EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual          DEH41549 R05

 

Install Door Interlock System 

 

 

It must be ensured that the supply power 
to the compartment is turned off/ 
compartment is de-energized for all the 
incoming and outgoing circuits of the LVS 
prior to any work being conducted on it. 

 

During the installation and related work 
on the equipment, it must be ensured 
that the operator is using the prescribed 
PPE for the specified tasks.

 

 

 

Ensure only qualified personnel install, operate, service, and maintain all electrical 
equipment. 

 

 

Details regarding installation of the door interlock system are shown below in 

Figure 44

, 45 and

 46

 

Figure 44. AKD-8—Door Interlocking Components (Model 1) 

 

 

 

Racking stroke of legacy = 4.25”. Racking stroke of Retrofills = 2.75”. 

 

Racking stroke of the Retrofills is equal to that of AKR30S. 

 

Same mounting bracket used for all AKR breakers in AKD8, depending on SKU the mounting holes are 
decided on. 

 

Provisions for fixing the door interlock are already present on the mounting bracket.  

 

Door interlock system of AKR30S can be used for Retrofills. 

 

Remove existing activator and replace with new activator shown.  

 

For AKR30S, existing door interlock suffices. No changes needed.  

Содержание EntelliGuard AKR30S-800A

Страница 1: ...also be part of a single ended or double ended load center unit substation This manual applies to EntelliGuard R breakers to be used in AKD 8 Switchgear substructures found in OEM Equipment and GE Sw...

Страница 2: ...pecs 7 Weight lbs 7 Views 8 History and Types 9 AKD 9 AKD 5 AK 25 AK 50 AKT 50 AK 75 AK 100 9 AKD 6 AKR 30 30H AKR 50 50H T50H AKR 75 75H AKR 100 9 AKD 8 AKR 30 30H 30L AKR 50 50H T50H AKR 75 75H AKR...

Страница 3: ...s 31 Wire Secondary Disconnect Assembly AKR30 30H 50 50H 30L 30S T 50H 36 AKD 8 Programmer Disconnects 38 Procedures 38 Wiring and Completion 41 AKD 8 Primary Disconnects Contacts or Fingers 41 Remove...

Страница 4: ...3 EntelliGuard R Circuit Breaker Retrofill AKD 8 Installation Manual DEH41549 R05 AKD 8 Neutral CT Adapter 400A 5000A 57 Procedures 58 AKD 8 Multi Source Ground Fault 59...

Страница 5: ...voided results in death or serious injury A variety of electrical hazards warnings are displayed here and are applied to installation manuals These are standard or generic alerts and labels that must...

Страница 6: ...There are also warnings pertaining to product safety that need to be custom written for particular or specific circumstances Table 4 Table 3 Generic Warning Alerts and Labels Used for Documentation a...

Страница 7: ...ot present in all hardware and software systems GE Energy assumes no obligation of notice to holders of this document with respect to changes subsequently made GE Energy makes no representation or war...

Страница 8: ...8 hrs depending on the complexity of the original breaker Once the retrofill breaker is fully prepared it should take about 20 minutes to swap out the old breaker and rack in the new EntelliGuard R re...

Страница 9: ...t breaker in a steel frame installing primary and secondary disconnects and driving drawout racking cams thru what looks like the EntelliGuard G Cassette s front dashboard Figure 1 AKD 8 AKR30H 50H Br...

Страница 10: ...ers ring silver plating on copper and aluminum bus un plated welded connections The switchgear is painted sand gray beige with some instrument doors painted blue AKR 30 50 in 22 wide sections were int...

Страница 11: ...e a drawout letter code D OEM versions are drawout letter code B and GE Switchboard versions are drawout letter code F B F breakers only differed by appearance items All Primary disconnect stabs are v...

Страница 12: ...rs Feature Model 1 Retrofill Breaker 800 1600A Model 2 Retrofill Breaker 800 1600A 2000A except AKR 30S Secondary Disc Bullet mounting Secondary disconnect bullets mounted on spring loaded bracket ass...

Страница 13: ...AKR125 Feature Retrofill Breaker 3200 5000A Secondary Disc Bullet mounting Secondary disconnect bullets mounted directly on metal bracket as on the legacy AKR breakers Kirk lock Actuator Compartment R...

Страница 14: ...AKD 8 Mechanical Drawings The following engineering or assembly drawings describe the layout and dimensions of the AKD 8 Retrofill breaker Figure 2 Figure 3 Figure 4 Figure 5 Figure 2 AKD 8 AKR30 30H...

Страница 15: ...Breaker Retrofill AKD 8 Installation Manual DEH41549 R05 Figure 4 AKD 8 AKR50 50H 30L Retrofill Breaker Dimensioning Model 1 R3 type Figure 5 AKD 8 AKR50 50H 30L AKRT 50H Retrofill Breaker Dimensionin...

Страница 16: ...5 EntelliGuard R Circuit Breaker Retrofill AKD 8 Installation Manual DEH41549 R05 Figure 5A AKD 8 AKR75 75H AKR 100 Retrofill Breaker Dimensioning Figure 5B AKD 8 AKR 125 Retrofill Breaker Dimensionin...

Страница 17: ...ent a Typical AKR 30 50 T50 AKD 8 compartment Figure 6 AKD 8 new Empty Compartment View 1 Figure 7 AKD 8 new Empty Compartment View 2 Racks Rails Extended Figure 8 is a photo of the interior of the AK...

Страница 18: ...ts of an AKD 8 compartment Figure 9 AKD 8 Circuit Breaker Compartment 22 Inch for AKR 30 50 T50 Breakers Interior View The figures Figure 6A 7A 8A 9A below present a Typical 30 AKR 75 100 AKD 8 compar...

Страница 19: ...AKD 8 The photos point out the shutter assembly and Draw out tray assembly in the AKD 8 Figure 8A AKD 8 Compartment Assemblies Interior Components Figure 9A points out the major components of an AKD...

Страница 20: ...uring the assembly may give way Ensure lifting equipment has capability for device being lifted Wear hard hat gloves and safety shoes Failure to comply with these instructions could result in serious...

Страница 21: ...eft side viewed from front of the front fascia Remove Circuit Breaker from Container Inspect 1 Inspect the shipping container for obvious signs of rough handling and or external damage incurred during...

Страница 22: ...rom entering the breaker If dampness or condensation is encountered in the storage location heaters can be used to prevent moisture damage Use Lifting Truck 1 Use a lifting truck to lift and mount the...

Страница 23: ...ng or operating a breaker refer to the breaker instruction manual for pre operation inspection and test 2 Check thoroughly for any damaged or loose parts and for any dirt or foreign matter which may b...

Страница 24: ...all wiring connections are properly made Wrong connections will cause the breaker to malfunction Modify AKD 8 AKR30S Switchgear Compartment Only It must be ensured that the supply power to the compart...

Страница 25: ...isconnects Removing the glastic sheet does not require any tools but you need to exercise the caution while removing the glastic sheet to avoid contact with compartment mounted secondary disconnects A...

Страница 26: ...y must be done by a trained service technician only 4 Apply corrosion resistance treatment to the exposed metal after removing the pin 5 Reassemble the bracket assembly and scrap or discard the pin To...

Страница 27: ...breaker OR Use GE part number 0247B8961G002 lifting bar and suitable hoist to lift from above as shown in Figure 14 Figure 13 AKD 8 Location of Eyebolts Figure 14 AKD 8 Using GE Lifting bar and hoist...

Страница 28: ...right with the shutter open insert the racking tool in the handle insertion hole so that it engages with the racking mechanism and remove the screwdriver Figure 16 14 With the racking tool inserted cr...

Страница 29: ...reaker is in its maximum travel position At this point the primary disconnect fingers have completely engaged with the primary bus stabs 20 Remove and store the racking handle in it storage location A...

Страница 30: ...shown in Figure 18A This lifting bar has been tested to 200 of its 700 lb rating B Alternate method use a lifting chain and hooks rated at least 1400 lbs to lift the breaker from above as shown in Fig...

Страница 31: ...r Figure 16 and turn it clockwise to the right so that the racking handle shutter opens 15 While turning the screwdriver to the right with the shutter open insert the racking tool in the handle insert...

Страница 32: ...the secondary disconnect assembly bullets shown in Figure 20 below Wiring the secondary disconnect assembly bullets shown in Figure 20 below The EntelliGuard R Retrofill Breaker has these two options...

Страница 33: ...secondary disconnect block from the box The kit comes in just one box Each kit of secondary disconnect has 4 nuts plain washers and spring washers These can be arranged on a work station for preparing...

Страница 34: ...ily Figure 23 and Figure 24 For Model 2 AKD8 Retrofill Breakers Figure 22 AKD 8 Seven Bullets to a Block Three Blocks Exploded View Model 2 1 If the EntelliGuard R Retrofill breaker order included 3 7...

Страница 35: ...urn to their initial positions when they are released from being pressed down 3 Check for electrical continuity between the bullets on one end and the wire terminations on the other Blocks containing...

Страница 36: ...KD 8 Installation Manual DEH41549 R05 WIRING Do not pinch damage the wires while installing the secondary disconnect blocks Figure 23 AKD 8 Seven Bullets to a Block Three Blocks to a Retrofill Photo V...

Страница 37: ...uted The wires should not be routed from the outside of the metal structure as it might interfere with the motion of the kit when racking into the compartment Ensure that the wires are securely fixed...

Страница 38: ...or Shunt trip 125Vdc only Use 2 NO contacts in series with coil For S T 1 use 2nd NO contact at terminals B25 B26 Jumper A21 to B25 and B26 to A5 For S T 2 use 2nd NO contact at terminals B17 B18 Jump...

Страница 39: ...ssembly consists of the plug assembly mounted on a spring loaded assembly that receives the breaker WIRING Note Look for the wiring connection scheme on the existing or old terminal block and use the...

Страница 40: ...ASSY AKR75 100 125 AKR75 100 125 19 pin configuration If the legacy LVS doesn t have a 12 pin programmer disconnect configuration and the customer chooses to install a programmer disconnect then the...

