GE
Security
EST Fire & Life Safety
EST iO64 and iO500
Technical Reference Manual
P/N 3101112 • REV 2.0 • ISS 30JUL08
Страница 1: ...GE Security EST Fire Life Safety EST iO64 and iO500 Technical Reference Manual P N 3101112 REV 2 0 ISS 30JUL08...
Страница 2: ...tered trademarks of the manufacturers or vendors of the respective products Intended use Use this product only for the purpose it was designed for refer to the data sheet and user documentation for de...
Страница 3: ...ring 58 Panel low voltage wiring 59 Battery wiring TB8 60 Notification appliance circuit wiring TB2 61 Device loop wiring 63 Alarm trouble and supervisory relay wiring TB3 65 Remote annunciator wiring...
Страница 4: ...a device in alarm 200 Appendix A Panel specifications 201 Control panel specifications 202 Appendix B Worksheets 205 Battery calculation worksheet 206 Notification appliance circuit calculations work...
Страница 5: ...ccuracy of its contents GE Security assumes no responsibility for errors or omissions iO64 and iO500 FCC compliance This equipment can generate and radiate radio frequency energy If the equipment is n...
Страница 6: ...tration number and ringer equivalence number REN for this equipment If requested this information must be provided to the telephone company For equipment approved after July 23 2001 This dialer compli...
Страница 7: ...manufacturer for repair or warranty information If the dialer is harming the telephone network the telephone company may request that you disconnect the dialer until the problem is resolved The diale...
Страница 8: ...ution may be particularly important in rural areas Note The Load Number LN assigned to each terminal device denotes the percentage of the total load to be connected to a telephone loop which is used b...
Страница 9: ...ent needed Protected Premises Local Fire Alarm System Control panel Appropriately sized batteries Auxiliary Fire Alarm System Local Energy Type Control panel Appropriately sized batteries CTM module R...
Страница 10: ...the optional panel accessories See each component s installation sheet instructions for more information 7 Review the wire routing See Cabinet wire routing 8 Connect the field wiring See the appropri...
Страница 11: ...6 Event details display screens 6 System LEDs 9 LED display expander LEDs 10 Control buttons 11 Component descriptions 13 Events with event messages 15 Printout examples 15 Event ID numbers and descri...
Страница 12: ...Enabling a zone 38 Disabling a panel event 39 Enabling a panel event 41 Disabling a loop event 42 Enabling a loop event 44 Disabling a panel NAC 45 Enabling a panel NAC 46 Disabling enabling the diale...
Страница 13: ...program the panel Front panel display layout LCD display System LEDs Control buttons 00 00 00 01 01 07 Control panel operations The control panel operates in either normal mode or off normal mode Norm...
Страница 14: ...and the panel buzzer Executes the appropriate programmed output response for the input that signaled the event Communicates event information to the remote annunciator Sends a record of the event to...
Страница 15: ...e of inactivity System normal display screen The LCD display shows the system normal display screen when the control panel is in the normal quiescent state The screen displays the following Time Displ...
Страница 16: ...Event type message The event message for the type of event taking place Device label The label for the device either the default label or a custom programmed label LCD display under off normal conditi...
Страница 17: ...ber Device number Device type Serial number Internal event panel and loop events details display screen Internal Event 021 Internal event number Note See Event ID numbers and descriptions for a list o...
Страница 18: ...Manual To access the event details screen 1 When an event takes place press Enter on the front panel 2 View the event details The event details screen is displayed for 15 seconds and then returns to t...
Страница 19: ...es when performing an audible walk test Steady indicates a silent test Monitor Yellow LED Flashes when there is an active monitor event on any loop On steady once acknowledged Service Detector Yellow...
Страница 20: ...zones 1 through 12 and 17 through 28 if the second LED expander is installed LED 1 Alarm Red LED flashes LED 2 Trouble Yellow LED flashes LED operation zones 13 through 16 and 29 through 32 if the sec...
Страница 21: ...rill Initiates a drill when the button is pressed for two seconds The LED next to the button indicates the function is active Pressing drill a second time turns off the drill function Note Drill will...
Страница 22: ...enu Display mode Enters the menu mode Menu mode Exits menu mode Space Enters a space such as when placing a space between words Comma Enters a comma Alphanumeric keypad Entry mode Pressing a button on...
Страница 23: ...ain AC wiring block and fuse holder Provides connections for 120 or 230 volt AC primary power from dedicated service Includes a primary power fuse 5 A 3 RS 232 card connector J3 Provides a connection...
Страница 24: ...nector J7 Provides a connection for the optional loop expander card only on the 250 500 point panel 10 Class A card connector J2 Provides a connection for the optional Class A card only on the 64 poin...
Страница 25: ...T ACT Zone supervisory Supervisory SUPV ACT Input supervisory latching Supervisory SUPV ACT Input supervisory nonlatching Supervisory SUPV ACT Monitor type reporting Zone monitor Monitor MON ACT Input...
Страница 26: ...00 18 01 01 2007 Time and date the event took place E 010 Event 010 see Event ID numbers and descriptions Loop 2 initializing Label could be the default label or a custom label Zone event ALRM ACT 18...
Страница 27: ...A device on loop 1 has an address set to zero 009 Loop 1 mapping Loop 1 is mapping its devices 010 Loop 2 initialization Loop 2 is starting up 011 Loop 2 fault A short or open was detected on loop 2 a...
Страница 28: ...ay not be able to charge the batteries 036 Battery low The batteries are low on charge 037 Battery missing The battery is no longer connected 038 AC power There is a problem with the panel s AC power...
Страница 29: ...network receiver failed 057 Net recvr config fault The panel failed to communicate with the network receiver after a configuration change 058 NAC 1 trouble An open or short has been detected on NAC 1...
Страница 30: ...maintenance alert or test has been detected on zone 8 079 Zone 9 active trouble disable prealarm alarm verify maintenance alert or test has been detected on zone 9 080 Zone 10 active trouble disable...
Страница 31: ...ve trouble disable prealarm alarm verify maintenance alert or test has been detected on zone 25 096 Zone 26 active trouble disable prealarm alarm verify maintenance alert or test has been detected on...
Страница 32: ...ayed on a secondary screen called the Event Details screen To access the event details screen 1 When an event takes place press Enter on the front panel 2 View the event details For a description of t...
Страница 33: ...display The Reset LED lights Devices in an off normal state remain in their off normal state until the element causing their off normal state clears When reset is complete Reset clears from the LCD d...
Страница 34: ...ers The ACK Panel Silence LED lights To silence the panel buzzer 1 Press the Ack Panel Silence button 2 Determine the type of condition that caused the buzzer to sound alarm trouble supervisory or mon...
Страница 35: ...mmed as waterflow cannot be silenced until the activated devices are restored to normal via a panel reset After the waterflow device events restore the Signal Silence button or the auto signal silence...
Страница 36: ...imer expires any NACs that are programmed as silenceable are deactivated and the Signal Silenced LED is illuminated If another event takes place that activates the previously silenced notification app...
Страница 37: ...l Silence button you can press the Signal Silence button a second time to turn the notification appliances back on Note NACs re sound automatically if a new alarm from another device is received When...
Страница 38: ...annunciator and tests the LCD display so that you can verify proper operation LEDs stay on for 15 seconds Reports Test Control Program To conduct a lamp test 1 Press the Menu button 2 Choose Test 3 Ch...
Страница 39: ...ontrol Enable Disable Activate Restore Activate Restore Device Panel NAC Device Loop 01 To activate a device 1 Press the Menu button 2 Choose Control 3 Enter your password the minimum of a level one p...
Страница 40: ...Panel NAC Device Loop 01 To restore a device 1 Press the Menu button on the front panel 2 Choose Control 3 Enter your password the minimum of a level one password is required 4 Choose Activate Restor...
Страница 41: ...gram Enter Password 0000 Control Enable Disable Activate Restore Activate Restore Device Panel NAC To activate a NAC 1 Press the Menu button 2 Choose Control 3 Enter your password the minimum of a lev...
Страница 42: ...ogram Enter Password 0000 Control Enable Disable Activate Restore Activate Restore Device Panel NAC To restore a NAC 1 Press the Menu button on the front panel 2 Choose Control 3 Enter your password t...
Страница 43: ...and enables the device Note If the device you are disabling is active a warning message is displayed Reports Test Control Program Enter Password 0000 Control Enable Disable Activate Restore Enable Dis...
Страница 44: ...Chapter 1 System operation 34 EST iO64 and iO500 Technical Reference Manual Device Disable 001 Device 001 Press the Menu button to exit menu mode Warning Device Active Continue Cancel...
Страница 45: ...000 Control Enable Disable Activate Restore Enable Disable Device Zone Panel Event Device Loop 01 Device Enable 001 Device 001 To enable a device 1 Press the Menu button 2 Choose Control 3 Enter your...
Страница 46: ...the LCD display increment If you are using an LED display expander the zone LEDs blink for the disabled zone Resetting the panel has no effect on a disabled zone but removing all power from the panel...
Страница 47: ...Chapter 1 System operation EST iO64 and iO500 Technical Reference Manual 37 Zone Disable 01 Zone 01 or Press the Menu button to exit menu mode Warning Device Active Continue Cancel...
Страница 48: ...nabling is active a warning message is displayed Reports Test Control Program Enter Password 0000 Control Enable Disable Activate Restore Enable Disable Device Zone Panel Event Zone Enable 01 Zone 01...
Страница 49: ...s on the LCD display increment A message indicating the event that is disabled is displayed on the LCD display Note Not all panel events can be disabled Panel events that cannot be disabled are labele...
Страница 50: ...e Panel Event 5 Choose Panel Event 6 Select the event type that you want to disable Refer to Event ID numbers and descriptions for event descriptions and the list above for the events that can be disa...
Страница 51: ...n the LCD display indicating the disabled event disappears Reports Test Control Program Enter Password 0000 Control Enable Disable Activate Restore Enable Disable Device Zone Panel Event To enable an...
Страница 52: ...s that cannot be disabled are labeled as forbidden The following loop events can be disabled Loop 1 fault event ID 001 Loop 2 fault event ID 011 Loop 1 card fault event ID 003 Loop 2 card fault event...
Страница 53: ...EST iO64 and iO500 Technical Reference Manual 43 Enable Disable Zone Panel Event Loop Event 7 Press Enter 8 Press Cancel to return to the previous menu or Press the Menu button to exit menu mode Loop...
Страница 54: ...e LCD display indicating the disabled loop event disappears Reports Test Control Program Enter Password 0000 Control Enable Disable Activate Restore Enable Disable Zone Panel Event Loop Event To enabl...
Страница 55: ...s state Resetting the panel has no effect on a disabled NAC but removing all power from the panel clears the disable and enables the NAC Reports Test Control Program Enter Password 0000 Control Enable...
Страница 56: ...normal The disabled points and active points counters on the LCD display decrement Reports Test Control Program Enter Password 0000 Control Enable Disable Activate Restore Enable Disable Panel Event L...
Страница 57: ...rements Pending events in the CMS queue are purged To disable the dialer and network card 1 Press Remote Disconnect 2 Enter your password the minimum of a level one password is required Enabling If th...
Страница 58: ...Chapter 1 System operation 48 EST iO64 and iO500 Technical Reference Manual Remote Disconnect button 00 00 00 01 01 07...
Страница 59: ...e Drill will not operate with an active alarm or supervisory event at the panel To start and stop a drill 1 To start a drill press and hold the Drill button for two seconds The LED next to the button...
Страница 60: ...the zone in walk test If an unselected zone or device goes into alarm or trouble all programmed outputs operate as programmed Zones and devices behave as follows during walk test For alarm events the...
Страница 61: ...The panel terminates walk test if any of the following occur There are 30 minutes of inactivity for the zone or device being tested Walk test is stopped by the user Reports Test Control Program Test W...
Страница 62: ...ending the walk test Once the reset is complete you can end the walk test and view a walk test report 1 Press the Menu button 2 Choose Test 3 Choose Walk Test Silent or Walk Test Audible 4 Choose eith...
Страница 63: ...electronics installation 56 Cabinet wire routing 57 AC power wiring 58 Panel low voltage wiring 59 Battery wiring TB8 60 Notification appliance circuit wiring TB2 61 Device loop wiring 63 Alarm troubl...
Страница 64: ...e cabinet and standby batteries 2 Install a semiflush trim ring optional to the cabinet 3 Fasten the cabinet box to the framing studs where indicated Surface mount Semiflush mount Trim ring Backbox an...
Страница 65: ...ference Manual 55 Cabinet backbox backbox with door and backbox with door and trim ring attached D1 D2 D3 D4 D5 D6 Surface mounting holes Semiflush mounting holes Surface mounting holes D8 D7 D9 Backb...
Страница 66: ...ical Reference Manual Panel electronics installation The panel electronics must be installed in the cabinet box Note Wait until the possibility of construction damage or vandalism has passed before in...
Страница 67: ...wer limited wiring in the unshaded area at all times Cabinet wire routing 00 00 00 01 01 07 1 1 Power limited only when connected to a power limited source If connected to a nonpower limited source al...
Страница 68: ...d branch supply WARNING Never replace the fuse while the circuit is energized The replacement fuse must be of equivalent size and type CAUTION The middle connection EARTH GND on the terminal block mak...
Страница 69: ...nstallation and wiring EST iO64 and iO500 Technical Reference Manual 59 Panel low voltage wiring Circuit specifications Circuit voltage 24 VAC Panel low voltage wiring TB1 EGND 24 VAC IN Terminal wiri...
Страница 70: ...64 point control panel cabinet and two 18 Ah batteries will fit in the 250 500 point control panel cabinet If larger batteries are required you must use a GE Security battery cabinet To determine whi...
Страница 71: ...t panel 6 0 A total 2 5 A max per circuit at 120 230 VAC 60 Hz 5 0 A total 2 5 A max per circuit at 230 VAC 50 Hz Max resistance 26 total Max capacitance 0 35 F EOLR 15 k 1 2 W P N EOL 15 Synchronized...
Страница 72: ...iO500 Technical Reference Manual 64 point panel Class B wiring NAC1 NAC2 NAC2 NAC1 EOLR TB2 250 500 point panel Class B wiring TB2 TB6 EOLR NAC3 NAC4 NAC4 NAC3 EOLR NAC1 NAC2 NAC2 NAC1 250 500 point...
Страница 73: ...4 Circuit specifications Class B or Class A Communication line voltage Maximum 20 6 V peak to peak Circuit current 0 5 A max Max total resistance 66 Max total capacitance 0 5 F Max resistance between...
Страница 74: ...op PRI Loop card Loop devices Isolator module Isolator module UL ULC listed enclosure Data line Loop devices with isolator base Loop card LEDs There are three LEDs on the card that indicate loop commu...
Страница 75: ...ervisory event common supervisory The alarm relay changes over on any alarm event common alarm Note Relay circuits can only be connected to power limited sources Relays are not supervised Relay specif...
Страница 76: ...wire Circuit resistance 90 Circuit capacitance 0 3 F Ground fault impedance 0 to 5 k RS 485 communications speed 9600 baud Wiring 18 to 14 AWG 1 0 to 2 5 sq mm twisted pair Max wire run 4 000 feet 1 2...
Страница 77: ...Chapter 2 Installation and wiring EST iO64 and iO500 Technical Reference Manual 67 Annunciator channel wiring Class B TB4 Channel 1 Channel 2 CH1 IN CH1 IN CH2 IN CH2 IN Annunciator...
Страница 78: ...power by 500 mA Note If more than 1 5 A is required you must use a power limited and regulated 24 VDC auxiliary booster power supply that is UL ULC listed for fire protective signaling systems Contin...
Страница 79: ...to 75 and the Line Cut timer in the line card itself set to 175 seconds If you are unsure of the firmware version in the receiver or there are communication faults between the panel and the receiver t...
Страница 80: ...ring Tip Ring Tip Ring Tip Ring Tip Ring Protected premises punch down block TELCO Line 2 TELCO Line 1 PBX RJ 31X block supplied by installer 8 position 4 conductor modular cords supplied by installer...
Страница 81: ...7 F Wire length 50 feet max Signal voltage 10 V Operating current Standby Alarm 13 mA Max 20 mA Printer communication speed 9600 baud SA 232 wiring connections RTS green wire TXD white wire RXD red wi...
Страница 82: ...B 25 Description GND COM pin 7 Black wire ground connection RTS DTR pin 20 Green wire printer supervision TXD RXD pin 3 White wire communication RXD TXD pin 2 Red wire communication Computer download...
Страница 83: ...Reference Manual 73 DB 9 pin connections DB 9 male front view SA 232 card to computer DB 9 connections SA 232 card DB 9 Description GND COM pin 5 Black wire ground connection RTS Not used TXD RXD pin...
Страница 84: ...d are only used when wiring NACs Class A on a 64 point control panel Circuit specifications Operating current Standby 3 mA Alarm Max 60 mA Max resistance 26 Max capacitance 0 35 F Max current 2 5 A pe...
Страница 85: ...rlier the Timeout Seconds must be set to 60 the Hello Timer set to 75 and the Line Cut timer in the line card itself set to 175 seconds If you are unsure of the firmware version in the receiver or the...
Страница 86: ...uirements When connecting a CTM to the panel the following hardware and programming requirements must be met The NAC used must be dedicated to CTM use only All alarm zones must be programmed to activa...
Страница 87: ...5 trip coil max loop resistance 25 2 This circuit is nonpower limited and is supervised for grounds and opens but not shorts 3 Supervised and power limited 4 NAC must be programmed for city tie 5 CTM...
Страница 88: ...mitter it can be connected to either a single circuit alarm or alarm and trouble or up to three circuits alarm supervisory and trouble Below are application diagrams for using the RPM module For detai...
Страница 89: ...RPM yellow wire From COM on RPM black wire From 24 on RPM red wire Control panel TB3 TRBL C NC SUP NC ALM 24VOUT NO C NO Alarm supervisory and trouble transmitted on separate circuits Note JP1 on the...
Страница 90: ......
Страница 91: ...asswords 95 Restoring the factory default settings 96 Programming the programmable keys 97 Clearing the history 100 Restarting the panel 101 Enabling the RS232 CU Enable command 102 Contact ID event c...
Страница 92: ...mming 141 Printer programming 143 Network card programming 144 Lock remote read programming 145 AC voltage programming 146 Panel operation programming 147 Panel events programming 149 Loop events prog...
Страница 93: ...or option Permitted in UL 864 Y N Possible settings Settings permitted in UL 864 Panel default AC fail delay Y 0 to 15 hours 1 2 or 3 hours 3 hours Telephone line cut supervision duration Y 1 to 120...
Страница 94: ...programming custom programming You can manually custom program the panel by going through each programming option and selecting a value for that option See the advanced programming section for more i...
Страница 95: ...e cursor down Menu Used to open and close the primary menu screen Enter Takes you to a programming option s sub menu or jumps you to the Save function in the menu so you can quickly save your data Key...
Страница 96: ...Technical Reference Manual Default passwords The panel comes standard with a default set of passwords Level 1 1111 Level 2 2222 Remote annunciator 3333 Note It is recommended that you change the defau...
Страница 97: ...s may not be visible or available Panel operation options Language English Marketplace US AC fail delay 3 hours Zone resound On Reset inhibit Off Auto signal silence Off Day start 06 00 Night start 18...
Страница 98: ...Printer Yes Disable Dialer Acct 1 Disable NET Yes Disable CID 521 NAC1 522 NAC2 526 NAC3 527 NAC4 Test Printer Yes Test Dialer Acct 1 Test NET Yes Test CID 600 Annunciator class Class B Annunciators...
Страница 99: ...es Event notification Device Hello time 25 Timeout 40 Receiver 2 Line 2 Swinger shutdown Off Printer Type Unsupervised Event notification Trouble Printer Yes Trouble Coder 00 00 00 00 Trouble Dialer A...
Страница 100: ...Dialer Acct 1 Test NET Yes Test CID 614 Device Day sensitivity Least Night sensitivity Least Day prealarm Off Night prealarm Off Base follow Alarm Type input device Depends on type of device and marke...
Страница 101: ...larm verify Dialer None Alarm verify NET No Alarm verify CID 118 Maintenance alert Printer Yes Maintenance alert Coder 00 00 00 00 Maintenance alert Dialer Acct 1 Maintenance alert NET Yes Maintenance...
Страница 102: ...Program Program Auto Program Advanced Program Date and Time Enter Password 0000 Date and Time Date 01 01 2007 Time 00 00 Daylight Savings To set the time and date 1 Press the Menu button 2 Choose Pro...
Страница 103: ...se Daylight Savings 6 Set daylight saving to Yes The panel recognizes daylight saving time No The panel does not recognize daylight saving time 7 Set the Month Start 01 to 12 8 Set the Month End 01 to...
Страница 104: ...EST iO64 and iO500 Technical Reference Manual hour you would enter the following when programming Month start 03 Week start 2 Week day start 1 Hour start 02 Month end 11 Week end 1 Week day end 1 Hour...
Страница 105: ...tes of inactivity Reports Test Control Program Program Date and Time Clear History Password Enter Password 0000 Password Level 1 Level 2 Remote Ann Enter Old Password 0000 To set the passwords 1 Press...
Страница 106: ...s Test Control Program Program Clear History Password Restore Defaults Enter Password 0000 To restore the default settings 1 Press the Menu button 2 Choose Program 3 Choose Restore Defaults 4 Enter yo...
Страница 107: ...beled as to their function with a slip in label To operate the buttons you must be logged on with a minimum level one password Note The buttons can be programmed before they are enabled For the button...
Страница 108: ...enable disable activate or restore panel NACs Device Programs the key to enable disable activate or restore a single device or multiple devices Zone Programs the key to enable or disable zones 9 Sele...
Страница 109: ...zone number that you want to add and press Enter The zone number will automatically increment to the next zone number so that you can quickly add all desired zones If the zone is already added remove...
Страница 110: ...may want to clear history before turning over the system to the building owner so they can start with a clean history If your system history is full of events from a faulty device problem or situation...
Страница 111: ...e panel without having to cycle AC power Reports Test Control Program Program Laptop Enable Programmable Keys Panel Restart Enter Password 0000 To restart the panel 1 Press the Menu button 2 Choose Pr...
Страница 112: ...ctivity meaning that if the command is enabled but does not connect to the CU PC within four minutes the command turns off and must be reenabled Reports Test Control Program Program Restore Defaults U...
Страница 113: ...e You can also change the default codes to whatever code you desire Event CID AC power disable 500 AC power trouble 301 Alarm active 110 Annunciator trouble 334 Aux power 1 disable 500 Aux power 1 tro...
Страница 114: ...ormal test 608 Dialer configuration 354 Drill 601 Duct active 116 Ground fault disable 500 Ground fault trouble 310 Heat active 114 Internal fault 307 Loop 1 initialization 000 Loop 1 fault disable 50...
Страница 115: ...1 Loop 2 map mismatch 331 Loop 2 over limits 331 Loop 2 address zero 331 Loop 2 mapping 000 Monitor active 140 NAC1 trouble 321 NAC2 trouble 322 NAC3 trouble 326 NAC4 trouble 327 NAC1 disable 521 NAC2...
Страница 116: ...ive 111 Supervisory active 200 System startup 000 System AC power disable 500 System AC power trouble 301 Test fire 604 Time 625 Walk test 607 Waterflow active 113 Zone active 110 Zone trouble 373 Zon...
Страница 117: ...e system automatically finds all of the devices connected to your system and assigns them to a zone The number of devices assigned to a zone is based on the type of panel 64 point panel Four devices p...
Страница 118: ...initiated by the detector The bases that work with this option are the sounder base and relay base For example if the detector has a prealarm setting but base follow is set to alarm the base s relay...
Страница 119: ...ts will be sent Primary receiver number Enter the primary receiver s phone number Up to 20 digits 0 9 and The comma causes a two second delay in dialing The number or hash symbol and the asterisk symb...
Страница 120: ...000 000 000 000 Event Notif Event Network Receiver 000 Line 000 Save NET options programming Account ID Enter the central monitoring station CMS account s six digit ID code IP Enter the IP address fo...
Страница 121: ...When you are finished labeling make sure the cursor is on the device number field and press the Cancel button to exit and go to the next auto programming option Zone 01 Label goes here Label continued...
Страница 122: ...tion options loops devices zones etc panel configuration options annunciators dialer network printer etc panel operation options language marketplace AC fail delay etc panel events and loop events All...
Страница 123: ...options include Correlation groups programming Device programming Loop 2 enable Loop class programming Zone programming Panel operation options include Language Marketplace AC fail delay Zone resound...
Страница 124: ...gramming Advanced programming for panel and loop options is covered in the following topics in this chapter Programming events Advanced programming lets you create custom responses to these types of e...
Страница 125: ...lt setting which can be used with no additional programming See Factory Default Settings for more information Reports Test Control Program Program Incremental Program Auto Program Advanced Program Ent...
Страница 126: ...s in Group 1 turn on Correlation group operation Correlation group Input devices smoke detector pull station by themselves or in a zone Output devices and NAC devices strobe horn Input device Zone inp...
Страница 127: ...Add Rem Zone to add or remove a zone Add Rem Panel NAC to add or remove a NAC 5 If you chose Add Rem Device choose the loop the device is on Note If your panel only has one loop the loop selection sc...
Страница 128: ...Select the correlation group that you want to correlate assign the device to Select Yes to add the device to the correlation group or No to not add the device to the correlation group When finished c...
Страница 129: ...realarm condition The base will not restore until the prealarm event restores which can happen if the device goes into alarm If you do not set a prealarm threshold the base will never activate Base fo...
Страница 130: ...ices are restored to normal via a panel reset Circuit cannot be restored until devices are restored to normal and the panel is reset Duct alarm For duct smoke detectors All activations are immediately...
Страница 131: ...connected to visible notification appliance that do not turn off when Signal Silence is pressed Relay module Relay nonsilence For the connection of relay devices that do not follow signal silence Rel...
Страница 132: ...to program both addresses are still displayed but in reverse order e g 002 001 Note Depending on the type of device you are programming some of the options in the table below may not be available 6 Wh...
Страница 133: ...cond loop so that it can be programmed Loop Configuration Mapping Loop 2 Enable Yes Save To enable loop 2 1 Access the loop configuration options menu See Loop configuration options 2 Choose Loop 2 En...
Страница 134: ...ss Zone Correlation Groups Loop Class Loop 1 Class A Loop 2 Class A Save To program loop class 1 Access the loop configuration options menu See Loop configuration options 2 Choose Loop Class 3 Select...
Страница 135: ...unds Depending on the number of devices on your panel the amount of time it takes to map can vary Note When mapping is finished a map mismatch event may be generated if the current map does not match...
Страница 136: ...ing Loop 1 No Loop 2 No Save OR To disable mapping 1 Access the loop configuration options menu See Loop configuration options 2 Choose Mapping 3 Select the loop for which you want to disable mapping...
Страница 137: ...he map in the panel database which syncs the two maps and removes the map fault from the system Another way to get a map mismatch is by adding a new device to your system The panel sees the device and...
Страница 138: ...he configuration utility but the device has not been physically wired into the system when you download to the panel from the configuration utility the configuration utility map will not match the pan...
Страница 139: ...the zone are only connected to waterflow switches Note Do not mix device and zone types For example do not place a nonlatching supervisory device in an alarm zone When the supervisory device activate...
Страница 140: ...Groups Zone Number 01 Zone 01 Zone 01 Type Alarm Label Correlation Groups To program a zone 1 Access the loop configuration options menu See Loop configuration options 2 Choose Zone 3 Choose the zone...
Страница 141: ...efault Settings for more information Notes CMS device is only available if the dialer or network card is installed Printer is only available if the printer RS 232 card is installed IP MSK and GWY are...
Страница 142: ...iating device or zone Note The panel can only play one code at a time For example device 1 is coded as 1 2 3 4 and is associated with NAC1 and device 2 is coded as 5 6 7 8 and is associated with NAC2...
Страница 143: ...ion is sent to dialer account two None Event information is not sent to the dialer NET Yes or No Specifies if event information is sent to the connected network CID Contact ID event code 000 to 999 Pa...
Страница 144: ...ss B Panel Configuration Panel NAC Ann Class A Annunciator To program annunciator class 1 Access the panel configuration options menu See Panel configuration options 2 Choose Ann Class 3 Select either...
Страница 145: ...and two lines When finished choose Save Event notification Set the trouble event information by setting the notification information When finished choose Save See Factory default settings for annuncia...
Страница 146: ...O500 Technical Reference Manual Annunciator 01 Type Off Expanders 1 Label 5 When you finish programming each option choose Save 6 Continue programming your system or press Menu to exit menu mode Annun...
Страница 147: ...e number of consecutive times a single trouble event is transmitted over a 24 hour period before it is no longer sent Some trouble events are not affected when swinger shutdown is set They are Loop 1...
Страница 148: ...sent to both dialer accounts Acct 1 Event information is sent to dialer account one Acct 2 Event information is sent to dialer account two None Event information is not sent to the dialer NET Yes or N...
Страница 149: ...r hash symbol and the asterisk symbol are used with calling feature codes and services Consult your telephone service provider for more information Enter the secondary receiver s phone number Up to 20...
Страница 150: ...f or 1 to 45 days Specifies how often the dialer performs a test call Note The off setting is not acceptable for UL ULC installations Refer to UL 864 programming requirements for details Test time Set...
Страница 151: ...notification settings for reporting events Make sure your device event notification settings are correct Refer to Device programming for more information Zone When a device is a member of a zone only...
Страница 152: ...rogram the network receiver 1 Access the panel configuration options menu See Panel configuration options 2 Choose CMS Device 3 Choose Network 4 Program the network using the Network programming optio...
Страница 153: ...the printer s switch settings Unsupervised The printer connection is not supervised None CU There is no printer or you are connecting a computer running the configuration utility to the panel 5 Choose...
Страница 154: ...tion utility or upload and view system reports using the configuration utility Network card default settings IP 192 168 001 003 Mask 255 255 255 000 Gateway 000 000 000 000 Panel Configuration IP 192...
Страница 155: ...ou log onto the panel with a level two password all communication options are available and there are no restrictions Panel Configuration MSK 255 255 255 000 GWY 000 000 000 000 Lock Rmt Read Yes Pane...
Страница 156: ...models Use 220 230 and 240 only on 230 VAC control panel models Panel Configuration GWY 000 000 000 000 Lock Rmt Read Yes AC Voltage 120 To program AC voltage 1 Access the panel configuration options...
Страница 157: ...ch time a device in the zone goes into alarm even if they were silenced Off Inhibits the NACs from turning on again after they were silenced when a second device in the zone goes into alarm Note The o...
Страница 158: ...device number So if an event takes place on loop 1 the remote annunciators will display it as loop 17 Loop 2 events will display on the annunciator LCD as loop 2 events Key 1 Set to Enabled Allows key...
Страница 159: ...ouble Yes Acct 1 Yes 309 Battery low disable Yes None No 500 Battery low trouble Yes Acct 1 Yes 302 Battery missing disable Yes None No 500 Battery missing trouble Yes Acct 1 Yes 311 Clear history No...
Страница 160: ...omm fault trouble Yes Acct 1 No 354 Panel silence No None No 315 Program mode Yes Acct 1 Yes 627 Reset Yes Acct 1 Yes 305 Reset Silence inhibit No None No 000 Self test fault No None No 307 Signal sil...
Страница 161: ...ble above Printer Yes or No Specifies if event information is printed Dialer Acct 1 2 Event information is sent to both dialer accounts Acct 1 Event information is sent to dialer account one Acct 2 Ev...
Страница 162: ...es 333 Loop 1 unconf alarm disable Yes None No 500 Loop 1 unconf alarm trouble Yes Acct 1 Yes 110 Loop 1 unconf trbl disable Yes None No 500 Loop 1 unconf trbl trouble No None No 331 Loop 1 map mismat...
Страница 163: ...ose Loop Events 6 Select the loop event 7 Choose Event Notification 8 Set the event notification See default settings in the table above Printer Yes or No Specifies if event information is printed Dia...
Страница 164: ...figured alarm 1 Press the Menu button 2 Choose Program 3 Choose Advanced Program 4 Enter the level two password 5 Choose Advanced Program 6 Choose Unconfigured Alarms 7 Choose Loop 1 Unconf Alarm or L...
Страница 165: ...10 10 10 10 Dialer Account 1 2 None Event information is not sent to the dialer NET Yes or No Specifies if event information is sent to the connected network CID Contact ID event code 000 to 999 16 W...
Страница 166: ...puts do not turn off even though the common trouble condition cleared because the NACs are not supervised To turn off the NAC outputs you must manually restore the NAC from the front panel s Control m...
Страница 167: ...if event information is printed Coder 4 digit coded output which is played in response to alarm conditions 00 00 00 00 to 99 99 99 99 Dialer Acct 1 2 Event information is sent to both dialer accounts...
Страница 168: ...base activates its relay when the detector meets the prealarm condition or goes into an alarm condition The base will not restore until both events have been restored Verify The base activates its re...
Страница 169: ...Enter to continue Incremental programming continues based on the settings you made above 8 If you selected to label devices and or zones use the procedures that follow to enter your labels 9 When incr...
Страница 170: ...e XX 3 Press Enter to save the label and go to the next zone number Note Pressing the Enter button saves the current label and then goes to the next zone number so that you can quickly go to each zone...
Страница 171: ...is a collection of NACs and or output devices strobe that responds to an input device smoke detector When you program the loop devices you will have to correlate assign the desired input device or zon...
Страница 172: ...n if the device goes into alarm If you do not set a prealarm threshold the base will never activate Base follow refers to how the detector base operates in an alarm condition initiated by the detector...
Страница 173: ...ices are restored to normal via a panel reset Circuit cannot be restored until devices are restored to normal and the panel is reset Duct alarm For duct smoke detectors All activations are immediately...
Страница 174: ...turn off when Signal Silence is pressed Relay module Relay nonsilence For the connection of relay devices that do not follow signal silence Relay with silence For the connection of relay devices that...
Страница 175: ...the screen e g 001 002 The first address listed is the device address you are programming When you pick the second address to program both addresses are still displayed but in reverse order e g 002 00...
Страница 176: ...vent Note If your system is configured as a zoned system you will see two events one for the zone and one for the device 2 Press Enter The device details screen is displayed 3 Press Enter The Enter Pa...
Страница 177: ...available reports Content History report 168 Walk Test report 170 Device Maintenance report 171 System Status report 172 Correlation Groups report 173 Zone report 174 System Configuration report 175 I...
Страница 178: ...ort Alarm Only alarm events are displayed in the report Date forward Allows you to enter a starting date for the report From that date forward all events are displayed in the report Notes You must hav...
Страница 179: ...3 Choose History 4 Choose Date Forward 5 Enter the starting date for the report month day year 6 Press Enter 7 Choose either LCD The report is displayed on the LCD display or Printer The report is pr...
Страница 180: ...reset is complete you can end the walk test and view a walk test report You must have a printer connected to your panel to print a report Requesting a report while another report is being printed or d...
Страница 181: ...the current report even if it has not finished and starts the new report that you requested Reports Test Control Program Reports Device Maintenance System Status Correlation Groups Device Maintenance...
Страница 182: ...tops the current report even if it has not finished and starts the new report that you requested Reports Test Control Program Reports System Status Correlation Groups Zone System Status All Alarm Supe...
Страница 183: ...if it has not finished and starts the new report that you requested Reports Test Control Program Reports Device Maintenance System Status Correlation Groups Correlation Groups Group 01 Group 02 Group...
Страница 184: ...starts the new report that you requested Reports Test Control Program Reports System Status Correlation Groups Zone Zones Zone 01 Zone 02 Zone 03 To view a zone report 1 Press the Menu button 2 Choos...
Страница 185: ...Panel configuration report Displays dialer network printer annunciator class annunciator and NAC configuration information Devices report Displays function type zone label follow day sensitivity night...
Страница 186: ...n Panel Configuration Loop Zone Config Devices Event Config or Dialer Config 5 Choose either LCD The report is displayed on the LCD display or Printer The report is printed on the connected printer If...
Страница 187: ...y stops the current report even if it has not finished and starts the new report that you requested Reports Test Control Program Reports Zone System Configuration Internal Status To view an internal s...
Страница 188: ...us Device Details Device Details Device Count Serial To view the device count on your system 1 Press the Menu button 2 Choose Reports 3 Choose Device Details 4 Choose Device Count 5 Choose either LCD...
Страница 189: ...Printer The report is printed on the connected printer If you do not have a printer this option is not available 6 If you selected LCD when finished viewing the report press Cancel twice to return to...
Страница 190: ...Check diagnostic see Loop comm check for more information Response Quality report This report allows you to enter a quality percentage value which then lists the devices that are communicating at tha...
Страница 191: ...option is not available 6 If you selected LCD when finished viewing the report press Cancel twice to return to the reports menu 7 Choose another report to view or to exit menu mode press the Menu but...
Страница 192: ...lay or Printer The report is printed on the connected printer If you do not have a printer this option is not available 7 If you selected LCD when finished viewing the report press Cancel twice to ret...
Страница 193: ...report while another report is being printed or displayed on the LCD display stops the current report even if it has not finished and starts the new report that you requested Reports Test Control Prog...
Страница 194: ...nting on the printer or displaying on the LCD display Reports Test Control Program Reports Device Details Diagnostics Cancel Reports To cancel a report 1 Press the Menu button 2 Choose Reports 3 Choos...
Страница 195: ...rmation Content Preventive maintenance schedule 186 Fast ground check 187 Recalibrate device 188 Flash device LED 189 Loop comm check 190 Control panel testing 191 Canadian tests for grounds opens and...
Страница 196: ...r to NFPA 72 section Inspection Testing and Maintenance Canadian Electrical Code Part I ULCS524 or ULCS536 for more information on required inspection and testing methods and frequency of fire alarm s...
Страница 197: ...y active By using Fast Ground Check you can decrease the system check time to every 4 seconds meaning that you will be able to troubleshoot your ground faults much quicker and determine if they have b...
Страница 198: ...ee if the detector has been cleaned properly If the device is not cleaned the device trouble will return meaning that more cleaning is required If the device is cleaned the corresponding device troubl...
Страница 199: ...hich causes the LED to flash on the two devices with the same address making it easy for you to find the two devices Test Control Program Diagnostics Enter Password 0000 Diagnostics Fast Ground Check...
Страница 200: ...Choose Loop Comm Check 5 On the Diagnostics screen you can monitor the progress of the check Once the check is complete select Continue To go to the report Diagnostics screen Go to the next step Back...
Страница 201: ...verified in the alarm supervisory and trouble modes To ensure that the panel can operate correctly when primary power is lost the batteries should be inspected and tested periodically Batteries shoul...
Страница 202: ...or monitor Note NAC responses activate as programmed Reports Test Control Program Test Walk Test Silent Walk Test Audible Test Fire Enter Password 0000 Test Fire Loop 01 Test Fire 001 Device 001 To c...
Страница 203: ...the dialer s accounts for proper operation Reports Test Control Program Test Walk Test Audible Test Fire Dialer Enter Password 0000 To conduct a dialer test 1 Press the control panel s Menu button 2 C...
Страница 204: ...d the LED annunciator and tests the LCD display so that you can verify proper operation LEDs stay on for 15 seconds Reports Test Control Program To conduct a lamp test 1 Press the Menu button 2 Choose...
Страница 205: ...ction for the zone in walk test If an unselected zone or device goes into alarm or trouble all programmed outputs operate as programmed Zones and devices behave as follows during walk test For alarm e...
Страница 206: ...xt device The panel terminates walk test if any of the following occur There are 30 minutes of inactivity for the zone or device being tested Walk test is stopped by the user Reports Test Control Prog...
Страница 207: ...prior to ending the walk test Once the reset is complete you can end the walk test and view a walk test report 1 Press the Menu button 2 Choose Test 3 Choose Walk Test Silent or Walk Test Audible 4 C...
Страница 208: ...installed is typically found on the Accessories menu Start All Programs Accessories Communications Setting up a HyperTerminal connection Before you can gather information from the control panel you m...
Страница 209: ...file extension is added automatically If you want to save the file somewhere other than the default location click the Browse button navigate to the desired location then name the file 3 Click Start...
Страница 210: ...cribes how the device and control panel operate When the device in alarm is removed the control panel remains in alarm and a trouble event is displayed When the new device is installed it does not go...
Страница 211: ...EST iO64 and iO500 Technical Reference Manual 201 Appendix A Panel specifications Summary This appendix lists all of the specifications for the control panel Content Control panel specifications 202...
Страница 212: ...5 Class B Class A optional Data line length 4 000 ft 1 219 m 8 drops max RS 485 Class A or B Data line length 4 000 ft 1 219 m Operating voltage 24 VDC Auxiliary power output circuit Aux power 1 500 m...
Страница 213: ...1 mA Max 100 mA FCC registration number GESAL01BSADACT Industry Canada Registration number 3944A SADACT Ringer equivalence number 0 1B Ground fault impedance 0 to 5 k Alarm contact Form C N O 24 VDC a...
Страница 214: ......
Страница 215: ...worksheet 206 Notification appliance circuit calculations worksheet 209 Introduction 209 What you ll need 209 Worksheet method 211 Equation method 212 Notification appliance voltage drop calculation w...
Страница 216: ...tion appliances from their respective installation sheets Battery calculation worksheet Standby current mA Alarm current mA Control panel use Worksheet A and place totals here Auxiliary smoke power us...
Страница 217: ...A Base panel 1 See note 1 below See note 2 below Primary loop circuit fully loaded loop 55 125 XAL250 loop expander card fully loaded loop 60 125 SA CLA Class A card 3 60 SA 232 RS 232 card 13 13 SA D...
Страница 218: ...current mA Qty x Alarm current mA RPM 20 270 SIGA UM or MAB 1 2 17 RLCD F 98 113 RLCD C F 99 115 RLED C F 28 62 LED24 6 34 Totals mA transfer totals to Battery Calculation Worksheet Note 1 Enter 1 reg...
Страница 219: ...pliances To do this we assume these two worst case conditions The voltage at the NAC terminals is the minimum provided by the power supply The notification appliances are clustered at the end of the N...
Страница 220: ...erminals at minimum voltage The current draw of notification appliances can vary substantially with the type of power supplied full wave rectified VFWR or direct current VDC It is important to know th...
Страница 221: ...nel 0 24 0 24 0 24 0 24 Load voltage drop V Source voltage 20 4 20 4 20 4 20 4 V Load voltage drop V Minimum voltage V Regulated appliance voltage 16 0 16 0 16 0 16 0 V Voltage drop 2 V Total operatin...
Страница 222: ...V range If all appliances draw the same maximum current the total current is the maximum current multiplied by the number of appliances If different appliance types have different maximum currents th...
Страница 223: ...24 V A 3 Calculate the allowable voltage drop Vd between the power supply and the appliances Vd Vm Va Where Vm minimum voltage from above Va appliance minimum voltage For regulated notification appli...
Страница 224: ...t 4 0 V 2 0 A 2 0 Lc Rmax Rw 2 2 0 0 002 ft 2 1 000 0 ft 2 500 0 ft So the maximum wire run for this NAC would be 500 ft rounding down for safety NAC maximum wire run quick reference tables 64 point p...
Страница 225: ...8 V 19 8 V NAC 2 voltage drop calculations Circuit length Total circuit current 2 Wire resistance per 1000 ft 1 Voltage drop feet x amps x 1000 Panel voltage Voltage drop End of line voltage 3 Voltag...
