OPM_SGS_ISG_M22_M30_0US_V011.doc
28/38
Installation
Guide
SG Series
225 & 300 kVA
3.8.5 Setup
for
SG Series
when functioning as frequency converter
When the
SG Series
is utilized for
different
output frequency compared to the input
frequency
, the
Automatic Bypass
and
Manual Bypass
functions are disabled, therefore the
Load
cannot be transferred to
Utility
in case of overload, short circuit, or inverter failure.
In situations where the UPS needs to be powered down for maintenance purposes, the
critical
Load
must also be powered down during this time, the
UPS cannot be transferred to
Manual Bypass
, serious damage to the
Load
could result.
Circuit breaker
Q2 - Manual Bypass
must be blocked in the open position,
to avoid any accidental closure, by
means of a padlock or a similar
device, when the UPS is used as a
frequency converter.
As an added measure of safety the
bus bar connections
BR1
,
BR2
and
BR3
should also be removed.
See
Fig. 3.8.3-2
.
SG
S_225-
300_S
wi
tc
hes
Q
2_01
Q2
Q1
Fig. 3.8.5-1 Switch Q2 – Manual Bypass
NOTE !
The standard
SG Series
UPS may be operated at 50Hz input with 60Hz
output frequency conversion.
It is recommended that the static switch bypass be electronically
blocked if the UPS is to operated as a frequency converter in order to
prevent damage to the load.
Check with a Global Services Field Service Engineer to facilitate the
parameter change.
CAUTION !
The output transformer of the UPS is designed for 60Hz only.
Operation at 50Hz, 480V output may overheat the transformer.
The optional 5th harmonic filter is designed for 60Hz operation.
If the UPS is purchased with this internal filter it may not be operated
at 50Hz input or damage to the filter could result.