Digital Energy™
g
OPM_LPS_3UI_10K_20K_0US_V010.doc
37/38
Installation Guide
LP 33
/ 10 - 20 kVA
EPO (Emergency Power Off)
An external Emergency switch (
NC - Normally Closed
voltage-free contact) can be connected on
terminals
X2 / 1, 2
or connector
J2 / 12, 25
of the
Customer Interface
(see
Fig. 4.4-1 / X2 & J2
).
7
89
10
1
1
22
21
20
19
18
7
J2
X1
2
1
JP3
X2
Fig. 4.4-2 PCB Customer Interface
LPS33U_01
0-020_UPS
EPO_01
OFF
Q1
Q2
ON
OFF
ON
F1 F2 F3
F13 F14
F15
F9 F10
F11
1
2
X7
P2 - Mainboard
J28
JP8
Fig. 4.4-3 PCB P2 - Mainboard
To enable this function, remove jumper
JP3
on the
Customer Interface
and
the cable on the terminal
X2 / 1, 2
(see
Fig. 4.4-2).
Verify if the cable on the terminal
X7 / 1, 2
and jumper
JP8
on the control
board
P2 – Mainboard
are OFF
(see
Fig. 4.4-3).
In a parallel system a separate NC
(Normally Closed)
contact must be connected
individually to each unit
.
When activated, this switch causes the immediate shutdown of
booster
,
battery-charger
,
inverter
;
and the
contactors K4, K6
and
K7
.
NOTE !
This procedure could imply a load shutdown.
When the
EPO
has been activated, the system must be restored as following
:
•
Press the push-button
EPO
(contact on
X2 / 1, 2
is closed again).
•
Perform the command
INVERTER OFF
entering the screen:
MENU/COMMAND MENU/
INVERTER OFF
.
COMMAND MENU
INVERTER ON
INVERTER OFF
٭
•
Start the inverter entering the screen:
MENU/COMMAND MENU/
INVERTER ON
.
COMMAND MENU
INVERTER ON
٭
INVERTER OFF