8. KEYBOARD AND DISPLAY
GEK-106168E
DBF Breaker Failure Protection
49
8.6. CONFIGURATION MENU.
The DBF has a configuration unit which can only be accessed by means of the keyboard.
To enter the configuration, start from the main screen ‘DBF – GENERAL ELECTRIC’ and use the keyboard to
enter a four-digit code. If the code is correct the access to the configuration unit is permitted. If not it returns to the
main screen.
The code is unique for all the DBF relays and is not intended to be a password, but rather a simple safety
measure to avoid accidental changes to the configuration. This code is 7169, chosen to coincide with the ASCII
code for the initials GE.
After pressing 7169 at the front keyboard, and scrolling with the arrow keys, the following information will appear:
•
NET. BAUDRATE : The speed in bauds which the DBF will use for serial communications through the remote
port. The possible speeds are between 1200 and 19200 bauds.
•
NET.STOP BITS : The number of stop bits which are added to each byte which is transmitted on the serial
line. It is treated as a binary logic setting selected by means of the logic key 1/Y for 1 and 3/N for 2.
•
LOC. BAUDRATE : as above but for local communications.
•
LOC. STOP BITS : As above but for local communications.
•
LOCAL SETTINGS : Settings changes by local communications (allowed/not allowed).
•
REM SETTINGS : Settings changes by remote communications (allowed/not allowed).
•
LOC OPERATIONS : Operations being performed by local communications (computer directly connected)
(allowed/not allowed).
•
REM OPERATIONS : Operations being performed by remote communications (e.g. modem) (allowed/not
allowed).
•
UNIT NUMBER : Each DBF is identified by a unit number which it uses to identify the messages which are
sent to it on the remote communications line. This number can be between 1 and 255.
•
PASSWORD : To prevent unauthorized persons from communicating with the relay via a communications
program and changing the settings or performing operations, the relay has a password. This password can
only be seen on the relay display and takes the form of a number between 0 and 99999.
•
t TIME-OUT : Set to 0 if the relay is not working in a DDS integrated system. Set to the maximum time
between two synch signals coming from the PC host, when the relay is working in a DDS integrated system. If
a new synch signal is not received in this time the relay will report an error.
Содержание DBF
Страница 3: ......
Страница 7: ...LIST OF FIGURES iv DBF Breaker Failure Protection GEK 106168E ...
Страница 27: ...3 SETTINGS 20 DBF Breaker Failure Protection GEK 106168E ...
Страница 31: ...4 TECHNICAL CHARACTERISTICS 24 DBF Breaker Failure Protection GEK 106168E ...
Страница 45: ...6 ACCEPTANCE TESTS 38 DBF Breaker Failure Protection GEK 106168E ...
Страница 47: ...7 INSTALLATION AND MAINTENANCE 40 DBF Breaker Failure Protection GEK 106168E ...
Страница 57: ...8 KEYBOARD AND DISPLAY 50 DBF Breaker Failure Protection GEK 106168E ...
Страница 58: ...FIGURES GEK 106168E DBF Breaker Failure Protection 51 FIGURES FIGURES FIGURES FIGURES ...
Страница 59: ...FIGURES 52 DBF Breaker Failure Protection GEK 106168E FIGURE 1 BREAKER FAILURE LOGIC 189C4114 SHEET 2 ...
Страница 60: ...FIGURES GEK 106168E DBF Breaker Failure Protection 53 FIGURE 2 EXTERNAL CONNECTIONS 189C4114 SHEET 1 ...
Страница 61: ...FIGURES 54 DBF Breaker Failure Protection GEK 106168E FIGURE 3 FRONT VIEW 226B7412 H9 ...
Страница 62: ...FIGURES GEK 106168E DBF Breaker Failure Protection 55 FIGURE 4 REAR VIEW 226B7412H10 ...
Страница 63: ...FIGURES 56 DBF Breaker Failure Protection GEK 106168E FIGURE 5 DIMENSIONS DIAGRAM 226B6086H10 ...
Страница 64: ...FIGURES GEK 106168E DBF Breaker Failure Protection 57 FIGURE 6 PANEL DRILLING 226B6086H10 ...