6 ACCEPTANCE/PERIODIC TESTS
6
6.8 INSTANTANEOUS HDO UNIT
The instantaneous HDO unit will react differently depending on how the signal is applied. If the signal is applied
suddenly with no prefault current, the operating time will be longer. If a prefault current is applied prior to the
fault the operating time will be shorter. The following test determines that the instantaneous unit is working cor-
rectly and confirms the operating time for faults applied with no prefault current.
Connect the relay as shown in Figure 6–2: DIAC 66K TOC INVERSE TIME TEST SETUP on page 6–4. Set
the instantaneous unit pickup to 2 Amps (for the 5 Amp rated relay) or 0.4 Amps (for the 1 Amp rated relay)
with a zero IOC delay setting. Also set the TOC pickup to its lowest setting not including zero. This allows the
Instantaneous HDO unit to function without coordinating with the TOC unit. Apply 6 Amps (for the 5 Amp rated
relay) or 1.2 Amps (for the 1 Amp rated relay) and measure the operating time. The operating time should be
between 32ms and 46ms. This time is subject to dependent on the multiple of pickup current and the fault inci-
dence angle. A graph of how the instantaneous unit varies as a function of input current is provided for refer-
ence in Figure 2–17: IOC CURVE FOR THE HDO INSTANTANEOUS UNIT on page 2–19.
Table 6–2: PICKUP TIMES FOR VARYING TIME DIALS
CURVE
PICKUP TIMES (IN SECONDS) FOR TIME DIAL SETTINGS
10
7
3
1
IAC 51
3.62 to 4.05
2.42 to 2.69
0.996 to 1.106
0.372 to 0.413
IAC 53
2.73 to 3.03
1.78 to 1.98
0.742 to 0.824
0.025 to 0.028
55-ST
0.29 to 0.32
0.21 to 0.23
0.10 to 0.12
0.058 to 0.064
57-MT
17.3 to 19.3
12.20 to 13.65
5.27 to 5.86
1.783 to 1.980
66-LT (Type 66K)
†
33.9 to 37.7
24.1 to 26.7
10.3 to 11.4
3.460 to 3.848
75-ST
0.577 to 0.641
0.424 to 0.471
0.200 to 0.221
0.09 to 0.10
IAC 77
1.810 to 2.013
1.20 to 1.33
0.545 to 0.605
0.228 to 0.253
95-ST
0.690 to 0.767
0.490 to 0.544
0.230 to 0.252
0.102 to 0.110
IEEE Inverse
3.108 to 3.450
2.206 to 2.450
0.95 to 1.06
0.345 to 0.384
IEEE Very Inverse
2.390 to 2.635
1.69 to 1.88
0.745 to 0.828
0.273 to 0.304
IEEE Extremely Inverse
2.32 to 2.58
1.65 to 1.84
0.734 to 0.815
0.266 to 0.296
IEC Inverse
3.94 to 4.37
2.79 to 3.10
1.21 to 1.34
0.431 to 0.478
IEC Very Inverse
3.060 to 3.402
2.170 to 2.415
0.95 to 1.05
0.332 to 0.369
IEC Extremely Inverse
2.950 to 3.284
2.109 to 2.330
0.913 to 1.015
0.329 to 0.364
Definite Time
9.5 to 10.5
6.65 to 7.31
2.83 to 3.15
0.95 to 1.05
I
2
T
0.3510 to 0.3865
0.256 to 0.282
0.124 to 0.137
0.0664 to 0.0730
†
MPU = 5X
Содержание DIAC 66K
Страница 2: ......
Страница 4: ......
Страница 30: ...3 2 DIAC Type 66K Digital Overcurrent Relay GE Power Management 3 CALCULATION OF SETTINGS GEK 106261 3 ...
Страница 50: ...6 10 DIAC Type 66K Digital Overcurrent Relay GE Power Management 6 ACCEPTANCE PERIODIC TESTS GEK 106261 6 ...
Страница 54: ...A 2 DIAC Type 66K Digital Overcurrent Relay GE Power Management A 1 CHANGE NOTES APPENDIXA A ...
Страница 57: ...GE Power Management DIAC Type 66K Digital Overcurrent Relay NOTES ...
Страница 59: ...GE Power Management DIAC Type 66K Digital Overcurrent Relay NOTES ...