4–28
MM200 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
CONTROL ELEMENTS
CHAPTER 4: SETPOINTS
Power Failure Time
Range: 0 to 30 s in steps of 1 s
Default: 0.0 s
Sets the maximum measured duration of power failure time. If the mains voltage returns
within the Power Failure Time, the motors that were energized before the power failure
are automatically reconnected.
If the mains voltage does not return within this period of time, the above motors remain
disconnected and a “Trip – Power Failure” fault is generated. Once the mains voltage has
returned, the trip will be maintained until a reset command is received.
Restart Time Delay
Range: 0 to 300 s in steps of 1 s
Default: 0.0 s
After the mains voltage returns, this setting defines the time delay before the motor is
restarted.
NOTE
NOTE:
This function restarts the motor based on the stages of the startup sequence provided by
the starter type selected.