Chapter 7 Global Meter Setup
EXAMPLE 1:
Relay 1 will be “SET” once the reading exceeds 5.00 amps. Relay 1 will be “RESET” once the reading
falls below 5.00 amps.
5 . 0 0 A
0 A
R E S E T
L 1
S E T
N O P O W E R T O T H E U N I T
R E S E T
1. Enter in GROUP 0, FUNCTION 4, Segment C and D: UP, DOWN
2. Enter in GROUP 4, FUNCTION 2, LIMIT 1, Segments B, C, and D: UP, UP, DOWN
EXAMPLE 2: NORMALLY RESET - NON-EVENT CONDITION WILL RESET RELAY
Relay 1 will be “SET” if the instantaneous reading for amps is below 4.00 amps or above 5.00 amps.
Under all other conditions the relay will be “RESET”.
NOTE:
U
NDER THIS SETUP THE RELAY WILL
NOT
ACT AS A PROTECTIVE SWITCH
.
4 . 0 0 A
5 . 0 0 A
0 . 0 0 A
S E T
S E T
L M 2
L M 1
R E S E T
N O P O W E R T O T H E U N I T
R E S E T
P
ROGRAMMING
S
TEPS
:
1. Enter in GROUP 0, FUNCTION 4, Segments C and D: UP, UP
2. Enter in GROUP 4, FUNCTION 2, LIMIT 1, Segments: B, C, and D: UP, UP, DOWN. Value: 5.00
3. Enter in GROUP 4, FUNCTION 2, LIMIT 2, Segments: DOWN, UP, DOWN. Value: 4.00
27
GE Industrial Systems