CHAPTER 1: INTRODUCTION
SPECIFICATIONS
MM200 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
1–9
Inputs specifications
DIGITAL INPUTS (LO)
Fixed pickup: ......................................................... 24 V DC
Continuous current draw:............................... 4 mA
Type: ......................................................................... opto-isolated inputs
External switch: ................................................... wet contact
Maximum input voltage:.................................. 36 V DC
DIGITAL INPUTS (HI)
Nominal voltage: ................................................. 120 V AC to 240 V AC
Recognition time:................................................ 2 cycles
Continuous current draw:............................... 4 mA @120 V AC; 8 mA @ 240 V AC
Type: ......................................................................... opto-isolated inputs
External switch: ................................................... wet contact
Voltage range: ...................................................... 65 V AC to 300 V AC
GROUND CURRENT INPUT (50:0.025)
CT primary: ............................................................ 0.5 to 15.0 A
Nominal frequency:........................................... 50 or 60 Hz
Accuracy (CBCT): ................................................. ±0.1 A (0.5 to 3.99 A)
±0.2 A (4.0 A to 15 A)
PHASE CURRENT INPUTS
Range: ...................................................................... 0.07 to 40 A (8 × CT), direct connection up to 5 A FLA
Input type:.............................................................. combined 1 A / 5 A
Frequency: ............................................................. 50 or 60 Hz
Accuracy:................................................................ ExtCT: ±2% of reading or ±1% of 8× CTPrimary, whichever is
greater
Direct: 2% of reading or ±0.1 A, whichever is greater
Withstand (at 5A nominal): ............................. 0.2 s at 100 × rated current
1.0 s at 50 × rated current
2.0 s at 40 × rated current
continuous at 3 × rated current
maximum 100 A peak
Short Circuit:.......................................................... 5000 A @ 240 V AC direct connect
100000 A @ 600 VAC with accessory external CT
THERMISTOR INPUTS
Sensor type: .......................................................... Positive temperature coefficient PTC (
R
HOT
= 100 to
30000 ohms), negative temperature coefficient NTC (
R
HOT
=
100 to 30000 ohms)
Accuracy:................................................................ ±6% of reading or ±100 ohms, whichever is greater
Outputs specifications
OUTPUT RELAYS
Configuration:....................................................... electromechanical 2 x Form-A and 1 x Form-C
Contact material: ................................................ silver-alloy
Operate time:........................................................ 10 ms
Minimum contact load: .................................... 10 mA at 5 V DC
Maximum switching rate: ............................... 300 operations per minute (no load), 30 operations per
minute (load)
Mechanical life:.................................................... 10 000 000 operations
Continuous current:........................................... 5 A at 60°C
Make and carry for 0.2s:.................................. 30 A per ANSI C37.90 (
not UL rated
)
Содержание MM200
Страница 6: ...TOC IV MM200 MOTOR MANAGEMENT SYSTEM INSTRUCTION MANUAL ...
Страница 104: ...5 4 MM200 MOTOR MANAGEMENT SYSTEM INSTRUCTION MANUAL COMMANDS CHAPTER 5 DIAGNOSTICS ...
Страница 106: ...6 2 MM200 MOTOR MANAGEMENT SYSTEM INSTRUCTION MANUAL COMMUNICATIONS INTERFACES CHAPTER 6 COMMUNICATIONS ...
Страница 110: ...A 4 MM200 MOTOR MANAGEMENT SYSTEM INSTRUCTION MANUAL REPAIRS CHAPTER A APPENDIX A ...