GE Multilin
G60 Generator Protection System
5-119
5 SETTINGS
5.4 SYSTEM SETUP
5
b) BASIC CONFIGURATION
PATH: SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT
BASIC CONFIGURATION
PMU1
PMU 1 BASIC
CONFIGURATION
PMU 1
FUNCTION: Disabled
Range: Enabled, Disabled
MESSAGE
PMU 1 IDCODE:
1
Range: 1 to 65534 in steps of 1
MESSAGE
PMU 1 STN:
GE-UR-PMU
Range: 32-character ASCII string truncated to 16
characters if mapped into C37.118 Default: GE-UR-PMU
MESSAGE
PMU 1 SIGNAL SOURCE:
SRC 1
Range: Available signal sources
MESSAGE
PMU 1 CLASS:
CLASS M
Range: None, CLASS M, CLASS P
MESSAGE
PMU 1 FORMAT:
Integer
Range: Integer, Floating-point
MESSAGE
PMU 1 STYLE:
Polar
Range: Polar, Rectangular
MESSAGE
PMU 1 RATE:
10/sec
Range: 1/sec, 2/sec, 4/sec, 5/sec, 10/sec, 12/sec, 15/
sec, 20/sec, 25/sec, 30/sec, 50/sec, 60/sec, 100/
sec, 120/sec
MESSAGE
PMU 1 PHS-1:
Off
Range: Available synchrophasor values
MESSAGE
PMU 1 PHS-1
NAME: GE-UR-PMU-PHS-1
Range: 16 -character ASCII string
↓
MESSAGE
PMU 1 PHS-14:
Off
Range: Available synchrophasor values
MESSAGE
PMU 1 PHS-14:
NAME: GE-UR-PMU-PHS-14
Range: 16 -character ASCII string
MESSAGE
PMU 1 A-CH-1:
Off
Range: Available FlexAnalog values
MESSAGE
PMU 1 A-CH-1:
NAME: AnalogChannel1
Range: 16 -character ASCII string
↓
MESSAGE
PMU 1 A-CH-16 (16):
Off
Range: Available FlexAnalog values
MESSAGE
PMU 1 A-CH-16 (16):
NAME: AnalogChannel16
Range: 16 -character ASCII string
MESSAGE
PMU 1 D-CH-1:
Off
Range: Available FlexLogic operands
MESSAGE
PMU 1 D-CH-1
NAME: DigChannel1
Range: 16 character ASCII string
MESSAGE
PMU 1 D-CH-1
NORMAL STATE: Off
Range: Off, On
↓
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...