Integritas Wall Mount Charger
-
Quick Start Guide
L
Gnd
N
L1
Step 4A Single Phase—Connect 120/240 Single Phase AC Input
Sizing external protectors and wire for all rectifier positions (3 or 6) provides full power for all rectifier positions.
1.
Verify the charger AC breaker (AC1) is OFF.
2.
Verify AC voltage matches AC Input per Charger Label with a meter.
3.
Bring AC wires into the AC Input Box in conduit through one of the
2”
knockouts
4.
Connect Ground wire (green /green
-
yellow) to lug.
a.
Strip
1/2”
(13mm)
b.
Insert into ground lug.
c.
Tighten lug screw securely.
d.
Pull wire to verify.
5. Connect each AC wire to the terminal
block in the AC Input Box.
AC terminal connections are labeled at each
position—Gnd, L, N, L1, and L2.
a.
Strip
1/4”
(10mm).
b.
Insert into terminal block.
c.
Torque screw to 13 in
-
lb (1.5 Nm).
d.
Pull wire to verify.
Go to Step 5
Gnd
L2
Top Feed
Bottom Feed
L2
L1
Gnd
Recommended External Protection and Minimum Wire Size
—
6 AWG max.
120V~ Phase to Neutral
(1200W per rectifier max)
240V~ Phase to Phase
(2725W per rectifier
max)
Single-Phase Rectifiers
Rectifier Positions Powered
Maximum
Rectifiers
per Feed
External Feed
Protector
Minimum
Wire
External
Feed Protec-
tor
Mini-
mum
Wire
1
1
20A
14AWG
20A
14AWG
2
2
40A
8AWG
40A
8AWG
3 Rectifier Charger
—
All positions
3
60A
6AWG
60A
6AWG
240V
120V
N
L1
Gnd