22
EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH41549 R05
2.
To locate the breaker for its proper compartment, refer to the breaker location list on the front view
drawing. Find the proper breaker by the identification card on the breaker carton, or the mark number
on the breaker nameplate. All identical legacy breakers have the same mark number.
Clean and Grease Breaker
1.
Before installing or operating a breaker, refer to the breaker instruction manual for pre-operation
inspection and test.
2.
Check thoroughly for any damaged or loose parts and for any dirt or foreign matter which may be in
the breaker.
3.
Clean those areas if necessary with a clean, lint-free rag and isopropyl alcohol or acetone.
4.
Be sure to apply a thin film of electrical grease DH0HD38 (Mobilgrease 28) to the primary disconnect
fingers (
Figure 10/10A
). GE Part #193A1751P1 is a 1 oz. tube of Mobilgrease 28.
Figure 10. AKD-8—Primary Contacts or “Fingers” (Apply
Grease)
Figure 10A. AKD-8—(3200-5000A) Primary Contacts or
“Fingers” (Apply Grease)