Digital Energy™
g
OPM_LPS_3UI_10K_20K_0US_V010.doc
13/38
Installation Guide
LP 33
/ 10 - 20 kVA
3.2 DELIVERY
When delivered, check carefully the
package integrity
and the
physical conditions of the UPS
equipment
.
In case of any damage sustained during transport, immediately inform the carrier and contact your
local
Service Center
.
A
detailed report
of the damage is necessary for any insurance claim.
NOTE !
A damaged UPS must never be installed or connected to
utility
or
battery
!
3.3 STORAGE
The equipment is carefully packed for
transport and storage so that it is in a perfect
condition when eventually installed.
Never leave an UPS outside the building and
do not store the UPS one on top of the other.
It is recommended to store the UPS in its
original package in a
dry, dust free room
and far away from chemical substances,
with temperature not exceeding -13°F
to
131°F
(-25°C to 55°C).
3.3.1
Storage of the UPS
Some important functions of the UPS, such as the customized functions, are defined by
parameters stored in a
RAM memory
.
The RAM is supplied by a small
backup battery
located on the
Control Unit board
.
If the storage time of the UPS exceeds
1 year
,
these functions
should be verified
by an
authorized
Service Center
before putting the UPS into operation.
NOTE !
In case of storage of the UPS pay attention to:
FRAGILE
SENSITIVE
TO DAMPNESS
TO HEAT
SENSITIVE
TO FROST
SENSITIVE