AN-31 Terminal X30/11 High Voltage
Range:
Function:
10 V
*
[par. AN-30 -
10 V]
Sets the analog input scaling value to
correspond to the high reference feedback
value (set in
).
AN-34 Term. X30/11 Low Ref./Feedb. Value
Range:
Function:
0
*
[-999999.999 -
999999.999]
Sets the analog input scaling value to
correspond to the low voltage value (set
in
parameter AN-30 Terminal X30/11 Low
AN-35 Term. X30/11 High Ref./Feedb. Value
Range:
Function:
100
*
[-999999.999 -
999999.999]
Sets the analog input scaling value to
correspond to the high-voltage value
parameter AN-31 Terminal X30/11
AN-36 Term. X30/11 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 - 10
s]
NOTICE
This parameter cannot be adjusted
while the motor is running.
Enter the filter time constant. This
constant is a first-order digital low-pass
filter time for suppressing electrical noise
in terminal X30/11. A high value improves
dampening, but also increases the delay
through the filter.
AN-37 Term. X30/11 Live Zero
Option:
Function:
This parameter makes it possible to disable the
live zero-monitoring. For example, to be used if
the analog outputs are used in a decentral I/O
system (when an analog output does not fulfil
any control function, but feeds a data storage
device).
[0]
Disabled
[1]
*
Enabled
3.7.6 AN-4# Analog Input 4 OPCGPIO
General Purpose I/O
Parameter group for configuring the scale and limits for
analog input 4 (X30/12) placed on General Purpose I/O
OPCGPIO General Purpose I/O.
AN-40 Terminal X30/12 Low Voltage
Range:
Function:
0.07 V
*
[0 - par.
AN-41 V]
Sets the analog input scaling value to
correspond to the low reference feedback
value set in
AN-41 Terminal X30/12 High Voltage
Range:
Function:
10 V
*
[par. AN-40 -
10 V]
Sets the analog input scaling value to
correspond to the high reference feedback
value set in
AN-44 Term. X30/12 Low Ref./Feedb. Value
Range:
Function:
0
*
[-999999.999 -
999999.999]
Sets the analog output scaling value to
correspond to the low voltage value set
in
parameter AN-40 Terminal X30/12 Low
AN-45 Term. X30/12 High Ref./Feedb. Value
Range:
Function:
100
*
[-999999.999 -
999999.999]
Sets the analog input scaling value to
correspond to the high-voltage value
set in
parameter AN-41 Terminal X30/12
AN-46 Term. X30/12 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 - 10
s]
NOTICE
This parameter cannot be adjusted
while the motor is running.
Enter the filter time constant. This
constant is a first-order digital low-pass
filter time for suppressing electrical noise
in terminal X30/12. A high value improves
dampening, but also increases the delay
through the filter.
AN-47 Term. X30/12 Live Zero
Option:
Function:
This parameter makes it possible to disable the
live zero-monitoring. For example, to be used if
the analog outputs are used in a decentral I/O
system (when an analog output does not fulfil
any control function, but feeds a data storage
device).
[0]
Disabled
[1]
*
Enabled
Parameter Description
72
03/2016 All rights reserved.
DET-620D