Contact ID event codes
Many of the events that take place in a fire alarm control panel are
sent to a central monitoring station (CMS) via a dialer or over a
network. The following table lists the control panel's panel and loop
events and their default Contact ID (CID) codes. Some events do not
have a CID code. Through programming, you can assign whatever
code you desire to an event that does not have a code. You can also
change the default codes to whatever code you desire.
Event
CID
AC power (disable)
500
AC power (trouble)
301
Alarm active
110
Annunciator trouble
334
Aux. power 1 (disable)
500
Aux. power 1 (trouble)
312
Aux. power 2 (disable)
500
Aux. power 2 (trouble)
312
Battery charger (disable)
500
Battery charger (trouble)
309
Battery low (disable)
500
Battery low (trouble)
302
Battery missing (disable)
500
Battery missing (trouble)
311
Clear history
621
Common alarm
110
Common disable
500
Common monitor
140
Common supervisory
200
Common trouble
373
Common trouble for network dialer
373
Common trouble for telco dialer
373
Date
625
Device trouble
373
Device disable
570
Device pre alarm
118