background image

BASIC OPERATION AND FEATURES 

SX TRANSISTOR CONTROL

 

 

 

Page 

5

 

 

following description provides a brief introduction to 

examples of some of these features. 

 
Section 1. 2 Solid-State Reversing 

 

The direction of armature rotation on a shunt motor is 

determined by the direction in which current flows through 

the field windings. Because the shunt motor field only 

typically requires about 10% of the armature current at full 

torque,  it is normally cost effective to replace the double-

pole, double-throw reversing contactor with a low power 

transistor H-Bridge circuit (Figure 4).  

 

 

By energizing the transistors in pairs, current can be made 

to flow in either direction in the field.  The field control 

circuit operates at 2 KHZ, and the armature control circuit 

typically operates at 12KHZ, a frequency normally above 

human hearing. This high frequency coupled with the 

elimination of directional contactors, provides very quiet 

vehicle operation. 

 

The line contactor is normally the only contactor required 

for the shunt motor traction circuit. This contactor is used 

for both pre-charge of the line capacitors and for 

emergency shut down of the motor circuit, in case of 

problems that would cause a full motor torque condition. 

The line can be energized and de-energized by the various 

logic combinations of the vehicle, i.e. activate on key, seat 

or start switch closure, and de-energize on time out of idle 

vehicle. Again, these options add to the quiet operation of 

the vehicle. 

  

Section 1. 3 Flexible System Application

  

 

Because the shunt motor controller has the ability to 

control both the armature and field circuits independently, 

the system can normally be adjusted for maximum system 

efficiencies at certain operating parameters. Generally 

speaking, with the ability of independent field and 

armature, the motor performance curve can be maximized 

through proper control application.  

 
Section 1. 4 More Features with Fewer Components  
 

Field weakening with a series wound motor is 

accomplished by placing a resistor in parallel with the field 

winding of the motor. Bypassing some of the current 

flowing in the field into the resistor causes the field current 

to be less, or weakened. With the field weakened, the motor 

speed will increase, giving the effect of “overdrive”.  To 

change the “overdrive speed”, it is necessary to change 

the resistor value.  In a separately excited motor, 

independent control of the field current provides for 

infinite adjustments of “overdrive” levels, between 

motor base speed and maximum weak field. The 

desirability of this feature is enhanced by the 

elimination of the contactor and resistor required for 

field weakening with a series motor. 

 

 With a separately excited motor, overhauling speed 

limit, or downhill speed, will also be more constant. By 

its nature, the shunt motor will try to maintain a 

constant speed downhill. This characteristic can be 

enhanced by increasing the field strength with the 

control. Overhauling load control works in just the 

opposite way of field weakening, armature rotation 

slows with the increase of current in the field. An 

extension of this feature is a zero-speed detect feature 

which prevents the vehicle from free-wheeling down 

an incline, should the operator neglect to set the brake. 

 

Regenerative braking (braking energy returned to the 

battery) may be accomplished completely with solid-state 

technology. The main advantage of regenerative braking is 

increased motor life. Motor current is reduced by 50% or 

more during braking while maintaining the same braking 

torque as electrical braking with a diode clamp around the 

armature. The lower current translates into longer brush 

life and reduced motor heating. Solid state regenerative 

braking also eliminates a power diode, current sensor and 

contactor from the circuit. 

 

For GE, the future is now as we make available a new 

generation of electric traction motor systems for electric 

vehicles having separately excited DC shunt motors and 

controls. Features that were once thought to be only 

available on future AC or brushless DC technology vehicles 

systems are now achievable and affordable. 

 

 
 
 
 
 
 
 

FUSE

LINE

CAP

ARM

F2

F1

Q2

Q4

Q3

Q5

Q1

POS

NEG

Figure 4

A1 +

A2 -

Q6

May 2000

 

Содержание IC3645SR4R333AS2

Страница 1: ... normal field service channels Do not contact GE directly for this assistance Table of Contents Copyright by General Electric Company May 2000 Section 1 0 INTRODUCTION 4 1 1 Motor Characteristics 4 1 2 Solid State Reversing 5 1 3 Flexible System Application 5 1 4 More Features with Fewer Components 5 Section 2 0 FEATURES OF SX FAMILY OF MOTOR CONTROLLERS 6 2 1 Performance 6 2 1 1 Oscillator Card F...

Страница 2: ... 0 TROUBLESHOOTING AND DIAGNOSTIC STATUS CODES 13 4 1 General Maintenance Instructions 13 4 2 Cable Routing and Separation 13 4 2 1 Application Responsibility 13 4 2 2 Signal Power Level Definitions 13 4 2 2 a Low Level Signals Level L 13 4 2 2 b High Level Signals Level H 14 4 2 2 c Medium Power Signals Level MP 14 4 2 2 d High Power Signals Level HP 14 4 2 3 Cable Spacing Guidelines 14 4 2 3 a G...

Страница 3: ... Dash Displays 39 6 2 1 Connections 38 6 2 2 Par t Numbers 38 6 2 3 Connector Reference Numbers 39 6 3 Start up Display Sequence 40 6 4 Outline Drawings 40 6 5 Suggested Wiring Configuration for Use of GE Standard Traction Pump Dash Display Motor Traction System 40 Section 7 0 MEMORY MAPS 41 7 1 Typical Memory Map for DM Proportioning Control 41 43 ...

Страница 4: ...nce curves of Figure 1 the high torque at low speed characteristic of the series motor is evident In a shunt motor the field is connected directly across the voltage source and is therefore independent of variations in load and armature current If field strength is held constant the torque developed will vary directly with the armature current If the mechanical load on the motor increases the moto...

Страница 5: ...y placing a resistor in parallel with the field winding of the motor Bypassing some of the current flowing in the field into the resistor causes the field current to be less or weakened With the field weakened the motor speed will increase giving the effect of overdrive To change the overdrive speed it is necessary to change the resistor value In a separately excited motor independent control of t...

Страница 6: ...ts the average current to a value set by Function 4 and Function 8 of the Handset The C L setting is based on the maximum thermal rating of the control Because of the flyback current through 3REC the motor current is usually greater than battery current except at 100 ON time Section 2 1 3 Braking Section 2 1 3 a Regenerative Braking to Zero Speed Slow down is accomplished when reversing direction ...

Страница 7: ...lting PMT should open the Line contactor in the event of a failure Section 2 1 6 On Board Coil Drivers Internal Coil Suppression Coil drivers for the LINE and SP or BYPASS contactors are on board the control card These contactors must have coils rated for the vehicle battery volts Section 2 2 System Protective Override Section 2 3 Diagnostics Section 2 2 1 Static Return to Off SRO Section 2 3 1 Sy...

Страница 8: ... a Light Emitting Diode LED display and a keyboard for data entry Note for ordering purposes a separate Handset part is required for SX controls Features and functions Monitor existing system status codes for both traction and pump controls Monitor intermittent random status codes Monitor battery state of charge if available Monitor hourmeter reading on traction and pump controls Monitor or adjust...

Страница 9: ...ment 02 Control Type SH Separately Excited Control Plugging SR Separately Excited Control Regen to Zero Argument 03 Operating Voltage 1 120 volts 5 36 48 volts 2 24 volts 6 24 36 volts 3 36 volts 7 72 80 volts 4 48 volts Argument 04 Package Size D 6 86 X 6 67 R 6 86 X 8 15 U 8 66 X 8 13 W 8 66 X 10 83 Argument 05 Armature Current 2 characters 22 220 Amps 33 330 Amps 40 400 Amps etc Argument 06 Fie...

Страница 10: ...OUTLINE DRAWINGS ELEMENTARY DRAWINGS AND INPUTS OUTPUTS SX TRANSISTOR CONTROL Page 10 Section 3 2 Outline SX 2 Package Size May 2000 ...

Страница 11: ...P6 P3 P4 P5 FOOT SW DIRECTION SW TRAVEL ENABLE SW P21 P13 ACC POT P14 P11 P18 1A OR SP DVR P7 P6 P2 P1 P3 P4 P5 LEFT CONTROL MASTER RIGHT CONTROL SLAVE P11 P13 LINE P16 PY7 12V 48V P16 PY7 P21 P12 LEFT TURN SW P12 RIGHT TURN SW B P10 3 1 2 JACK RABBIT SW BOOM UP SW LEFT TACH TILT SW P14 RIGHT TACH PIN 1 2 3 4 5 6 7 8 9 10 11 12 DESCRIPTION CLOCK OUT TMM7A POWER SUPPLY 5V Y PLUG CONNECTIONS DATA OU...

