GEI-68720 

iv) 

To  check  performance,  turn  the  stop  screw  in  until  one  contact 

continuity  lamp  is  lit. 

Turn  stop  screw  in  an  additional  1/2  turn 

and  all  continuity  lamps  should  be  lit. 

Back  off  the  stop  screw  to  obtain  at  least  1/4  inch  contact  gap. 

v) 

Insert  a  7/32-inch  gage  between  any  of  the  normally-open  moving  and 

stationary  contacts  and  turn  the  stop  screw  clockwise  until  the 
continuity  lamp  lights. 

Lock  the  stop  screw  in  this  position  with 

the  locking  nut. 

3.2.  Normally-Closed  Contact  Gap  and  Wipe 

a. 

The  moving  contact  arms  must  be  adjusted  so  that  the  normally-closed 

contacts  make  approximately  simultaneously  (�.008)  when  the  relay  is 

operated  by  hand.  The  wipe  and  gap  are  automatically  set  by  the  formation 
of  the  stationary  contacts  and  the  strength  of  the  control  spring. 

Adjustments  can  be  made  as  follows: 

PICKUP 

i) 

Turn  the  stop  screw  clockwise  until  the  first  normally-closed  contact 

opens. 

ii) 

Turn  the  stop  screw  an  additional  1/2  turn  clockwise.  All  normally-
closed  contacts  should  be  open. 

iii)  Turn  stop  screw  counterclockwise  until  there  is  approximately  1/8  gap 

between  the  stop  screw  and  armature. 

Lock  the  stop  screw  in  this 

position. 

The  main  coil  should  be  adjusted  to  pick  up  at  80%  of  rated  voltage  for  AC 

relays,  and  60%  of  rated  voltage  for  DC  relays.  This  adjustment  may  be  obtained  by 

unseating  the  knurled  adjusting  nut  at  the  lower  end  of  the  armature  and  turning 

this  nut  in  a  clockwise  direction  to  raise  the  pickup.  The  pickup  is  decreased  by 

turning  the  nut  in  the  counterclockwise  direction. 

The  reset  coil  should  pick  up  at  80%  of  rated  AC  voltage,  and  50%  to  75%  of 

rated  DC  voltage.  There  is  no  adjustment  available  to  alter  this  pickup.  Since  the 
reset  coil  is  rated  intermittently,  care  should  be  exercised  when  applying  this 

voltage. 

After  all  adjustments  are  completed,  the  mounted  relay  should  be  operated  a  few 

times  to  be  certain  that  the  mechanism  operates  freely  and  that  the  contact  surfaces 

align  properly. 

Check  to  see  that  the  armature  latches  in  when  operated  by  hand, 

and  opens  readily  when  reset. 

RENEWAL  PARTS 

When  ordering  renewal  parts,  address  the  nearest  Sales  Office  of  the  General 

Electric  Company,  specify  quantity  required,  name  of  the  part  wanted,  and  the 
complete  nameplate  data.  The  renewable  parts  publication  is  GEF-2757. 

www 

. ElectricalPartManuals 

. com 

Содержание HFA54

Страница 1: ...INSTRUCTIONS MULTI CONTACT AUXILIARY RELAY TYPE HFA54 GEI 68720G d Control GE Meter an Parkway 205 Great Val 55 0715 Malvern PA w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 2: ...rovide for every possible contingency to be met in connection with installation operation or maintenance Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser s purposes the matter should be referred to the GeneralElectric Company To the extent required the products described herein meet applicable ANSI IEEE and NEMA standard...

Страница 3: ...onnections for the relays are shown in Figures 4 5 and 6 APPLICATION The HFA relays are electric reset hinged armature instantaneous auxiliary relays that are suitable for application where the operating characteristics and ratings as described in this book are required RAT NGS The TYPE HFA relays are available with coil ratings for standard voltages up to 575 volts at 25 50 or 60 cycles and up to...

Страница 4: ...th a specific contact arrangement they wi11 be shipped with six 6 circuit closing contacts code 60 However the HFA54D and HFA54 K relays are available with contact code 33 only as given in Table V The general characteristic of HFA54 relays are summarized in Table II TABLE II No Model Separate Additional Contact No Contact Characteristics Arrangement Circuits Table HFA54 B 5 Hand Reset III HFA54 C ...

Страница 5: ...H J L CODE NO 60 51 4 2 1 33 a a b b b a 24 POSITION NO CONTACT ARRANGEMENT 1 a a a a a 2 a a a a b 3 a a b b b 4 a b b b b 5 a a a b b 6 a a a a a TABLE V HFA54D K CODE NO 33 POSITION NO CONTACT ARRANGEMENT 1 a 2 a1 3 bl 4 b 5 b 6 a TABLE VI HFA54M N CODE NO 1 2 3 24 a b b b b a POSITION NO CONTACT ARRANGEMENT 1 a a a 2 a a b 3 b bl b1 4 a bl b 5 a a a 6 a a a 5 15 b b b b b a 15 06 b b b b b b b...

Страница 6: ...owever the charged external capacitor has sufficient energy to back up the operating coil to ensure proper latch holding of the armature See Figs 11 12 and 13 for outlines of the external capacitor and resistor BURDENS The operating coil burdens 1 isted Table VII are measured with the relay in the picked up position at rated voltage and are for continuous rating The common AC and DC burden table V...

