Chapter 7 Global Meter Setup
7.5 G
ROUP
0, F
UNCTION
3 - P
ROGRAMMING
P
ROCEDURE
Ö
To change the
SYSTEM CONFIGURATION SWITCH
settings, follow these steps:
NOTE:
PRESS
MAX/MIN/LIMITS
, AT ANY TIME, BEFORE STORING THE LAST DIGIT OR SWITCH.
MAX
AC VOLTS
A B C N
AC AMPS
MAX/MIN
LIMITS
VOLTS
PRINT
PROG
PHASE
NEXT
0.
AMPS
B C A
I I I
A B C
N N N
I I I
A B C
LM2
LM1
MIN
MAX
AC VOLTS
A B C N
AC AMPS
MAX/MIN
LIMITS
VOLTS
PRINT
PROG
PHASE
NEXT
03.0
AMPS
B C A
I I I
A B C
N N N
I I I
A B C
LM2
LM1
MIN
_
_
_
Step 1
:
a.
Enter Group Level of Programming Mode,
(see Chapter 6).
b.
Press
MAX/MIN/ LIMITS
until
0.
appears in
upper display.
c.
Press
VOLTS
to activate the Group.
Ö
03.0
appears in upper display.
Ö
Lower display indicates current PACK 0 Switch
Settings.
MAX
AC VOLTS
A B C N
AC AMPS
MAX/MIN
LIMITS
VOLTS
PRINT
PROG
PHASE
NEXT
03 I
AMPS
B C A
I I I
A B C
N N N
I I I
A B C
LM2
LM1
MIN
_ _
_
MAX
AC VOLTS
A B C N
AC AMPS
MAX/MIN
LIMITS
VOLTS
PRINT
PROG
PHASE
NEXT
03. I
AMPS
B C A
I I I
A B C
N N N
I I I
A B C
LM2
LM1
MIN
_
_
_
Step 2
:
a.
Press
PRINT/PROG
until desired PACK appears.
b.
Press
VOLTS
to begin Data Entry Sequence.
Ö
Three dashes appear in lower display.
Step 3:
a.
Press
PRINT/PROG
to toggle the segments UP or
DOWN for desired setting.
b.
Press
VOLTS
to store
See Chapter 12 to Exit.
7.6 G
ROUP
0, F
UNCTIONS
4-5 - T
IME
D
ELAY FOR
R
ELAYS
1 & 2 (O
PTION
NL)
The EPM3000P can be equipped with a relay option. Two relays are included in this option. The relays can be used in
computer controlled or dedicated alarm options.
COMPUTER
CONTROLLED
The relays can be locked or unlocked through a computer
(must have communication
option).
DEDICATED ALARM
The relays can be locked or unlocked using the meter's keypad or its measured inputs.
The computer cannot change the state of the relay.
Under GROUP 0, FUNCTIONS
4-5
, time delay for the Relays 1 or 2 can be set between 0 - 255 seconds. This allows
conditions to exist for a specified time period before the relay or alarm activates. If a time greater than 255 seconds is
entered, the meter defaults to the maximum value of 255 seconds.
26
GE Industrial Systems