Страница 12: ...S SUPPLY 10 BRAKE DRIVER SIGNAL 11 CROSS TALK SEND 12 TURN SWITCH 13 TILT SENSOR 14 TACHOMETER INPUT SIGNAL 15 TACHOMETER 12 VOLTS SUPPLY 16 MOTOR CURRENT COMPENSATION 17 LINE CONTACTOR DRIVER AND SUPPRESSION 18 N A 19 N A 20 N A 21 CROSS TALK RECEIVE 22 SERIAL RECEIVE 23 SERIAL TRANSMIT MOTOR TRACTION Y PLUG PIN INPUT OUTPUT DESCRIPTION 1 CLOCK OUT DASH DISPLAY 4 2 DATA OUT DASH DISPLAY 3 3 ENABL...

Страница 13: ... with periodic equalizing charges Visual inspection of GE contactors contained in the traction and pump systems is recommended to occur during every 160 hours of vehicle operation Inspection is recommended to verify that the contactors are not binding and that the tips are intact and free of contaminants GE does not recommend that any type of welding be performed on the vehicle after the installat...

Страница 14: ...nd higher levels should never encircle each other or run parallel for long distances Medium power signals are designated as level MP These signals consist of It is practical to use existing wire runs or trays as long as the level spacing see section 4 2 2 can be maintained for the full length of the run DC switching signals greater than 15 V Signals with currents greater than 250 mA and less than ...

Страница 15: ...he instructions outlined in the following status code instruction sheets If mis operation of the vehicle occurs a status code will be displayed on the Dash Display for vehicles equipped with a Dash Display or made available by plugging a Handset into the plug Y location and then reading the status code With the status code number follow the procedures outlined in the status code instruction sheets...

Страница 16: ... going from the Y plug and the Dash Display or Handset Defective Dash Display or Handset Replace Dash Display or Handset NEG 48V FU3 KEY SWITCH P1 P2 P6 FOOT SWITCH 12V TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 01 No foot switch or deadman switch input no voltage to P6 This status code will be displayed when P6 is less than 12 battery volts MEMORY R CALL E NO CORRECTIVE...

Страница 17: ...e the controller unit KEY SWITCH P1 P2 P3 P17 P5 TRAVEL ENABLE SW DIRECTIONAL SW P4 FOOT SW P6 L BOOM SW JACK RABBIT SW TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 03 Travel enable switch is closed on initial power up This status code will be displayed when P5 is greater than 12 of battery voltage at initial key switch on MEMORY R CALL E NO CORRECTIVE ACTIONS TROUBLE SHOO...

Страница 18: ...SW JACK RABBIT SW TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 07 Accelerator input voltage too high on power up after initial key switch closure This status code will be displayed when the accelerator input voltage at P7 is higher than 3 7 volts and travel enable switch is selected MEMORY R CALL E NO CORRECTIVE ACTIONS TROUBLE SHOOTING DIAGRAM Circuits valid for Traction ...

Страница 19: ... than 4 7K ohms Defective control Disconnect wire from P7 Measure voltage from P7 to negative Voltage should be greater than 4 5 volts if not replace control P7 P8 ACC POT P9 P7 P8 ACC POT TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 09 The travel enable switch is open and the directional switch is closed This status code will be displayed when P5 is less than 12 of batter...

Страница 20: ...heck minimum battery volts at P1 and NEG NEG FU3 P1 NOMINAL BATTERY VOLTAGE MINIMUM LIMIT VOLTS AT 1 95 VDC PER CELL 24 80 48 72 36 23 4 78 0 46 8 70 2 35 1 TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 16 Battery voltage is too high or control card is mis adjusted This status code will be displayed when the battery volts are greater than 2 4 volts per cell at initial key s...

Страница 21: ...r SYMPTOM Control will not operate POSSIBLE CAUSE Defective control Replace controller unit NO GRAPHIC FOR THIS STATUS CODE TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 24 Motor field current is high on start up in the forward direction This status code will be displayed when the current draw in the motor field is too high at start up in the forward direction MEMORY R CALL...

Страница 22: ... be dropping below 10 Volts DC under load Loose connection at P1 Insure that the wire connection at P1 is tight Defective control Replace controller unit NEG FU3 KEY SWITCH P1 P2 TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 41 Open thermal protector TP or transistor over temperature This status code will be displayed when the voltage at the thermal protector is too high ME...

Страница 23: ...ler SYMPTOM Control will not operate POSSIBLE CAUSE Defective control Replace controller unit NO GRAPHIC FOR THIS STATUS CODE TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 43 Motor armature offset voltage is too low This status code will be displayed when the voltage at the current sensor input is less than 2 4 volts with no current flowing in the motor circuit MEMORY R CAL...

Страница 24: ...VER BLOCK FU1 LINE 12V P21 P11 RIGHT CONTROL SLAVE POWER CONNECTIONS LEFT CONTROL POS A1 F1 NEG A2 F2 FIELD ARMATURE 48V May 2000 TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 45 Armature transistor did not turn on properly This status code will be displayed when during control operation the armature transistor fails to turn on properly This will result in a PMT condition M...

Страница 25: ... P11 RIGHT CONTROL SLAVE POWER CONNECTIONS LEFT CONTROL POS A1 F1 NEG A2 F2 FIELD ARMATURE 48V TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 47 The PMT enable signal from the opposite control dropped below 5V during motoring This status code will be displayed when the voltage at PL2 21 drops below 5V during motoring MEMORY R CALL E NO CORRECTIVE ACTIONS TROUBLE SHOOTING DIA...

Страница 26: ...STATUS INDICATION 51 Capacitor volts are low before the line contactor closes This status code will be displayed during key on when the capacitor volts is less than 85 of battery volts at initial key switch on MEMORY R CALL E NO CORRECTIVE ACTIONS TROUBLE SHOOTING DIAGRAM Circuits valid for Traction Controller SYMPTOM Line contactor does not close when capacitor does not precharge POSSIBLE CAUSE D...

Страница 27: ...ATUS CAUSE OF STATUS INDICATION 68 The PMT enable signal from the opposite control from the one displaying the 68 fault code drops below 5V This status code will be displayed when the voltage at PL21 drops below 5V MEMORY RE ALL C YES CORRECTIVE ACTIONS TROUBLE SHOOTING DIAGRAM Circuits valid for Traction Controller SYMPTOM Control will not operate POSSIBLE CAUSE Auxiliary control shut down Check ...

Страница 28: ...VER BLOCK FU1 LINE 12V P21 P11 RIGHT CONTROL SLAVE POWER CONNECTIONS LEFT CONTROL POS A1 F1 NEG A2 F2 FIELD ARMATURE 48V May 2000 TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 75 Regen fault with capacitor 1C voltage too high This status code will be displayed when the voltage on the capacitor is greater than battery voltage plus 6 volts during the regenerative braking cycl...

Страница 29: ...EY SWITCH L P1 P17 P2 P6 FOOT SW P18 1A OR SP DVR LEFT CONTROL MASTER P12 LEFT TURN SW B P10 3 1 2 FU3 DRIVER BLOCK FU1 LINE 12V P21 P11 RIGHT CONTROL SLAVE POWER CONNECTIONS LEFT CONTROL POS A1 F1 NEG A2 F2 FIELD ARMATURE 48V May 2000 TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 77 Motor current is detected during regenerative braking This status code will be displayed wh...

Страница 30: ...YES CORRECTIVE ACTIONS TROUBLE SHOOTING DIAGRAM Circuits valid for Traction Controller SYMPTOM Control will not operate POSSIBLE CAUSE Bad tachometer Replace tachometer Lost wire from tachometer Verify tach connections Motor has stalled Defective control Replace controller unit KEY SWITCH L P1 P17 P2 P6 FOOT SW P18 1A OR SP DVR LEFT CONTROL MASTER P12 LEFT TURN SW B P10 3 1 2 FU3 DRIVER BLOCK FU1 ...

Страница 31: ...Voltage 36 48 volts is auto ranging Selection of Card Operation Type At the transistor control traction card unplug the Y plug if the dash display is in use and plug in the Handset to the plug location Y on the control card After installing the Handset tool plug the battery in and turn the key switch on The chart at the right details the start up display sequence that will occur START UP DISPLAY S...

Страница 32: ...a blank display if BDI is not used and there are no fault codes The vehicle can now be operated with the Handset connected or the Handset can be disconnected before operation NOTE You can return to the segment check mode at any time by holding down the ESC key until 8888 appears in the display Section 5 3 2 Status Code Scrolling The SX family of controllers furnishes a function register that conta...

Страница 33: ...This function allows for the adjustment of the rate of time it takes for the control to accelerate to 100 applied battery voltage to the motor on hard acceleration in high speed mode Range 0 1 to 25 5 seconds Set 1 to 255 Resolution 0 1 seconds per set unit Example Setting of 20 2 0 seconds C A 2 2 seconds FUNCTION 4 ARMATURE CURRENT LIMIT Push 4 This function allows for the adjustment of the arma...

Страница 34: ...6 28 amps Important Note The function is used to optimize motor and control performance and this setting will be determined by GE and OEM engineers at the time of vehicle development This setting must not be changed by field personnel without the permission of the OEM FUNCTION 9 REGEN BRAKING CURRENT LIMIT Push 9 This function allows for the adjustment of the regen braking current limit Resolution...

Страница 35: ...he BDI to operate properly the setting as shown in the table must be entered Battery Volts Set Units 24 volts Between 0 and 31 36 volts Between 32 and 44 48 volts Between 45 and 69 36 48 volts Between 184 and 250 No BDI Between 251 and 255 FUNCTION 16 FIELD RAMP DOWN RATE WHILE IN REGENERATIVE BRAKING MODE Push CONT 1 Important Note This function is used to optimize motor and control performance a...

Страница 36: ...GE application engineer To ensure optimum operation of the control this function must be left with zero stored in this register FUNCTION 26 RATIO Push CONT 11 This function sets the ratio between armature and field current when transitioning from minimum field to maximum field current The setting represents the quantity of field current changed for each 1 amp of armature current changed Max Max Re...

Страница 37: ...ould not be adjusted FUNCTION 55 NOT APPLICABLE This function is not applicable to this type of control and should not be adjusted FUNCTION 56 NOT APPLICABLE This function is not applicable to this type of control and should not be adjusted FUNCTION 57 NOT APPLICABLE This function is not applicable to this type of control and should not be adjusted FUNCTION 58 NOT APPLICABLE This function is not a...

Страница 38: ...usted by Function 24 This function sets the armature current at which minimum field current will achieved The ratio setting is adjusted by Function 26 This function sets the ratio between armature and field current when transitioning from minimum field to maximum field current Setting is the value of field current changed for each 100 amps of armature current changed The full load transition point...

Страница 39: ...bols indicate the active readout mode Section 6 2 1 Connections Connections are made to the Dash Display with five 5 22 gage wires to Plug Y of each control Shielded cable is required to eliminate signal interference Section 6 2 2 Part Number IC3645LXTDD T 3 T Traction Only P Traction Pump 3 Round Face with four display symbols For Custom Dash Displays contact your vehicleOEM g GE Electric Vehicle...

Страница 40: ...0 81 3 0 19 4 8 2 00 50 8 PUMP TRACTION CONNECTOR OMITTED IF NOT REQUIRED 0 41 10 4 Section 6 5 Suggested Wiring Configuration for Use of GE Standard Traction Pump Dash Display with Dual Motor Traction System 1 2 3 4 5 5 4 3 2 1 BACK VIEW OF DISPLAY T P PY3 PY4 PY2 PY1 PY5 Y PLUG CONNECTIONS LEFT CONTROL CONNECTIONS RIGHT CONTROL CONNECTIONS Y PLUG CONNECTIONS BARE WIRE NEGATIVE CONNECTION PY1 PY2...

Страница 41: ...re Current Ramp Up Rate in Regen HS or PC None 18 19 19 Tach Loss Trip Time HS or PC None 19 20 20 Hill Climbing Speed Limit HS or PC None 20 21 21 Not Used HS or PC None 21 22 22 Not Used HS or PC For DD on power up 22 23 23 Error Compensation HS or PC None 23 24 24 FW Start HS or PC None 24 25 25 Monitor HS or PC GE Temporary Storage 25 26 26 Ratio HS or PC GE Temporary Storage 26 27 27 Not Used...

Страница 42: ... Only Reset to Zero Only 66 67 Hours Tens Ones 9 PC Only Reset to Zero Only 67 68 Hours Thou Hun 9 PC Only Reset to Zero Only 68 69 36 Stored Status Code 10 PC Only Reset to Zero Only 69 70 BDI 10 PC Only Reset to Zero Only 70 71 Hours Tens Ones 10 PC Only Reset to Zero Only 71 72 Hours Thou Hun 10 PC Only Reset to Zero Only 72 73 38 Stored Status Code 11 PC Only Reset to Zero Only 73 74 BDI 11 PC...

Страница 43: ...C None 106 107 58 Dash Display Min Fld 3 HS or PC None 107 108 59 Dash Display If Im Ratio 3 SL 3 HS or PC None 108 109 60 Dash Display CA 4 HS or PC None 109 110 61 Dash Display FWS 4 Ratio2 4 HS or PC None 110 111 62 Dash Display Min Fld 4 HS or PC None 111 112 63 Dash Display If Im Ratio 4 SL 4 HS or PC None 112 113 Secure HM Tens Ones PC Only OEM Read Only 113 114 Secure HM Thou Hun PC Only OE...

Отзывы: