B-54
D60 Line Distance Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
81C2
Reserved Register T3
-2147483647 to
2147483647
---
1
F004
0
81C4
Reserved Register T4
0 to 4294967295
---
1
F003
0
81C6
Reserved Register T5
0 to 4294967295
---
1
F003
0
81C8
Reserved Register T6
0 to 4294967295
---
1
F003
0
81CA
Reserved Register T7
0 to 4294967295
---
1
F003
0
81CC
Reserved Register T8
0 to 4294967295
---
1
F003
0
Breaker Failure (Read/Write Grouped Setting) (6 Modules)
8600
Breaker Failure 1 Function
0 to 1
---
1
F102
0 (Disabled)
8601
Breaker Failure 1 Mode
0 to 1
---
1
F157
0 (3-Pole)
8602
Breaker Failure 1 Source
0 to 5
---
1
F167
0 (SRC 1)
8603
Breaker Failure 1 Amp Supervision
0 to 1
---
1
F126
1 (Yes)
8604
Breaker Failure 1 Use Seal-In
0 to 1
---
1
F126
1 (Yes)
8605
Breaker Failure 1 Three Pole Initiate
0 to 4294967295
---
1
F300
0
8607
Breaker Failure 1 Block
0 to 4294967295
---
1
F300
0
8609
Breaker Failure 1 Phase Amp Supv Pickup
0.001 to 30
pu
0.001
F001
1050
860A
Breaker Failure 1 Neutral Amp Supv Pickup
0.001 to 30
pu
0.001
F001
1050
860B
Breaker Failure 1 Use Timer 1
0 to 1
---
1
F126
1 (Yes)
860C
Breaker Failure 1 Timer 1 Pickup
0 to 65.535
s
0.001
F001
0
860D
Breaker Failure 1 Use Timer 2
0 to 1
---
1
F126
1 (Yes)
860E
Breaker Failure 1 Timer 2 Pickup
0 to 65.535
s
0.001
F001
0
860F
Breaker Failure 1 Use Timer 3
0 to 1
---
1
F126
1 (Yes)
8610
Breaker Failure 1 Timer 3 Pickup
0 to 65.535
s
0.001
F001
0
8611
Breaker Failure 1 Breaker Status 1 Phase A/3P
0 to 4294967295
---
1
F300
0
8613
Breaker Failure 1 Breaker Status 2 Phase A/3P
0 to 4294967295
---
1
F300
0
8615
Breaker Failure 1 Breaker Test On
0 to 4294967295
---
1
F300
0
8617
Breaker Failure 1 Phase Amp Hiset Pickup
0.001 to 30
pu
0.001
F001
1050
8618
Breaker Failure 1 Neutral Amp Hiset Pickup
0.001 to 30
pu
0.001
F001
1050
8619
Breaker Failure 1 Phase Amp Loset Pickup
0.001 to 30
pu
0.001
F001
1050
861A
Breaker Failure 1 Neutral Amp Loset Pickup
0.001 to 30
pu
0.001
F001
1050
861B
Breaker Failure 1 Loset Time
0 to 65.535
s
0.001
F001
0
861C
Breaker Failure 1 Trip Dropout Delay
0 to 65.535
s
0.001
F001
0
861D
Breaker Failure 1 Target
0 to 2
---
1
F109
0 (Self-reset)
861E
Breaker Failure 1 Events
0 to 1
---
1
F102
0 (Disabled)
861F
Breaker Failure 1 Phase A Initiate
0 to 4294967295
---
1
F300
0
8621
Breaker Failure 1 Phase B Initiate
0 to 4294967295
---
1
F300
0
8623
Breaker Failure 1 Phase C Initiate
0 to 4294967295
---
1
F300
0
8625
Breaker Failure 1 Breaker Status 1 Phase B
0 to 4294967295
---
1
F300
0
8627
Breaker Failure 1 Breaker Status 1 Phase C
0 to 4294967295
---
1
F300
0
8629
Breaker Failure 1 Breaker Status 2 Phase B
0 to 4294967295
---
1
F300
0
862B
Breaker Failure 1 Breaker Status 2 Phase C
0 to 4294967295
---
1
F300
0
862D
...Repeated for Breaker Failure 2
865A
...Repeated for Breaker Failure 3
8687
...Repeated for Breaker Failure 4
86B4
...Repeated for Breaker Failure 5
86E1
...Repeated for Breaker Failure 6
FlexState Settings (Read/Write Setting)
8800
FlexState Parameters (256 items)
0 to 4294967295
---
---
F300
0
Digital Elements (Read/Write Setting) (48 Modules)
8A00
Digital Element 1 Function
0 to 1
---
1
F102
0 (Disabled)
8A01
Digital Element 1 Name
---
---
---
F203
“Dig Element 1“
8A09
Digital Element 1 Input
0 to 4294967295
---
1
F300
0
8A0B
Digital Element 1 Pickup Delay
0 to 999999.999
s
0.001
F003
0
8A0D
Digital Element 1 Reset Delay
0 to 999999.999
s
0.001
F003
0
Table B–10: MODBUS MEMORY MAP (Sheet 46 of 77)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...