background image

SPS J2007003 L064 - Quick Start Guide 

Document 850047442    r01 2015 July 

Precautions 



Install, service, and operate equipment only by professional, skilled and qualified personnel who have the necessary knowledge and 

practical experience with electrical equipment and who understand the hazards that can arise when working on this type of equipment.  



Disconnect batteries from outputs and/or follow safety procedures while working on equipment. Batteries may be connected in parallel 

with the output of the rectifiers. Turning off the rectifiers will not necessarily remove power from the bus.  



Do not disconnect permanent bonding connections unless all power inputs are disconnected. 



Verify that equipment is properly safety earth grounded before connecting power. High leakage currents may be possible. 



Exercise care and follow all safety warnings and practices when servicing this equipment. Hazardous energy and voltages are present in 

the unit and on the interface cables that can shock or cause serious injury. When equipped with ringer modules, hazardous voltages will 

be present on the ringer output connectors. 



Use the following precautions in addition to proper job training and safety procedures: 



Use only properly insulated tools. 



Remove all metallic objects (key chains, glasses, rings, watches, or other jewelry). 



Follow Lock Out Tag Out (LOTO) procedures:  customer specified, site specific, or general as appropriate. 

Disconnect all power input before servicing the equipment. Check for multiple power inputs. 



Wear safety glasses.  



Follow Personal Protective Equipment requirements:  customer specified, site specific, or general as appropriate. 



Test circuits before touching. 



Be aware of potential hazards before servicing equipment. 



Identify exposed hazardous electrical potentials on connectors, wiring, etc. 



Avoid contacting circuits when removing or replacing covers;. 



Use a personal ESD strap when accessing or removing electronic components. 



Personnel with electronic medical devices need to be aware that proximity to DC power and distribution systems, including batteries and 

cables, typically found in telecommunications utility rooms, can affect medical electronic devices, such as pacemakers. Effects decrease 

with distance.

 

 

Safety Statements 



Do not install this equipment over combustible surfaces.  



Rules and Regulations - Follow all national and local rules and regulations when making field connections.  



Compression Connectors 



U. S. or Canada installations - use Listed/Certified compression connectors to terminate Listed/Certified field-wire conductors. 



All installations - apply the appropriate connector to the correct size conductor as specified by the connector manufacturer, using only 

the connector manufacturer’s recommended or approved tooling for that connector.  



Electrical Connection Securing:  Torque to the values specified on labels or in the product documentation.  



Cable Dress - dress to avoid damage to the conductors and undue stress on the connectors.  



Circuit Breakers and Fuses 



Use only those specified in the equipment ordering guide. 



Size as required by the National Electric Code (NEC) and/or local codes. 

Safety Tested Limits - Refer to the equipment ratings to assure current does not exceed: 

 

Continuous Load (List 1) - 60% of protector rating 

 

Maximum Load (List 2 - typically end of discharge) - 80% of protector rating.

 



GMT Style Fuses - Use only fuses provided with safety caps.

 



Field-wired Conductors - Follow all National Electric Code (NEC) and local rules and regulations. 



Insulation rating:  90°C minimum; 105°C (minimum) if internal to enclosed equipment cabinets. 



Size AC field-wired conductors with 75°C ampacity (NEC) equal to or greater than their panel board circuit breaker rating. 



AC and DC input disconnect/protection - Provide accessible devices to remove input power in an emergency. 



Alarm Signals - Provide external current limiting protection. Rating 60V, 0.5A unless otherwise noted. 



Grounding - Connect the equipment chassis directly to ground. In enclosed equipment cabinets connect to the cabinet AC service ground 

bus. In huts, vaults, and central offices connect to the system bonding network.

 

Содержание J2007003L064

Страница 1: ...shelf for converter airflow Refer to Slimline Power System Brochure for details and accessories Quick Start Guide GE Critical Power SPS Stackable Slimline Converter Shelf Models J2007003L064 Step 1 Mount Shelf 1 Reposition mounting ears as required 4 screws each Torque to 25 in lb 2 8Nm Phillips screwdriver 2 Install Inter Shelf brackets between adjacent shelves optional Torque to 25 in lb 2 8Nm P...

Страница 2: ...d Shelf 4th Shelf Step 6 Connect Circuit Breaker Loads 1 Verify that breaker is OFF or not installed 2 Remove detachable terminal block 3 Insert load and load return wires Strip 0 4 in 10 mm 8 AWG 6 mm2 max 4 Torque to 6 5 in lb 0 75 Nm 5 Pull wires to verify 6 Insert detachable terminal block fully Detachable Terminal Block Screw Load Return 24V Load Wire Entry V V Step 7 Install Breakers Install...

Страница 3: ...ure If there are no alarms make required adjustments to the default settings on the controller for this installation Information Controller Configure Alarm Inputs and Outputs Converter Alarm Outputs 1 Select the Settings tab Power Converters to set alarm thresholds severity and relays on J1 connector 2 Select the drop down arrow next to the LED field and select ALM to activate the ALM LED for that...

Страница 4: ...tion Facilities OSP or where NEC applies Battery return may be either Isolated DC return DC I or Common DC return DC C Reference Documents These documents are available at www gecriticalpower com Document Title 850035894 Galaxy Pulsar Edge Quick Start Guide CC848815341 Pulsar Edge Controller Family Product Manual Slimline Power System Brochure 4 Parameter Range Default Converter Internal Selective...

Страница 5: ...ith electronic medical devices need to be aware that proximity to DC power and distribution systems including batteries and cables typically found in telecommunications utility rooms can affect medical electronic devices such as pacemakers Effects decrease with distance Safety Statements Do not install this equipment over combustible surfaces Rules and Regulations Follow all national and local rul...

Страница 6: ...SPS J2007003 L064 Quick Start Guide Document 850047442 r01 2015 July 2 Notes 6 ...

Страница 7: ...SPS J2007003 L064 Quick Start Guide Document 850047442 r01 2015 July 1 Notes 7 ...

Страница 8: ...uide Document 850047442 r01 2015 July 2 Notes 8 Document 850033855 r01 2013 August GE 601 Shiloh Rd Plano TX 75074 1 877 546 3243 Outside U S A 1 972 244 9288 www gecriticalpower com 2015 General Electric Company All rights reserved ...

Отзывы: