background image

Modifications reserved 

Page 5/10 

PRD_LPS_31E_8K0_20K_1GB_V021.doc 

Product Description 

LP 31 Series

 

2.4 Bypass operation 

 
The static switch provides transfer of the load to the line voltage without any interruption of the supply. 
The transfer is initiated by a signal from the output converter protection circuit in case of an overload, 
high temperature or output converter failure. 
When the conditions return to normal the load is automatically transferred back to the output converter. 
 
If the output converter is unable to deliver the demanded output power (overload, overtemperature) the 
bypass switch will automatically transfer the load to the mains. 
If bypass operation is caused by an overload situation, the UPS will switch back to output converter if 
the load is reduced to less than 100%. 
If bypass operation is caused by overtemperature, the unit will only switch back when the temperature 
has dropped below alarm level. 
When the normal situation is restored, the load will be transferred back to the output converter. 
 
 

 

 

Figure 3 - Bypass operation

 

 
 
If a power failure occurs during bypass operation, load power is lost. 
If the UPS functions under overload conditions it may not be able to protect the load. 
 

Содержание Digital Energy LP 31 Series

Страница 1: ...rgy Uninterruptible Power Supply LP 31 Series 8 10 15 20 kVA 400 VAC CE Series 1 Manufactured by GE Consumer Industrial SA General Electric Company CH 6595 Riazzino Locarno Switzerland T 41 0 91 850 5...

Страница 2: ...itions 4 2 3 Mains Failure 4 2 4 Bypass operation 5 3 EXTERNAL DESCRIPTION 6 3 1 Front and Rear Panel 6 3 2 The LCD screen 6 3 3 Alarm Conditions 7 4 STANDARD FEATURES 8 5 INTERFACING 9 5 1 ComConnect...

Страница 3: ...tely Energy is stored as Direct Current DC but input and output energy must be Alternating Current AC in sine wave form The UPS therefore contains an input converter AC to DC and an output converter D...

Страница 4: ...2 3 Mains Failure In the event of a mains power failure i e absent or outside tolerance the output converter uses the energy reserve stored in the battery to continue to produce AC power ensuring unb...

Страница 5: ...onverter is unable to deliver the demanded output power overload overtemperature the bypass switch will automatically transfer the load to the mains If bypass operation is caused by an overload situat...

Страница 6: ...terfaces ComConnect RS232 LCD screen 2 x 16 characters Potentialfree contacts Push buttons down enter reset up CardConnect slot Buzzer resettable Manual bypass switch Inverter on off switch Input Outp...

Страница 7: ...e Service information on internal components fan speed internal DC voltage internal temperature levels peak input voltage mean bypass input voltage mean output voltage Start of a quick battery test Fo...

Страница 8: ...m level The test will after a complete recharge result in new autonomy predictions Communications port ComConnect 9 pin Sub D male plug No load shutdown Whenever the load is 2 of the maximum load and...

Страница 9: ...red conditions include mains voltage availability discharge level of batteries temperature of the batteries interactive control and diagnostic information for stand alone and network systems Interface...

Страница 10: ...o the user 6 2 Alarm Boxes An interface box linked to the ComConnect port the VIC RELAYBOX 01 translates the ComConnect signals to five independent changeover contacts with a maximum switching capacit...

Отзывы: