06 Electrical Connection
User Manual V1.0-2023-10-30
35
ON-GRID
BACK-UP
BAT
PV
CT
E-N Link
N-BAR
E-BAR
or
L3
N
PE
BMS
CT1
L1
L1 L2 L3
N
N
PE
PE
L1
CT2
L2
L2
CT3
L3
L3
N
PE
PE
L3
L2
L2
L1
L1
N
PE
Main Panel
Inverter
Battery
PV string
Do not connect this cable when the N and
PE cables of the BACK-UP load end are
connected together.
BACK-UP
load
Normal loads
Utility
grid
NOTICE
•
N and PE wiring via ON-GRID and BACK-UP ports of the inverter are different based on
the regulation requirements of different regions. Refer to the specific requirements of local
regulations.
• The inverter has a built-in meter that can be directly connected to the CT for use.
• When the connection length between CT and inverter exceeds 20m, the accuracy will decrease.
If there are high accuracy requirements, you can connect an external smart meter.
The N and PE cables of the BACK-UP load end are connected together for wiring in the distribution
box.
This wiring method is suitable for regions such as Australia and New Zealand.
6.3 Wiring Diagram
RCD
RCD