ROGRAMMING
M
ODE
Setting the ProBridge Gateway to Programming mode:
•
Set the device to programming mode by setting the dipswitch at SW4.
(SW4 RS232 SEL on, RS485 SEL off)
•
Ensure the RS232 (4310-0047B) cable is connected from the PC or
Laptop to one of the port 1 connectors on the ProBridge Gateway.
•
Open HyperTerminal on a laptop PC,
o
Set the RS232 port to 9600, N, 8, 1. (File/Properties, “Connect
to” tab, “Configure” button)
o
Set local echo on (File/Properties, “Settings” tab, “ASCII Setup”
button)
•
Cycle power on the ProBridge Gateway box and follow the instructions
in HyperTerminal.
Connection Diagram for programming mode is shown below
12V DC
RS-232
PORT 2
R
S-
4
85
P
O
R
T
0
R
S-
23
2
/
R
S-
4
8
5
P
O
R
T
1
RS-485 SEL
RS-232 SEL
TERM 1
BIAS 1 -
BIAS 1 +
TERM 0
BIAS 0 -
BIAS 0 +
P
O
RT
0
PO
R
T
1
8
7
6
5
4
3
2
1
O
F
F
O
N
8
7
6
5
4
3
2
1
O
F
F
O
N
8
7
6
5
4
3
2
1
O
F
F
O
N
8
7
6
5
4
3
2
1
O
F
F
O
N
SW
1
SW
2
SW
3
SW
4
Ka
late
l P
ro B
rid
ge
e
ProBridge Gateway
RS232
DB9F
4310-0047B Cable
RJ45 (Port 1)
Notebook or PC
Running HyperTerminal (RS232)
for Programming
Содержание Interlogix 0150-0265A
Страница 18: ......