34
Table 9: Alarm operation (mains powered)
FP2416/2464 & FP2432/24128
FP2864/28255 &
FP2864N/28255N
Mains load (maximum)
200 VA
200 VA
Total output current (27.6 V)
4 A
4 A
Required battery charging current (maximum
battery capacity)
0 A
0 A
Current required by system
0.6 A
1 A
Available auxiliary current
3.4 A
3 A
Charging current based to charge batteries up to 80% in 24 hours at 75% efficiency.
Environmental specifications
FP/FR12xx & FR2000
FP1216EN & FP1264 &
FP1216N / FP1264N
FP/FR2xxx &
FP2864N/28255N
IP rating (enclosure)
IP54
IP54
IP54
Operating temperature
-5 ºC to +40 ºC
- 5 ºC to +40 ºC
- 5 ºC to +40 ºC
Storage temperature
-20 ºC to +60 ºC
-20 ºC to +60 ºC
-20 ºC to +60 ºC