D e t a i l e d O p e r a t i o n
Communication Port
40
6" QuickPanel View Keypad
GFK-2357A
3
Shielding
Shielded cable is required for compliance with CE and FCC requirements. The
cable shield should be connected to the metal connector shell or by pin #1 of the
QuickPanel 25-pin serial connector. Shield and cable ground (pin #7 of the 25-pin
connector or pin #5 of the 9-pin connector) should not be connected directly
together.
The Frame Ground (pin #1) of the QuickPanel View should be used for attaching
the cable shield in these applications.
Caution:
Do not connect Signal Ground (pin #7) to Frame Ground (pin #1) on the
QuickPanel View Keypad, except in the specific and limited circumstances noted
in the Grounding section above.
W o r k i n g w i t h t h e C O M p o r t
To add a new remote netwo rki ng co nnection
1. From the
Start
menu, tap
Settings
and then
Network and Dial-up Connections
.
The
Connection
window appears.
2. Double-tap
Make New Connection
.
The
Make New Connection
window appears.
3. Type a name for the new connection.
4. Choose a connection type. If you are configuring a Modem, choose
Dial-Up Connection
. If you have a Device,
select
Direct Connection
.
5. Tap
Next
.