6. ACCEPTANCE TESTS
GEK-106168E
DBF Breaker Failure Protection
35
6.9.3 INTERNAL ARC TEST
1.
Change setpoint GENERAL/FUNCTION PERMIT/50BF 3P FUNCTION to NO PER.
2.
Change setpoint TABLE 1/INTERNAL ARC SETTINGS/INT ARC TIMER to 2s.
3.
Energize digital input CC4 52/b A
4.
Apply 2A to terminals A1-A2 (phase A).
5.
Check that after INT ARC TIMER time delay, contact C2-D2 is closed.
6.
Repeat steps 3, 4 and 5 for phases B (terminals B1-B2) with digital input CC5 52/b B and C (terminals A3-A4)
with digital input CC6 52/b C.
6.9.4 3P NO I FUNCTION
1.
Change setpoint GENERAL/FUNCTION PERMIT/50BF 1P FUNCTION to NO PER.
2.
Change setpoint GENERAL/FUNCTION PERMIT/50BF 3P FUNCTION to NO PER.
3.
Change setpoint GENERAL/FUNCTION PERMIT/3P No INT FUNCT to PER.
4.
Change setpoint TABLE 1/50BF SETTINGS/Nº OUTPUT STAGES to 1
5.
Change setpoint TABLE 1/50BF SETTINGS/ 3P NO I TIMER T3 to 1s
6.
Change setpoint TABLE 1/50BF SETTINGS/LOW LOAD 2P to PER.
7.
Energize digital input CC7 3P BF INITIATE. If the relay has not an expansion board, energize CC1 PHASE A
BF INITIATE and CC2 PHASE B BF INITIATE.
8.
Check that after 3P NO I TIMER T3 (2s), the following contacts are closed:
C4-D4
A12-B12
C5-D5
C1-D1
C6-D6
C7-D7
9.
If the relay is provided with an expansion board, check that also the following contacts are closed:
E1-F1 E2-F2
E3-F3 E4-F4
E5-F5 E6-F6
6.9.5 NEUTRAL OVERCURRENT UNIT TEST
1.
Change setpoint GENERAL/FUNCTION PERMIT/50BF 1P FUNCTION to NO PER.
2.
Change setpoint GENERAL/FUNCTION PERMIT/50BF 3P FUNCTION to NO PER.
3.
Change setpoint GENERAL/FUNCTION PERMIT/3P No INT FUNCT to PER.
4.
Change setpoint TABLE 1/50BF SETTINGS/LOW LOAD 2P to PER.
5.
Energize digital inputs CC4, CC5 and CC6 (52b inputs).
6.
Energize digital inputs CC7 3P BF INITIATE. If the relay has not an expansion board, energize digital inputs
CC1 PHASE A BF INITIATE and CC2 PHASE B BF INITIATE.
7.
Apply 2A to terminals B3-B4 (neutral).
Содержание DBF
Страница 3: ......
Страница 7: ...LIST OF FIGURES iv DBF Breaker Failure Protection GEK 106168E ...
Страница 27: ...3 SETTINGS 20 DBF Breaker Failure Protection GEK 106168E ...
Страница 31: ...4 TECHNICAL CHARACTERISTICS 24 DBF Breaker Failure Protection GEK 106168E ...
Страница 45: ...6 ACCEPTANCE TESTS 38 DBF Breaker Failure Protection GEK 106168E ...
Страница 47: ...7 INSTALLATION AND MAINTENANCE 40 DBF Breaker Failure Protection GEK 106168E ...
Страница 57: ...8 KEYBOARD AND DISPLAY 50 DBF Breaker Failure Protection GEK 106168E ...
Страница 58: ...FIGURES GEK 106168E DBF Breaker Failure Protection 51 FIGURES FIGURES FIGURES FIGURES ...
Страница 59: ...FIGURES 52 DBF Breaker Failure Protection GEK 106168E FIGURE 1 BREAKER FAILURE LOGIC 189C4114 SHEET 2 ...
Страница 60: ...FIGURES GEK 106168E DBF Breaker Failure Protection 53 FIGURE 2 EXTERNAL CONNECTIONS 189C4114 SHEET 1 ...
Страница 61: ...FIGURES 54 DBF Breaker Failure Protection GEK 106168E FIGURE 3 FRONT VIEW 226B7412 H9 ...
Страница 62: ...FIGURES GEK 106168E DBF Breaker Failure Protection 55 FIGURE 4 REAR VIEW 226B7412H10 ...
Страница 63: ...FIGURES 56 DBF Breaker Failure Protection GEK 106168E FIGURE 5 DIMENSIONS DIAGRAM 226B6086H10 ...
Страница 64: ...FIGURES GEK 106168E DBF Breaker Failure Protection 57 FIGURE 6 PANEL DRILLING 226B6086H10 ...