Figure 9-10: Liquid-tight fitting thread
9.4.2.10
Thread the end of the metal liquid tight conduit as well as the coaxial cable into
the fitting. Terminate the conduit into the fitting carefully to form a liquid-tight
assembly.
9.4.2.11
Place the O-ring in its seat for the cover (see Figure 9-5).
9.4.2.12
Connect the coaxial cable as outlined in Section 9.4.1.1.4.
Figure 9-11: Bushing adaptor terminal block
9.4.2.13
Replace the Bushing Adaptor top cover on its seat and reassemble using the
Allen key screws and/or locating keyway.
Ensure that there is no tension or stress on the coaxial cable and that there
is adequate cable inside the Bushing Adaptor to allow for strain relief of the
coaxial cable.