5 INSTALLATION
5
GEK-106261 5 INSTALLATION
5.1 ENVIRONMENT
Installation of the relay should be in a clean dry location that is free from dust.
5.2 MOUNTING
The relay should be securely mounted on a vertical surface that provides accessibility to both the front and rear
of the unit. The outline and panel drilling dimensions are provided in Figure 5–4: DIAC PANEL MOUNTING
AND DRILLING on page 5–5.
5.3 SURGE GROUND
The relay should be grounded to the station ground mat with a 12 AWG braided ground lead connected to ter-
minal 4. If the relay is to be retrofitted in a panel, terminal 4 should be removed from the new case and installed
into the old case. For the surge protection to function properly the relay must be grounded.