![background image](http://html1.mh-extra.com/html/ge/gl-311-f3-4031-p-ve/gl-311-f3-4031-p-ve_operating-instructions-manual_4331766090.webp)
R
ECONDITIONING
OI 250 (EN)
REV7
/REV7
10.1.9
Mounting the Guide Shaft
• Insert the interrupter unit (5) and the movable contact system (6)
into the fixed contact (7) so that the shaft holes in the guide levers
(8) and fixed contact (7) are lined up.
• Place the spacer sleeve (21) between the levers.
• Connect the guide lever and fixed contact to the guide shaft (28).
• Coat a new screw (22) with locking adhesive per S1.
• Fasten the shaft with the locking plate (23) and the new screw
(22). Tighten to a torque of 17Nm.
5
Interrupter unit
1x
6
Movable contact system
1x
7
Fixed contact
1x
8
Guide lever
2x
17
Socket head cap screw, M8x12 A2-70
1x
21
Spacer sleeve
1x
23
Locking plate
1x
28
Guide shaft
1x
5
6
7
8
23 22
21
28
BA
-P-
P
S
-9
Содержание GL 311 F3/4031 P/VE
Страница 2: ......
Страница 10: ...INTRODUCTION 10 146 OI 250 EN REV7 REV6...
Страница 12: ...SAFETY 12 146 OI 250 EN REV7 REV3...
Страница 48: ...INSTALLATION 48 146 OI 250 EN REV7 REV7...
Страница 80: ...INSPECTION AND MAINTENANCE 80 146 OI 250 EN REV7 REV3...
Страница 102: ...RECONDITIONING 102 146 OI 250 EN REV7 REV7...
Страница 104: ...END OF LIFE MANAGEMENT 104 146 OI 250 EN REV7 REV2a...
Страница 114: ...SPECIAL EQUIPMENT OPTIONAL 114 146 OI 250 EN REV7 REV0...
Страница 128: ...REPLACEMENT PARTS AND ACCESSORIES 128 146 OI 250 EN REV7 REV6...
Страница 130: ...HANDLING USED SULFUR HEXAFLUORIDE 130 146 OI 250 EN REV7 REV2...