Chapter 3: Programming
EST iO64 and iO500 Technical Reference Manual
117
Note:
By default, NACs, zones, and devices are assigned to
correlation group 1.
Loop Configuration
Loop Class
Zone
Correlation Groups
⇩
Correlation Groups
Number 01<>
⇩
Correlation Group 01
Add/Rem Zone
Add/Rem Device
Add/Rem Panel NAC
⇩
To program correlation groups:
1. Access the loop configuration options menu. See "Loop
configuration options."
2. Choose Correlation Groups.
3. Choose a correlation group (1 to 32).
4. Choose one of the following:
Add/Rem Device to add or remove a device.
Add/Rem Zone to add or remove a zone.
Add/Rem Panel NAC to add or remove a NAC.
5. If you chose Add/Rem Device, choose the loop the device is on.
Note: If your panel only has one loop, the loop selection screen
does not display. Go to the next step.
6. Enter the device, zone, or NAC number.
7. On the Status line, press Enter to include it or exclude it.
When it is added to the correlation group, “Included” is
displayed.
When it is removed from a correlation group, “Excluded” is
displayed.
8. Repeat steps 5 and 6 to add or remove other devices, zones, or
NACs.
9. Repeat steps 3 to 7 until each correlation group is programmed
as desired.
10. Continue programming your system or press Menu to exit menu
mode.
Add/Rem Device
Device 001<>
Status Excluded
<-Enter <-Cancel