• Open fixture by unlocking two latches. Keep one
latch hooked onto the housing ear to suspend the
light
engine.
UL Units:
• Terminals are readily accessible on terminal board
and will accept service leads ranging in size from
AWG No. 16 through No. 6.
• Service leads (See fixture labeling for supply wire
temperature rating) should extend through mounting
bracket approximately 7 inches.
• Attach service leads to terminal board as shown on
luminaire
nameplate.
• See table below for screw torques (See Table 1).
• A wiring diagram is provided on a label in luminaire.
NOTE:
Make all electrical connections in accordance with
the National Electrical Code and any applicable local code
requirements including grounding.
NOTE:
Verify that supply voltage is correct by comparing
it to nameplate.
WIRING
4
CAUTION
Risk of Burn:
Allow light engine/fixture to cool before handling.
TABLE 1.
Terminal Board Torque Table UL Units:
Wire Range Copper
Aluminum
Torque (in lbs)
10-16
30
8-6
SOL,STR
STR6,SOL,STR
45
Terminal Board Connections:
(See Figure 3.)
Terminal Board Positions
Supply Type
L1
High
Line
G
Ground
N/L2
Line/Neutral
• Rotate the light engine into position and secure by
snapping two latches on light engine to “ears” on
hood. (See Figure 4)
Figure 3
Figure 4
Tether
Ear
Latch
Wire