystems RX3i CPE400

Страница 1: ...GE Automation Controls Programmable Control Products PACSystems IC695CPE400 RX3i 1 2GHz 64MB Rackless CPU w Field Agent Quick Start Guide GFK 3002A October 2017 g ...

Страница 2: ......

Страница 3: ...Storage Device RDSD 9 Hardware Installation 10 Initial Checks 10 Installation 10 Installation in Hazardous Areas 12 Connect to Power Supply 13 Grounding 14 Module Start up 15 You Will Need 15 Basic Start up Steps 16 Configuration 17 Backwards Compatibility 17 PROFINET Controller Configuration 17 Field Agent Configuration 18 4 3 1 Start the Embedded Field Agent EFA 18 4 3 2 Log into the Web Console...

Страница 4: ......

Страница 5: ...istic control with Field Agent technology delivering near real time advice through market analysis fleet and enterprise data or asset process knowledge to optimize the outcomes that today s businesses require The Predix enabled CPE400 provides reliable secure communication and analytics using either cloud based or edge based outcome optimizing apps Controls can now be programmed to dynamically inf...

Страница 6: ...idly leverage external data External monitoring may be used to analyze and optimize entire business operations The analysis can then be used to dynamically adjust real time industrial controls to align with changing business objectives in today s Industrial Internet age Supports four independent 10 100 1000 Ethernet LANs Three are located on the front panel as shown in Figure 1 LAN1 attaches via t...

Страница 7: ...dant CPUs Effective with firmware release 9 30 the CPE400 supports two independent Redundant IP addresses one for LAN1 and one for LAN2 LAN2 Redundant IP is supported when configured for Ethernet mode only Redundant IP is supported by the SRTP Server Modbus TCP Server and EGD protocols It is not possible to use Redundant IP with the OPC UA Server or with the Ethernet firmware update web page The C...

Страница 8: ...m menus It interacts with the DISP pushbutton which jogs the cursor from one menu item to the next and with the SEL pushbutton which activates the currently indicated menu item for further action The OLED display permits the user to Display Ethernet LAN Settings IPv4 address Display the PLC firmware revision Set view PLC mode and view sweep time Set the PLC mode to RUN STOP with I O Enabled Disabl...

Страница 9: ...nce Off Power is not applied or CPU has a problem Blinking All other LEDs off PLC in STOP Halt state possible watchdog timer fault If the programmer cannot connect cycle power with charged Energy Pack attached and refer to fault tables OK Blinking alternately CPU encountered a Secure Boot Error OE OE On Green Output scan is enabled Off Output scan is disabled FRC On Yellow One or more Overrides ac...

Страница 10: ...r On Green The corresponding link has been established Blinking Green Traffic is detected at the corresponding port Off No connection established at corresponding port Link Speed lower On Green Corresponding data speed is 1 Gbps or 100 Mbps Off Corresponding network data speed is 10 Mbps Bottom Ethernet Indicators EFA RJ45 Built in LED LED LED State Operating State Link Status upper On Green The c...

Страница 11: ...aces automatically senses the data rate 10 Mbps or 100 Mbps or 1 Gbps communications mode half duplex or full duplex and cabling arrangement straight through or crossover of the attached link LEDs embedded in each RJ45 connector provide indications per the table above LAN1 or LAN2 may be used to communicate with the PME programming software using the Service Request Transport Protocol SRTP a propr...

Страница 12: ...e Ports Connectors2 Field Agent Port The RJ45 port marked EFA is located on the underside of the CPE400 as shown in Figure 2 This is an Ethernet port pre configured to connect securely to the Predix cloud environment For additional information concerning use of this port refer to the PACSystems RX7i RX3i and RSTi EP CPU Reference Manual GFK 2222Y or later For more detailed information regarding Fi...

Страница 13: ...it allows the CPE400 to save its current state upon loss of power Refer to the PACSystems RX3i Rackless Energy Pack IC695ACC403 Quick Start Guide GFK 3000 for complete wiring and grounding instructions Input Power Connector If no Energy Pack is to be connected refer to Section 2 4 Otherwise refer to the PACSystems RX3i Rackless Energy Pack IC695ACC403 Quick Start Guide GFK 3000 Removable Data Stor...

Страница 14: ...agree with your order contact Customer Care Installation As shipped the CPE400 is intended for mounting on a DIN rail A panel mount adaptor is also available If panel mounting is required replace the DIN rail adaptor with the panel mount adaptor using the screws supplied with that adaptor Both adaptors attach to the rear of the CPE400 chassis using four Torx M3 screws Torque newly installed screws...

Страница 15: ...t Guide GFK 3002A 50mm 50mm 100mm 100mm Air flow adjacent device right adjacent device left adjacent device below adjacent device above 25mm Air flow max 70 C Figure 3 Thermal Requirements Figure 4 Mounting on DIN Rail Figure 5 Dismounting from DIN Rail ...

Страница 16: ...s are available mount using two screws Figure 6 or for more secure mounting mount using four screws Figure 7 Figure 6 2 screw panel mount Figure 7 4 screw panel mount Installation in Hazardous Areas Refer to the Installation and Maintenance Requirements document GFK 3004 ...