Страница 41: ...inal block supplied 2 Check that the secondary disconnect plug assembly is not damaged and the wiring is intact 3 Check that the programmer disconnect block is moving freely within the assembly and re...

Страница 42: ...s The Finger Clusters Accessory Manual DEH 41533 covers the primary disconnects or fingers The primary disconnects are flexible connections between the breaker line and load terminals and between the...

Страница 43: ...ssembly together 3 Carefully slide out the bolt while removing the flat washer spring bushing upper retainer bow tie spacers lower retainer and fingers from the bottom of the assembly 4 Do the same fo...

Страница 44: ...ut to lock in the adjustment 17 Clean finger assemblies if necessary with a clean lint free rag and isopropyl alcohol or acetone 18 Be sure to apply a thin film of Mobilgrease 28 D50HD38 to the contac...

Страница 45: ...44 EntelliGuard R Circuit Breaker Retrofill AKD 8 Installation Manual DEH41549 R05 Mechanical Views Figure 34 provides further details Figure 34 Fingers or Clusters Mechanical View and Notes...

Страница 46: ...ting this dimension Figure 36A 36B shows the cluster components Figure 35A Adjustment 3200A only Double springs Figure 36A Components 3200A Figure 35B Adjustment 4000A 5000A Figure 36B Components 4000...

Страница 47: ...acer in each finger and hold them in position with a pressure plate retainer 12 Place a spring bushing and flat washer over the bolt then secure with the Adjusting nut 13 Repeat Steps 7 through 13 for...

Страница 48: ...47 EntelliGuard R Circuit Breaker Retrofill AKD 8 Installation Manual DEH41549 R05 Figure 37 Steps in Exploded Views AKR 75 75H Figure 38 Steps in Exploded Views AKR 100 125...

Страница 49: ...tor comes pre installed on all versions of Retrofill EntelliGuard ACB Hence no installation is required Retrofills provide the same electrical indication scheme as the legacy breakers Figure 40 and Fi...

Страница 50: ...49 EntelliGuard R Circuit Breaker Retrofill AKD 8 Installation Manual DEH41549 R05 Figure 40 Breaker Surfaces Activate Position Switch...

Страница 51: ...telliGuard R Circuit Breaker Retrofill AKD 8 Installation Manual DEH41549 R05 Figure 41 Breaker Surfaces Activate Position Switch Model 2 Figure 41A Breaker Surfaces Activate Position Switch AKR75 100...

Страница 52: ...R breaker comes pre installed with shutter Figure 42 Figure 43 and figure 43A actuators which operate the opening of the shutters Hence no installation is required Retrofills provide the same mechanic...

Страница 53: ...te service and maintain all electrical equipment Details regarding installation of the door interlock system are shown below in Figure 44 45 and 46 Figure 44 AKD 8 Door Interlocking Components Model 1...

Страница 54: ...ill door interlocking assembly Please remove the existing Door Interlock Actuators from the compartment for AKR 30 30H 50 50H AKRT 50 50H The Retrofill breaker has a Door Interlock Actuator Bracket mo...

Страница 55: ...Figure 46 AKD 8 AKR75 100 125 Door Interlocking Components Figure below shows the components that make up the AKD 8 Retrofill door interlocking assembly Figure below shows the Door Interlock Actuator...

Страница 56: ...osition Modify AKD 8 Switchgear Compartment Cut Power to AKD 8 Switchgear It must be ensured that the supply power to the compartment is turned off compartment is de energized for all the incoming and...

Страница 57: ...D 6 AKD 8 AKD 10 DEH 41563 Install AKD 8 Neutral Rogowski Current Transformer CT Turn off all power to switchgear Tagout and lockout main source up stream or main breaker Failure to comply with these...

Страница 58: ...us Rogowski ASM 10108266 AKD8 600A 10108266G2 Figure 40 Neutral Bus Rogowski ASM 10108266 AKD8 800A 10108266G3 Figure 40 Neutral Bus Rogowski ASM 10108266 AKD8 1000A 10108266G4 Figure 40 Neutral Bus R...

Страница 59: ...nergized and the breaker in the compartment being retrofit is switched off and removed from the LVS 2 Open the door on the rear of the compartment to access the Cable Bus compartment of the LVS 3 Note...

Страница 60: ...ed in the following ground fault applications Single Source Feeder breakers 3 wire or 4 wire Main Circuit breakers 3 wire or 4 wire For 4 wire multi source Ground Fault systems the Retrofill should be...

Страница 61: ...Wiring Diagram for the AK AKR Retrofill 60 EntelliGuard R Circuit Breaker Retrofill AKD 8 Installation Manual DEH41549 R05...

Страница 62: ...61 EntelliGuard R Circuit Breaker Retrofill AKD 8 Installation Manual DEH41549 R05...

Страница 63: ...62 EntelliGuard R Circuit Breaker Retrofill AKD 8 Installation Manual DEH41549 R05 NOTES...

Страница 64: ...ill AKD 8 Installation Manual DEH41549 R05 GE Energy Connections 41 Woodford Avenue Plainville CT 06062 www geindustrial com 2016 General Electric Company Trademark of the General Electric Company and...

Отзывы: