background image

Modifications reserved 

Page 7/10 

PRD_LPS_31E_8K0_20K_1GB_V021.doc 

Product Description 

LP 31 Series

 

The ‘

default screen’

 shows UPS model and actual load (values are examples): 

 

 

LP 15-31 

 

LOAD  37% 

 
The 

'information screens'

 show the UPSs system data: 

-  Mains voltage, mains frequency and the power delivered by the mains. 
-  Output voltage and output frequency, and the power delivered by the UPS. 
-  Power factor, crest factor and peak currents of the connected equipment. 
-  Temperature near the batteries, battery voltage and battery (dis)charging current. 
-  Remaining autonomy time (during mains failure). 
-  The total operating time of the UPS 
The 

'setup screens'

 show a programmable UPS function and its actual setting: 

-  System operating frequency. 
-  System operating voltage. 
- Battery 

capacity. 

- No-load 

shutdown 

(<2%). 

- Bypass 

enable/disable. 

-  Frequency tracking range. 
The 

'service screens'

 show service information targeted on trained service personnel: 

-  Serial number of the UPS, release number of the installed software. 
-  Service information on internal components, fan speed, internal DC voltage, internal temperature 

levels, peak input voltage, mean (bypass) input voltage, mean output voltage. 

-  Start of a quick battery test. 
-  Forced (manual) transfer to bypass. 
The 

'test screens'

 show the proceeding of the following tests: 

-  General system test. 
- Quick 

battery 

test. 

-  Battery calibration test. 
- Bypass 

test. 

 
 
 
 
 

3.3 Alarm Conditions 

 
The LCD screen on the front panel displays status messages and alarm messages. 
Three kinds of messages can be recognized. 
-  Status indications 

indicate the UPS operating mode. 

- Low 

priority 

alarms 

indicate 

abnormal operating situations; the screen message is accompanied by 

a 1x per sec. blinking red LED and a 1x per 8 seconds. sounding buzzer, resettable. 

-  High priority alarms 

indicate situations in which the connected load is at risk as a 

proper 

output voltage of the UPS is no longer guaranteed

; immediate action 

should be taken. 

 

The screen message is accompanied by a 1x per sec. blinking red 
LED 

'alarm'

 and a 1x per second sounding buzzer, resettable. 

 

Note: By using ComConnect, additional conditions can be monitored and signals include written screen 
messages (see section 5, Interfacing). 

Содержание Digital Energy LP 31 Series

Страница 1: ...rgy Uninterruptible Power Supply LP 31 Series 8 10 15 20 kVA 400 VAC CE Series 1 Manufactured by GE Consumer Industrial SA General Electric Company CH 6595 Riazzino Locarno Switzerland T 41 0 91 850 5...

Страница 2: ...itions 4 2 3 Mains Failure 4 2 4 Bypass operation 5 3 EXTERNAL DESCRIPTION 6 3 1 Front and Rear Panel 6 3 2 The LCD screen 6 3 3 Alarm Conditions 7 4 STANDARD FEATURES 8 5 INTERFACING 9 5 1 ComConnect...

Страница 3: ...tely Energy is stored as Direct Current DC but input and output energy must be Alternating Current AC in sine wave form The UPS therefore contains an input converter AC to DC and an output converter D...

Страница 4: ...2 3 Mains Failure In the event of a mains power failure i e absent or outside tolerance the output converter uses the energy reserve stored in the battery to continue to produce AC power ensuring unb...

Страница 5: ...onverter is unable to deliver the demanded output power overload overtemperature the bypass switch will automatically transfer the load to the mains If bypass operation is caused by an overload situat...

Страница 6: ...terfaces ComConnect RS232 LCD screen 2 x 16 characters Potentialfree contacts Push buttons down enter reset up CardConnect slot Buzzer resettable Manual bypass switch Inverter on off switch Input Outp...

Страница 7: ...e Service information on internal components fan speed internal DC voltage internal temperature levels peak input voltage mean bypass input voltage mean output voltage Start of a quick battery test Fo...

Страница 8: ...m level The test will after a complete recharge result in new autonomy predictions Communications port ComConnect 9 pin Sub D male plug No load shutdown Whenever the load is 2 of the maximum load and...

Страница 9: ...red conditions include mains voltage availability discharge level of batteries temperature of the batteries interactive control and diagnostic information for stand alone and network systems Interface...

Страница 10: ...o the user 6 2 Alarm Boxes An interface box linked to the ComConnect port the VIC RELAYBOX 01 translates the ComConnect signals to five independent changeover contacts with a maximum switching capacit...

Отзывы: