G500 Substation Gateway,

 

Quick Start Guide

 

GE Grid Solutions 

 

 

6

 

SWM0106-1.00-0 

GE Information 

 

Note

:   For Cyber Security reasons users are required to change this default root password using G500 Local Configuration Utility 

(

mcpcfg

). 

Warning

: The User is responsible for the new root password.  There is no back door, if lost a factory reset is required to recover a 

unit. Contact customer support for a Return Materials Authorization (RMA) estimate.

 

Default Administrator User – defadmin 

The G500 unit that comes from factory has below default administrator

(defadmin)

 user credentials. 

User Name:  

defadmin

 

Password:    

defadmin

  

The G500 supplies a temporary default administrator user with limited access for initial hardware configuration. This 

defadmin

 

user can perform only limited set of operations. 
The default administrator  (defadmin) user cannot perform  other settings or gateway  configuration changes, any operational 

workflows and login to runtime HMI. The default administrator (defadmin) user is intended to perform only below operations. 

 

To change or configure IP address to front and rear ethernet ports 

 

To add a nominated administrator-level user(s) 

 

To restore G500 Snapshots 

Warning

: The default administrator (defadmin) user will be deleted automatically once a nominated administrator user is created 

successfully. The local root user is required to recover the new administrator user if the credentials are lost 

Getting Started  

Please refer to G500 

Substation Gateway Instruction Manual

 (994-0152) for details about powering up the G500. Once the G500 is 

powered up use the below workflow(s) to prepare the G500 for operation. 

1.

 

Minimum setup for a new G500 without a pre-existing “Snapshot”: 

 

Task 1: Connect to the G500 

 

Task 2: Create a new Administrator user 

 

Task 3: Set the IP Address 

 

Task 4: Change the Root Password 

 

Task 5: Download the G500 Configuration 

2.

 

To restore an existing G500 “Snapshot”:  

 

Task 1: Connect to the G500 

 

Task 2: Restore the G500 Snapshot 

Note:

 In the following procedures/workflows, “

Enter

” indicates that the menu item number is typed in and then the Enter key is 

pressed. 

Setup G500 - First time setup 

Task 1: Connect to the G500 

Three methods are available to connect to a new G500 

 

Local monitor and keyboard via Local KVM interface (Keyboard Video Mouse) 

 

SSH to the front maintenance LAN port - default IP address 192.168.168.81 

 

USB Serial connection via the front USB type B maintenance port. 

Содержание G500

Страница 1: ...are Compartment Hardware Compartment The hardware compartment is a single package which contains Mounting Bracket Kit Top filler plate Bottom filler plate Left bracket Right bracket Bracket mounting h...

Страница 2: ...includes 4 metal pieces left bracket right bracket top filler plate and the bottom filler plate along with M4 quantity 10 and M3 quantity 8 screws The M4 screws are used to attach the left and right...

Страница 3: ...s Note The IRIG B input and output connectors are keyed and can only be installed in the corresponding position Missing Something Contact GE Customer Service right away and we ll figure it out Be sure...

Страница 4: ...user s password before executing the command Failing to use sudo prevents the command from executing no error feedback is displayed To launch mcpcfg from the G500 command line the user must type sudo...

Страница 5: ...All secure connections using certificates must be re associated with the new imported certificates e g Secure Connection Relay VPN Server etc License file key is not restored with the snapshot G500 e...

Страница 6: ...add a nominated administrator level user s To restore G500 Snapshots Warning The default administrator defadmin user will be deleted automatically once a nominated administrator user is created succes...

Страница 7: ...le to your computer USB port and to the G500 front maintenance port Note First time users will have to install all the required Windows drivers obtained from GE 2 Launch the Secure Terminal Emulator f...

Страница 8: ...Single or 2 Redundant or 3 PRP 6 Respond to the on screen prompts as required 7 Enter 2 Static IP Address 8 Type the IP address of the G500 and press Enter The default Subnet Mask as desired 9 Naviga...

Страница 9: ...prompt use the command ping 192 168 168 81 to ensure the G500 is connected The PC s network settings will have to be configured to the same subnet as the G500 to establish communications Task 2 Resto...

Страница 10: ...r additional details G500 Runtime HMI The G500 Runtime Human Machine Interface HMI is available to view real time information on G500 With the HMI a user has the option to monitor the status of a subs...

Страница 11: ...dress or Remote Port 1 Locate the G500 Runtime HMI shortcut 2 Copy the shortcut to the desktop or a desired location or pin it to Taskbar or Start Menu 3 Right click on the shortcut and select Propert...

Страница 12: ...o of its display ports Display Port 1 DP1 and Display Port 2 DP2 When single monitor is connected the connected monitor becomes the Primary Display Port DP1 is primary by default when two monitors are...

Страница 13: ...rom the G500 Runtime HMI or G500 Command Line to check the updated Secret Signature Note The default secret signature should be replaced with a secure signature chosen by your security administrator T...

Страница 14: ...t without the prior written permission of General Electric Company The information contained in this online publication is proprietary and subject to change without notice The software described in th...

Отзывы: