Digital Energy™
g
OPM_LPS_3UI_10K_20K_0US_V010.doc
33/38
Installation Guide
LP 33
/ 10 - 20 kVA
4.2 RELAY
CARD
Connections described in this chapter shall be done only by a trained person or
SERVICE ENGINEERS
.
The
Relay Card
, allows the programming of
4 output channels
on dry contacts, which can be
read on either terminal
J3
or plug
J4
(sub - D - male 9 pin).
Default configuration:
1
2
3 General
alarm
(NO)
4 Utility
failure
(NC)
5 C
(common)
6
Load on utility (NO)
7 Stop
operation
8 C
(common)
9 Utility
failure
(NO)
NO
= Normally Open
C
= Common
NC
= Normally Closed
Fig. 4.2-1 Relay Card
Output signals on voltage-free contacts
On terminals
J3
or
J4
connector
4 of the following 28 signals
can be selected from the display
(access only with password):
MENU / PARAMETER MENU /
LEVEL 2: SERVICE
.
0 - No signal
15 - Battery discharge
1 - Buzzer
16 - Manual bypass ON
2 - General alarm (NO)
17 - Rectifier ON
3 - Load on utility
18 - Inverter ON
4 - Stop operation
19 - Battery boostcharge
5 - Load on inverter
20 - Battery earth fault
6 - Utility failure
21 - Battery fault
7 - DC overvoltage
22 - Relay input 1
8 - Low battery
23 - Relay input 2
9 - Overload
24 - Relay output ON
10 - Overtemperature
25 - Relay output OFF
11 - Inverter utility not syncrony
26 - EPO (Emergency Power Off)
12 - Bypass locked
27 - IEM Mode ON
13 - Bypass utility failure
28 - General alarm (NC)
14 - Rectifier utility failure
NOTE !
The function
GEN-ON
is not available on the
Relay Card
.
In case this function is needed, the optional
Customer Interface
card must be
installed (see
Section 4.4.1)
.