Страница 226: ...cal values see Table 1 in the Notification appliance circuit calculations worksheet 2 Use the Maximum operating current at worst case VFWR from the installation or catalog sheet of each device 3 For U...
Страница 227: ...Twisted pair nonshielded 25 pF 36 pF 38 pF 20 000 ft 6096 m 13 888 ft 4233 m 13 157 ft 4010 m Twisted pair shielded 58 pF 82 pF 84 pF 8 621 ft 2628 m 6 098 ft 1859 m 5 952 ft 1814 m Nontwisted pair n...
Страница 228: ...Appendix B Worksheets 218 EST iO64 and iO500 Technical Reference Manual Device circuit path diagram FACP J J 10 ft 3 m 200 ft 61 m 30 ft 9 m J 100 ft 30 m 1000 ft 305 m 200 ft 61 m 100 ft 30 m...
Страница 229: ...505 13069 3984 1 to 25 26 to 50 5172 1577 8217 2505 13069 3984 26 to 50 26 to 50 5172 1577 8217 2505 13069 3984 51 to 75 26 to 50 5172 1577 8217 2505 13069 3984 76 to 100 26 to 50 5172 1577 8217 2505...
Страница 230: ...882 4599 1402 7315 2230 0 26 to 50 3550 1082 5640 1719 8971 2734 1 to 25 26 to 50 3145 958 4996 1523 7945 2422 26 to 50 26 to 50 2742 836 4356 1328 6928 2112 51 to 75 26 to 50 2348 716 3730 1137 5932...
Страница 231: ...to 75 1 to 25 1053 321 1672 510 2660 811 76 to 100 1 to 25 327 100 519 158 825 252 101 to 125 1 to 25 0 0 0 0 0 0 0 26 to 50 1910 582 3035 925 4827 1471 1 to 25 26 to 50 1465 446 2327 709 3700 1128 26...
Страница 232: ...0 0 0 0 1 to 25 1490 454 2367 721 3764 1147 1 to 25 1 to 25 745 227 1184 361 1883 574 26 to 50 1 to 25 0 0 0 0 0 0 51 to 75 1 to 25 0 0 0 0 0 0 76 to 100 1 to 25 0 0 0 0 0 0 101 to 125 1 to 25 0 0 0 0...
Страница 233: ...tion group 05 Correlation group 06 Correlation group 07 Correlation group 08 Correlation group 09 Correlation group 10 Correlation group 11 Correlation group 12 Correlation group 13 Correlation group...
Страница 234: ...st Day pre alarm percent Off 50 55 60 65 70 75 80 90 Night prealarm percent Off 50 55 60 65 70 75 80 90 Base type Standard Relay Isolator Sounder Base follow Alarm Alarm verify Alarm prealarm Verify P...
Страница 235: ...re alarm Print Yes No NET Yes No Dialer Acct 1 Acct 1 2 Acct 2 None Code 4 digit coded output CID Alarm verify Print Yes No NET Yes No Dialer Acct 1 Acct 1 2 Acct 2 None Code 4 digit coded output CID...
Страница 236: ...ence Manual Loop worksheet The loop worksheet is used to document your loop settings Note For default settings refer to Factory default settings Loop class Loop 1 class Class B Class A Loop 2 class Cl...
Страница 237: ...le silence Continuous nonsilenceable Temporal silenceable Genesis nonsilenceable Coder continuous Coder temporal Coder 120 SPM Coder basic Label up to 40 characters Correlation groups Event notificati...
Страница 238: ...retry time 01 45 seconds Account 1 retry count 01 10 attempts Event notification Device reporting Zone reporting Event reporting Account 2 ID 4 digit account ID code Account 2 primary receiver number...
Страница 239: ...4 digit account ID code IP address TCP IP port Send restorals Yes No Event notification Device reporting Zone only reporting Event only reporting Hello time seconds 10 255 seconds Timeout seconds 31 2...
Страница 240: ...ult settings Language English French Marketplace U S Canada AC fail delay Off 01 15 hours Zone resound Off On Reset inhibit Off 1 minute Auto signal silence Off 05 30 minutes Day start Start time End...
Страница 241: ...ng Monitor Label up to 40 characters Correlation groups Device allocation First address no less than the last address of the previous zone 1 Last address first address the number of devices 1 Event no...
Страница 242: ...int Yes No NET Yes No Dialer Acct 1 Acct 1 2 Acct 2 None Code 4 digit coded output CID Maintenance alert Print Yes No NET Yes No Dialer Acct 1 Acct 1 2 Acct 2 None Code 4 digit coded output CID Test P...
Страница 243: ...38 Programmable keys menu 239 Advanced program main menu 240 Advanced Loop configuration menu 241 Advanced Device configuration menu 242 Advanced Panel configuration menu 243 Advanced Panel configurat...
Страница 244: ...Front panel menu flowcharts 234 EST iO64 and iO500 Technical Reference Manual Main menu Menu Key Pressed Test Control Program 00 00 00 01 01 2007 Reports Test Control Program Main Menu Diagnostics Dia...
Страница 245: ...ervisory Trouble Disable Other Device Status All Panel Operation Panel Configuration Loop Zone Config System Configuration Device Count Serial Device Details Serial Loop 1 Loop 2 All Zone Devices Even...
Страница 246: ...st menu Test Menu Item Title Start End All Devices Zone Walk Test Silent All Devices Zone Walk Test Audible Account 1 Account 2 Dialer Test Fire 001 Device 001 Zone Number 01 Zone 01 Loop 01 Test Fire...
Страница 247: ...tivate Restore Drill Enable Disable Activate Restore Control Device Enable 001 Device 001 Zone Enable 01 Zone 01 Device Activate 001 Device 001 Loop 01 Device Loop 01 Device Continue Cancel Warning De...
Страница 248: ...nly Panel and CMS Restore Defaults Date and Time Clear History Password Restore Defaults Auto Program Advanced Program Incremental Program Program Daylight Savings Month Start 03 Month End 11 Week Sta...
Страница 249: ...ble keys menu Prog Keys Programmable Keys Key 2 Key 1 Panel NAC 1 NAC 1 Back Enter Enter To Add Key X Edit List New List Save Enter To Add Device 001 Loop 1 Device 001 Back Enter Loop 01 Device Device...
Страница 250: ...nual Advanced program main menu Advanced Prog Adv Panel Conf Adv Panel Op Adv Panel Events Adv Loop Events Adv Unconf Alarm Loop Configuration Panel Configuration Panel Operation Panel Events Advanced...
Страница 251: ...n Groups Number 01 Loop Class Zone Correlation Groups Device Loop Configuration Mapping Loop 2 Enable Yes Save Loop Class Loop 1 ClassA Loop 2 ClassA Save Loop Class Loop ClassA Save Mapping Loop 1 Ye...
Страница 252: ...001 Device 001 Group 01 Yes Correlation Groups Group 02 Yes Group 03 Yes Group 32 Yes Save Printer Yes Dialer Account1 2 CODER 10 10 10 10 Notification CID 110 NET Yes Save Active Trouble Disable Test...
Страница 253: ...01 100 Label aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaa Save Back Group 01 Yes Correlation Groups Group 02 Yes Group 03 Yes Group 32 Yes Save Annunciator 01 Annunciator Annunciator 02 Annunciator 03 An...
Страница 254: ...etwork Hello Time 055 Timeout Secs 000 Receiver 000 Line 000 Save Enabled Yes 7394310 Save Back Type Single Line Line 1 Line 2 Tone Wait Sec 20 Account 1 Account 2 Call Discn Sec 40 Dialer Test Freq D...
Страница 255: ...nel operation menu Adv Panel Op Marketplace US Reset Inhibit 1Min Auto Sig Sil 30 AC Fail Delay 15 Zone Resound On Panel Operation Date MM DD YYYY LCD Banner Evnt Notif ZoneDev Language English Day St...
Страница 256: ...Fail Dialer Normal Test Dialer Abnorm Test Dialer Config Program Mode Reset Reset Sil Inhibit Panel Silence Signal Silence Drill Walk Test Test Fire Clear History Time Date Common Disable System Star...
Страница 257: ...Adv Loop Events Loop 1 Initializing Loop 1 Fault Loop 1 Map Fault Loop Events Loop 1 Card Fault Loop 1 Unconf Alarm Loop 1 Unconf Trbl Loop 2 Initializing Loop 1 Map Mismatch Loop 1 Over Limits Loop...
Страница 258: ...menu Adv Unconf Alarm Active Event Notification Loop 2 Unconf Alarm Unconfigured Alarms Loop 1 Unconf Alarm Group 01 Yes Correlation Groups Group 02 Yes Group 03 Yes Group 32 Yes Save Correlation Grou...
Страница 259: ...nual 249 Advanced Common trouble menu Group 01 Yes Correlation Groups Group 02 Yes Group 03 Yes Group 32 Yes Save Adv Comm Trbl Correlation Groups Event Notification Common Trouble Printer Yes Dialer...
Страница 260: ...OST Continue Cancel Label Devices No Label Zones No Follow Alarm Auto Program Auto Zoning Yes Evnt Notif Zone Dialer Single Enable NET No Account ID 6769 Format CID Primary Recver Secondary Recver Acc...
Страница 261: ...programming menu Increment Prog Loop 2 NNN ZZZ Devices Old New Loop 1 XXX YYY Continue Devices Old New XXX YYY Continue Label Devices No Label Zones No Follow Alarm Incremental Program Loop Loop 1 Au...
Страница 262: ...nu Diags Fast Ground Check Recalibrate Device Diagnostics Flash Device LED Loop Comm Check Fast Ground Check Start End Recalibrate Device Device 001 Device 001 Flash Device LED Device 001 Device 001 D...
Страница 263: ...tions Summary This appendix has sounder base applications that can be used with the SB4U and Signature sounder bases Content Sounder base applications 254 Local alarm signaling application 254 Zone al...
Страница 264: ...alarm signal only when its detector is activated initiates an alarm event All other audible detector bases on the same riser remain silent until their detectors are activated The audible detector base...
Страница 265: ...A DATA 24 VDC 24 VDC SLC PAM 1 47 k EOLR AUX RISER ALTERNATE RISER SUPERVISION CIRCUIT Double screw terminal block supplied by installer BLU ORG Programming 1 Set the panel s Event Notification option...
Страница 266: ...zone are activated using a CRR module when any one of their detectors is activated initiate an alarm event Signal synchronization is not required because alarm signals are limited to the same notific...
Страница 267: ...rs into zones and correlate outputs for each zone The following instructions are for Zone 1 but apply for all zones as well 1 Set the panel s Event Notification option for Zone 2 Configure the smoke d...
Страница 268: ...detectors in Zone 1 Message Line 1 Zone 1 Message Line 2 As required Type Alarm Coder 0 0 0 0 6 Configure Correlation 01 as follows Inputs Zone 1 Outputs The CRR module labeled ZONE_1 SOUNDERS System...
Страница 269: ...6 5 G1M RM 7 8 1 2 3 4 6 5 CRR SLC DATA DATA DATA DATA 24 VDC 24 VDC AUX RISER NORMALACTIVE SLC NORMALACTIVE N C N C JP1 24 VDC Monitor Programming 1 Set the panel s Event Notification option for Devi...
Страница 270: ...set Follow Verification for No and set Follow Pre Alarm for Yes 3 Configure the CRR module as follows Device Type Relay Silence Message Line 1 SOUNDER_RLY_1 Message Line 2 As required 4 Configure the...
Страница 271: ...al Reference Manual 261 Appendix E Device types to personality codes correlation Summary This appendix shows the relationship between device types and personality codes Content Device types to persona...
Страница 272: ...Smoke Verified 1 Alarm NO latching Class B PS Smoke 1 Alarm NO latching Class B PS Smoke Verified 1 Alarm NO latching Class B PS Supervisory Latching 1 Alarm NO latching Class B PS Supervisory Nonlatc...
Страница 273: ...1 Alarm NO latching Class B 270B Pull Station 1 Alarm NO latching Class B 270F Pull Station 1 Alarm NO latching Class B 278 Pull Station 1 Alarm NO latching Class B CT2 Smoke 1 Alarm NO latching Class...
Страница 274: ...utput Class B MCC1 Continuous Silenceable 5 Signal supervised output Class B CC1S Supervised Output 5 Signal supervised output Class B CC1S Continuous Non Silenceable 5 Signal supervised output Class...
Страница 275: ...B UM Remote Drill 3 Active NO nonlatching Class B UM Remote Signal Silence 3 Active NO nonlatching Class B UM Remote AC Fail 3 Active NO nonlatching Class B UM Alarm 1 Alarm NO latching Class B UM 2...
Страница 276: ...ctive NO nonlatching Class B MAB Alarm 1 Alarm NO latching Class B MAB 2 Wire Alarm 13 Alarm two wire smoke unverified Class B MAB 2 Wire Alarm Verify 14 Alarm two wire smoke verified Class B MAB 2 Wi...
Страница 277: ...des correlation EST iO64 and iO500 Technical Reference Manual 267 Model name Device type Personality code MAB Continuous Silenceable 16 Signal supervised output Class B RM1 Monitor 23 Riser monitor 24...
Страница 278: ......
Страница 279: ...larm system vii auxiliary smoke power output wiring 68 auxiliary smoke power specifications 68 B backlight 5 banner screen 5 147 base follow 87 107 118 158 161 base type 161 batteries 13 60 204 batter...
Страница 280: ...et 226 device testing 50 193 196 device type 87 118 161 device types 264 diagnostics fast ground check 187 flash device LED 189 loop comm check 190 recalibrate device 188 diagnostics menu 254 diagnost...
Страница 281: ...l 2 password 84 line number 87 141 lock remote read 87 145 loop 2 enable 87 123 loop card fault 17 loop card LEDs 63 loop circuit 63 115 123 124 152 204 loop class 87 124 loop comm check 190 loop conf...
Страница 282: ...schedule 186 primary receiver number 107 139 printed events 15 printer 15 143 printer card 13 printer trouble 17 printer type 87 printer wiring 71 program menu 240 program mode 17 programmable keys 97...
Страница 283: ...ions 145 TCP IP port 87 141 telephone supervision 83 telnet 145 temporal 132 test 15 test fire 17 193 test frequency 87 test LED 9 test menu 238 test signal frequency 83 test time 87 testing 191 testi...
Страница 284: ...elation groups 116 129 zone disable 36 zone enable 38 zone event 5 zone label 107 129 158 zone programming 129 161 zone report 174 zone reporting 139 141 147 zone resound 87 147 zone settings workshee...