![GE DIAC 66K Скачать руководство пользователя страница 52](http://html.mh-extra.com/html/ge/diac-66k/diac-66k_instruction-manual_131818052.webp)
7-
2
DIAC Type 66K Digital Overcurrent Relay
GE Power Management
7 SPECIFICATIONS
GEK-106621
7
7.2 RATINGS
FREQUENCY
System Frequency
50/60 Hz
CURRENT (1A
OR
5A MODELS)
TRANSIENT OVERREACH
Maximum Transient Overreach
7%
CONTACT RATINGS
7.3 ENVIRONMENTAL
AMBIENT TEMPERATURE
Storage:
–40 to +85°C
Operation:
–25 to +70°C
Humidity:
Up to 95% without condensing
INSULATION WITHSTAND TESTS
Impulse Voltage:
5 KV peak, 1.2/50
µ
s, 0.5 Joules per
IEC255-5, Class III
SURGE WITHSTAND CAPABILITY
Fast Transient:
Per ANSI C37.90.2-1989
Per IEC 60255-22-4
Oscillatory:
Per ANSI C37.90.1-1989
Per IEC 255-4
RADIO FREQUENCY WITHSTAND
25 MHz to 1 GHz, keyed every 1 MHz for 2 seconds
Per ANSI C37.90.2
Per IEC 60255-22-3
ELECTROSTATIC DISCHARGE
Per IEC 60255-22-2
NOTE: The DIAC Type 66K relay must be powered up at least once per year to avoid deterioration of
electrolytic capacitors and subsequent relay failiure.
Table 7–2: MAXIMUM PERMISSIBLE CURRENT
1 A MODEL
5 A MODEL
Continuous
3 A
15 A
3 seconds
50 A
250 A
1 second
100 A
500 A
Table 7–3: OPERATING CURRENT RANGE
1 A MODEL
5 A MODEL
minimum
0.095 A
0.475 A
I
2
T (constant)
1520
38000
Table 7–4: MAXIMUM PERMISSIBLE CURRENT
Voltage
Cont.
Make &
Carry 1
sec
Break
Max.
Load
DC
resistive
125V
250V
10A
30A
0.5 A
0.3 A
60 W
DC
inductive
L/R=40 ms
125V
250V
370V
10 A
30A
0.25 A
0.15 A
0.05 A
50 V
Содержание DIAC 66K
Страница 2: ......
Страница 4: ......
Страница 30: ...3 2 DIAC Type 66K Digital Overcurrent Relay GE Power Management 3 CALCULATION OF SETTINGS GEK 106261 3 ...
Страница 50: ...6 10 DIAC Type 66K Digital Overcurrent Relay GE Power Management 6 ACCEPTANCE PERIODIC TESTS GEK 106261 6 ...
Страница 54: ...A 2 DIAC Type 66K Digital Overcurrent Relay GE Power Management A 1 CHANGE NOTES APPENDIXA A ...
Страница 57: ...GE Power Management DIAC Type 66K Digital Overcurrent Relay NOTES ...
Страница 59: ...GE Power Management DIAC Type 66K Digital Overcurrent Relay NOTES ...