06 Electrical Connection
User Manual V1.0-2023-10-30
50
NOTICE
• When using built-in meters for networking in a parallel system, only the master inverter needs to
connect CT cable.
• Please use the CT connection cable shipped in the attachment.
•
Inverter DO signal communication port, can be connected to dry contact signal with specification
parameters: Max ≤ 24Vdc, 1A.
•
EMS communication port: used to connect with the third party device. Third-party EMS device is
not supported in parallel system.
• In the parallel system, if you want to realize the DRED and RCR functions, you need only to
connect the DRED and RCR communication cables to the master inverter; To achieve remote
shutdown function, the remote shutdown communication cables needs to be connected to all
inverters.
•
To ensure communication quality, please connect the parallel communication port PAR1 of one
inverter to the parallel communication port PAR2 of another inverter.
• Other cables shall be prepared by the customer.
• To ensure the waterproof level of the inverter, do not remove the unused waterproof plugs of
communication port on the inverter.
6.8.1 Connecting the Communication Cable
Inverter parallel system networking
Master
Inverter 1
Slave
Inverter 1
Slave
Inverter n
n≤5