DigitalFlow™ XMT868i Startup Guide
43
Chapter 2. Initial Setup
2.4.3h Reynolds Correction
12.
Scroll to the appropriate choice to indicate whether you want
Reynolds Correction
.
•
If
Off
is selected, enter the
Calibration Factor
and press
[Enter]
.
•
If
Activ
is selected, the program asks for
KV Input Selection
. Scroll to
SIGS (Signals), SOUND
(Soundspeed)
or
STATC.
•
If
SIGS
or
SOUND
is selected, enter the
Calibration Factor
and press
[Enter]
.
•
If
STATC
is selected, enter the
Kinematic Viscosity
and press
[Enter]
.
Then enter the
Calibration
Factor
and press
[Enter]
.
•
For wetted transducers, the program returns to the
Channel PROGRAM
menu. You have completed entering
PIPE
parameters.
•
For clamp-on transducers, proceed to step 13 below.
Number of Traverses
13.
Scroll to the appropriate
Number of Traverses
(from 1 to 5) and press
[Enter]
.
14.
Accept the value for the
Transducer Spacing
by pressing
[Enter]
.
Record the value.
Note:
The XMT868i automatically calculates the transducer spacing. You should not enter a different value unless
specifically instructed by the factory.
The
User Program
returns to the
Channel PROGRAM
menu. You have completed entering
PIPE
parameters.
Note:
The site data programmed in this chapter is automatically stored in the meter’s non-volatile RAM (NVR). If the
power to the meter is disconnected, the same site data will be applied when the unit is next powered On.
2.4.3i
Procedure Options
Proceed to Chapter 3,
Operation
, for instructions on taking measurements. Or refer to the
Programming Manual
for
instructions on programming the Model XMT868i’s advanced features.
Содержание DigitalFlow XMT868i
Страница 2: ......
Страница 4: ...ii no content intended for this page ...
Страница 28: ...Chapter 1 Installation 20 DigitalFlow XMT868i Startup Guide no content intended for this page ...
Страница 34: ...Chapter 1 Installation DigitalFlow XMT868i Startup Guide 26 no content intended for this page ...
Страница 52: ...Chapter 2 Initial Setup 44 DigitalFlow XMT868i Startup Guide no content intended for this page ...
Страница 76: ...Appendix A CE Mark Compliance 68 DigitalFlow XMT868i Startup Guide no content intended for this page ...
Страница 86: ...Warranty 78 DigitalFlow XMT868i Startup Guide no content intended for this page ...
Страница 90: ...Index 82 DigitalFlow XMT868i Startup Guide no content intended for this page ...
Страница 92: ... no content intended for this page ...
Страница 94: ... no content intended for this page ...
Страница 95: ......