CHAPTER 1: GETTING STARTED
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
1–35
CURRENT UNBALANCE ALARM
: “Unlatched”
ASSIGN ALARM RELAYS
: “Alarm”
CURRENT UNBALANCE ALARM PICKUP
: “10%”
CURRENT UNBALANCE ALARM DELAY
: “10 s”
CURRENT UNBALANCE ALARM EVENTS
: “On”
CURRENT UNBALANCE TRIP
: “Latched” – the output relay will remind energized until the
Reset command executed
ASSIGN TRIP RELAYS
: “Trip”
CURRENT UNBALANCE TRIP PICKUP
: “20%”
CURRENT UNBALANCE TRIP DELAY
: “5 s”
1.4.8
S7 Motor Starting
The S7 Motor Starting settings page contains additional settings used to complement the
Thermal Model. In our example, these characteristics are specified under Motor Protection
heading.
For the Acceleration Timer element, enter the following values in the
S7 MOTOR STARTING
ACCELERATION TIMER
page. Press the
MESSAGE
key after each settings is completed to
move to the next message.
ACCELERATION TIMER TRIP
: “Latched”
ASSIGN TRIP RELAYS
: “Trip”
ACCELERATION TIMER FROM START
: “13 s” – as shown in the acceleration curves at
100% voltage
For the Start Inhibit element, enter the following values in the
S7 MOTOR STARTING
START INHIBIT
page. Press the
MESSAGE
key after each settings is completed to move
to the next message.
START INHIBIT BLOCK
: “On”
TC USED MARGIN
: “25%”
With these settings, the 469 relay prevents motor starting if there is insufficient thermal
capacity for a successful motor start. Refer to
on page 5–68 for additional
information.
There is not information available to set Starts/Hour, Time Between Starts, or the Restart
Block features. Therefore, the following settings must be disabled:
JOGGING BLOCK
: “Off”
RESTART BLOCK
: “Off”
1.4.9
S8 RTD Temperature
The S8 RTD Temperature page contains the settings for the twelve (12) field programmable
RTDs that are normally used for temperature monitoring. The temperature measured by
each RTD can be compared to pickup values, and set to energize Trip or Alarm outputs.
For proper temperature monitoring, enter the RTD types in the
S8 RTD TEMPERTURE
RTD
TYPES
page. Press the
MESSAGE
key after each settings is completed to move to the
next message.
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...