Страница 17: ...que for the three signal screws is 2 2 in Ibs 0 248Nm Secure the mating connector to the power input connector via the two captive screws provided The user supplied SELV3 power supply must supply voltage in the range of 18Vdc to 30Vdc Once the power supply cable or compatible Energy Pack ACC403 has been attached to the CPE400 and the power supply has been turned on the unit will start booting Ther...

Страница 18: ...ent conditions before serious damage can occur such as overheating of the equipment The fuse is rated for 4A continuous current Once the sensed current reaches 40A the fuse will blow after a period of 10ms to 100ms CAUTION EQUIPMENT REPAIR REQUIRED Internal components must be repaired at the factory they are not field replaceable Contact the GE support team at https ge ip force com communities CC_...

Страница 19: ...ing the compatible panel mount adaptor A computer running Proficy Machine Edition PME configuration and programming software PME Version 9 00 SIM 8 or later supports the CPE400 Version 9 50 SIM 5 is required for Hot Standby Redundancy Ethernet cable for connecting the PME programmer computer to the CPE400 Additional cables as needed to connect each port employed in the application A very small slo...

Страница 20: ...ss any buttons 5 If not previously configured configure the RX3i PLC using PME 9 00 SIM 8 or later as described in the Configuration section below Note When the ACC403 Energy Pack is powered up a finite period is required to charge it up to its operating level During this time the Energy Pack will indicate this condition via its LEDs refer to the PACSystems RX3i Rackless Energy Pack IC695ACC403 Qu...

Страница 21: ...version feature in PME Be aware of the constraints involved as will be notified in PME For instance the first PROFINET Controller in an RX3i CPU320 application will be assigned to the embedded PROFINET Controller feature of the CPE400 PROFINET Controller Configuration An Embedded PROFINET Controller may be configured on LAN2 To enable the PROFINET Controller in a CPE400 project select the CPE400 t...

Страница 22: ...onfiguration Mode as follows From the Main Menu select the FA Settings menu item From the FA Settings Menus select the Commands menu item From the Commands Menus select the Config Mode menu item Confirm entering Config Mode Configuration Mode will remain active for one hour or until the above steps are repeated to disable Configuration Mode Note Browsing to the Web Console too soon may result in s...

Страница 23: ...efault User Name predix Default Password predix2machine 7 A prompt to change the default password displays Complete the form to change the default password 8 The password complexity requirements display if the chosen password is not sufficiently complex After changing the password log in using the new password ...

Страница 24: ...ack to the login page 4 3 3 Configure the Network 4 3 3 1 EFA IP Addresses By default the Embedded Field Agent s WAN interface is set to a static address of 172 31 0 100 with a subnet mask of 255 255 0 0 To change the WAN IP address 1 Verify that the WAN Ethernet cable is connected to the IICS Cloud port EFA Port If a network proxy is needed to connect the field agent to the WAN refer to the secti...

Страница 25: ...tained automatically or specified statically When using a static IP address DNS servers must also be specified statically 4 3 3 2 Configure a Network Proxy A Network Proxy is only required when your network architecture is configured to restrict access directly to the Internet Contact your network administrator for the Network Proxy information If a network HTTP HTTPS proxy server is used to route...

Страница 26: ...ection button If the URL is reachable a Test Connection Succeeded message is displayed below the Test Connection button after the button is pressed Otherwise a message will appear indicating that the Test Connection attempt failed 4 3 3 3 Configure Time Synchronization In order for industrial data time stamping and Field Agent diagnostic information to operate reliably it is important for the Fiel...

Страница 27: ...configured a success statement will be displayed and the updated time will be displayed If the time and date was more than 20 minutes out of date prior to time synchronization occurring after pressing the Save button the Web Console session may end and an error message may be presented indicating that the session s timeout had been reached Log back into the Web Console to verify the time was updat...

Страница 28: ...f the Primary to the lower LAN3 port of the Secondary Note that no additional hardware other than the two redundant CPUs may be connected to LAN3 To enable redundancy in a CPE400 project select the CPE400 target in the PME Navigator and use the Property Inspector to change the Enable Redundancy target property to True Important Set the Background Window Timer to a minimum of 5ms in both the Primar...

Страница 29: ...ment Guide GFK 2830 PACSystems RX7i RX3i and RSTi EP CPU Programmer s Reference Manual GFK 2950 PACSystems HART Pass Through User Manual GFK 2929 PACSystems RX3i PROFINET IO Controller User Manual GFK 2571 PROFINET I O Devices Secure Deployment Guide GFK 2904 PACSystems RX3i Rackless Energy Pack IC695ACC403 Quick Start Guide GFK 3000 IC695CPE400 RX3i 1 2GHz 64MB Rackless CPU w Field Agent Importan...

Страница 30: ...rsion number of the product containing the covered binary iii your name iv your company name if applicable and v your return mailing and email address This offer is valid for three 3 years after the date of the last distribution of this particular version of this product For any code in this product covered by version 3 of the GNU General Public License GPL then this offer is valid for those who p...

Страница 31: ...regional phone numbers are available on our web site www geautomation com Copyright 2016 2017 General Electric Company All Rights Reserved Trademark of General Electric Company and or its subsidiaries All other trademarks are property of their respective holders GFK 3002A g ...

Отзывы: