CHAPTER 3: CONTROL PANEL
GRAPHICAL CONTROL PANEL
MM200 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
3–11
•
Black Text = Information Message
Message can have an associated countdown timer.
When the relay is first powered up, the status page lists why the relay is not available for
service. This is not an exhaustive list of setpoints to be configured, but is a list of key items
such as FLA, CT Type, starter type and control Source, that must be configured before the
unit will be available for use. Protection values must still be configured for the motor to be
protected correctly.
Inhibits
These include Process Interlock Stop, and Field Stop.
Trips / Alarms
These trigger depending on the protection setpoints. A typical example would be;
“Overload Trip”.
Information Messages
Information pages are split into two groups
–
With navigation (shown above, as an
Enter
symbol on the right side of the
display)
–
Without navigation
When a line showing a message (with navigation) is highlighted, pressing
Enter
will take
you directly to the page in question, so that the situation can be quickly resolved. A typical
example would be “FLA not set”. Selecting this entry on the page will take you to the
\setpoints\config\motor page.
Setpoints pages
The setpoints pages are divided into five sections.
•
Config (contains basic configuration setpoints)
•
Protection (contains the protection setpoints)
•
Control (contains the control setpoints)
•
Security (contains the password security setpoints)
•
Factory (contains settings used by GE Multilin personnel for testing and calibration
purposes.)
The
Home > Setpoints
page displays a warning message concerning unexpected
performance if setpoints are improperly changed. It is recommended that all relay outputs
capable of causing damage or harm be blocked before a setpoints change is made and it
is clear the relay is performing as intended with the new setpoints.
Figure 3-11: Setpoints home page
To streamline the setpoint entry process, the MM200 will not display setpoints that are not
relevant at the specific instance. For instance, if a process interlock function is disabled, the
six setpoints associated with that interlock function will not be displayed. If all ten process
Содержание MM200
Страница 6: ...TOC IV MM200 MOTOR MANAGEMENT SYSTEM INSTRUCTION MANUAL ...
Страница 104: ...5 4 MM200 MOTOR MANAGEMENT SYSTEM INSTRUCTION MANUAL COMMANDS CHAPTER 5 DIAGNOSTICS ...
Страница 106: ...6 2 MM200 MOTOR MANAGEMENT SYSTEM INSTRUCTION MANUAL COMMUNICATIONS INTERFACES CHAPTER 6 COMMUNICATIONS ...
Страница 110: ...A 4 MM200 MOTOR MANAGEMENT SYSTEM INSTRUCTION MANUAL REPAIRS CHAPTER A APPENDIX A ...