Страница 7: ...bed If the relays are not to be installed immediately they should be stored in their original cartons in a place that is free from moisture dust and metallic chips Foreign matter collected on the outside of the case may find its way inside when the cover is removed and cause trouble in the operation of the relay INSTALLATION Type HFA relays should be mounted on a vertical surface The outline panel...

Страница 8: ...nce if a contact is changed from circuit opening to circuit closing the following checks and adjustments should be made 1 Make sure that all contact and coil studs are tight 2 Make sure that the armature is free of binding when operated by hand The braided 11pigtail11 lead on all contacts must be adjusted to exert minimum force on the contacts 3 Make mechanical contact adjustments as follows 3 1 N...

Страница 9: ...mately 1 8 gap between the stop screw and armature Lock the stop screw in this position The main coil should be adjusted to pick up at 80 of rated voltage for AC relays and 60 of rated voltage for DC relays This adjustment may be obtained by unseating the knurled adjusting nut at the lower end of the armature and turning this nut in a clockwise direction to raise the pickup The pickup is decreased...

Страница 10: ...GEI 68720 ltlltlll FIG l 8025534 HFA54 RELAY BACK CONNECTED SURFACE MOUNTED FRONT VIEW 10 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 11: ...GEI 68720 FIG 2 8025781 HFA54 RELAY FRONT CONNECTED SURFACE MOUNTED FRONT VIEW 11 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 12: ...GEI 68720 FIG 3 8025539 HFA54 RELAY BACK CONNECTED SEMI FLUSH MOUNTED FRONT VIEW 12 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 13: ...IG 4 0104 A8528 5 INTERNAL CONNECTIONS OF HFA54B HFA54 C HFA54 0 and HF54 E RELAYS BACK VIEW POS 6 RESET 1 COIL 5 7 11 4 2 9 POS POS POS 4 3 2 6 8 10 12 INTERNAL CONNECTIONS BACK VIEW 13 14 FIG 5 6375837 4 INTERNAL CONNECTIONS OF HFA54H HFA54 J HFA54 K and HF54 L RELAYS BACK VIEW 13 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 14: ...CONTACT LONG WIPE b N C CONTACT bl N C CONTACT LONG WIPE 6 POS I O ALT c O N N FoR AATf D AC VOL i r I I I 1 I I ll RATEDI C t f I 15 8 os I 12 _ I _ INTERNAL CONNECTIOHS BACK VIEW c J XT R S FIG 6 0207A7851 4 INTERNAL CONNECTIONS OF HFA54M AND HFA54 N BACK VIEW Revised since last issue 14 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 15: ...__L_ a N O CONTACT a 1 N O CONTAC LONG WIPE b N C CONTACT b1 sN C CONTACT LONG WIPE LONG WIPE CONTACTS OJ ERLAP t EACH REtAY IS AVAI B ONLl TH CONTAC T C DE SPEC 5 3 s 5 4 4 6 POS 3 7 9 J 2 1 8 11 12 INTERNAL CONNECTIONS BACK VIEW OPER COl r EACH CONTACT CONVERT IBLE ONLY CCORDING TO CONTACT ARRANGEMENT CODE FOR MODELS AS Ll STED FIG 7 0362A0576 7 OUTLINE AND PANEL DRILLING DIAGRAM FOR HFA54B C D ...

Страница 16: ... u OUTL IfE GEI 68720 TOP Of PU L DRILLI FIG 8 04 18A0799 8 OUTLINE AND PANEL DRILLING DIAGRAM FOR HFA54 RELAYS FOR SEMI FLUSH MOUNTING TYPICAL MODEL NUMBER IS HFA54B F 16 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 17: ... MOUNTING TYPICAL MODEL NUMBERS ARE HFA54 B H AND HFA54M H I l 6 32 11 41 5 32 OUTLINE 18 111 TYPE OF PANEL I NSULAT lNG STEEL 8 Dl A 16 I 2 HOLESI A 8 c 11 16 7116 3t 9116 11 16 h FIG 10 6375836 5 OUTLINE AND PANEL DRILLING DIAGRA M FOR HFA54H J K AND L RELAYS FOR SURFACE OUNTING TYPICAL MODEL NU MBER IS HFAS4H1 H 17 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 18: ... 1 5 3 03 ____ 1 4 Z l5 n31 81 031 WI 3 00 0 3 tM 12 24 I 4 38 0 3 T iD t l 0 0 1__ Wo I 0 I N M f It _1 Y f FIG 11 0028F0910 0 SH 2 OUTL INE OF EXTERNAL CAPACITOR 5 F 18 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 19: ... 188 HtJI ES GEI 68720 4 125 031 1 5 031 _ S T 0 31 14 4 3 C63 12 24 THD 438 010 3 0 3 0 FIG 12 0028F0915 0 SH 2 OUTLINE OF EXTERNAL CAPACITOR 15 F 19 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 20: ...GEI 68720 __ HOLE 32 1 2 9 32 FIG 13 0389A0752 2 OUTLINE OF EXTERNAL RES IS TOR US ED WITH HFA54M and HFA54 N RELAYS 20 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 21: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 22: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 23: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 24: ... 91 500 Meter and Control Business Department General Electric Company Protection and Control 205 Great Valley Parkway Malvern Pennsylvania 19355 0715 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Отзывы: