1200-2000 Series Fire Panels, Repeaters, and Emulators
Interconnection and Wiring Guide
30
6 Technical specifications
6.1 Loop
specifications
Maximum number of loops per panel
1200 series................................................................................................................................................................................................... 4
2000 series................................................................................................................................................................................................... 8
Loop current
Loop overload.............................................................................................................................................................................>500 mA
Loop operating load .......................................................................................................................................................max. 100 mA
Class A / Class B loop configuration
LC2002............................................................................................................................................................ 2 x Class A / 4 x Class B
LC1502............................................................................................................................................................ 2 x Class A / 4 x Class B
With the following exceptions:
FP1200-00............................................................................................. 2 x Class A / 4 x Class B or 4 x Class A / 4 x Class B
FP1200-01..................................................................................................................................................... 2 x Class A / 2 x Class B
FP1200-02..................................................................................................................................................... 2 x Class A / 2 x Class B
Maximum number of addressable devices per loop
900 protocol ...........................................................................................................................................................................................126
2000 protocol ........................................................................................................................................................................................128
Maximum number of addressable devices per panel
900 protocol ........................................................................................................................................................................................ 1008
2000 protocol ..................................................................................................................................................................................... 1024
Zones
Maximum number of zones...................................................................................................................................16 or 64 zones*
Maximum number of zones (for control purposes) .............................................................................................................255
* Expandable to 32/128, 48/192 or 64/255 zones in cabinet size B